Endres+Hauser Tank Side Monitor NRF590 Operating instructions

Type
Operating instructions
BA256F/00/en/10.05
52020859
Valid as of software version:
V 02.02
Operating Instructions
Tank Side Monitor NRF590
Inventory Control
Software Version 02.02
Notes on Software Version SW 02.xx Tank Side Monitor NRF590
2
Notes on Software Version SW 02.xx
Key operation
From Software Version SW 02.01 onwards, the operation of the optical keys of the Tank Side
Monitor NRF590 is based on the distinction between "pressing" and "holding" of the keys.
Pressing a key means to touch the optical key and to release it after a short time (< 2 seconds).
The key operation "press" is required for most menue operations.
Holding a key means to touch the optical key for more than 2 seconds.
The key operation "hold" is required for scrolling in lists or changing of values.
The change of the display contrast is based on pressing the optical keys. When pressing the
according key combination, the contrast change screen appears, where the contrast may be changed
by continuously holding the respective keys.
Automatic HART scan
From Software Version 02.01 onwards, the HART scan is performed automatically by the NRF590
HART Master and needs not to be started from the operating menue.
Modbus termination
From Software Version 02.01 onwards, the Modbus termination is activated via menu operation,
not by a hardware jumper.
Tank Side Monitor NRF590 Table of contents
3
Table of contents
1 Safety instructions . . . . . . . . . . . . . . . . 4
1.1 Designated use . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.2 Installation, commissioning, operation . . . . . . . . . . . 4
1.3 Operational safety . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.4 Return . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.5 Notes on safety conventions and symbols . . . . . . . . . 6
2 Identification . . . . . . . . . . . . . . . . . . . . 7
2.1 Parts of the Tank Side Monitor . . . . . . . . . . . . . . . . 7
2.2 Nameplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.3 Product structure . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.4 Scope of delivery . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.5 Supplied documentation . . . . . . . . . . . . . . . . . . . . 10
2.6 CE mark, declaration of conformity . . . . . . . . . . . . 11
2.7 Registered trademarks . . . . . . . . . . . . . . . . . . . . . . 11
3 Installation . . . . . . . . . . . . . . . . . . . . . 12
3.1 Design, dimensions . . . . . . . . . . . . . . . . . . . . . . . . 12
3.2 Installation variants . . . . . . . . . . . . . . . . . . . . . . . . 12
3.3 Rotating the housing . . . . . . . . . . . . . . . . . . . . . . . 14
3.4 Rotating the display module . . . . . . . . . . . . . . . . . . 15
3.5 Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
3.6 Post-installation check . . . . . . . . . . . . . . . . . . . . . . 16
4 Wiring . . . . . . . . . . . . . . . . . . . . . . . . 17
4.1 Wiring the Non-IS (Ex d) connections . . . . . . . . . . 17
4.2 Wiring the IS (Ex ia) connection . . . . . . . . . . . . . . 24
5 Operation . . . . . . . . . . . . . . . . . . . . . . 27
5.1 Display and operating elements . . . . . . . . . . . . . . . 27
5.2 Key assignment . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
5.3 Measured value display . . . . . . . . . . . . . . . . . . . . . 30
5.4 Operating menu . . . . . . . . . . . . . . . . . . . . . . . . . . 32
5.5 Locking/unlocking parameters . . . . . . . . . . . . . . . 36
6 Commissioning. . . . . . . . . . . . . . . . . . 38
6.1 Theoretical background . . . . . . . . . . . . . . . . . . . . . 38
6.2 Configuration of the HART Interface . . . . . . . . . . . 41
6.3 Addressing of the HART instruments . . . . . . . . . . . 45
6.4 Steps of the Commissioning Procedure . . . . . . . . . 46
7 Maintenance and repairs . . . . . . . . . . 48
7.1 Exterior cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . 48
7.2 Replacing seals . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
7.3 Repairs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
7.4 Repairs to Ex-approved devices . . . . . . . . . . . . . . . 48
7.5 Spare parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
7.6 Return . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
7.7 Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
7.8 Software history . . . . . . . . . . . . . . . . . . . . . . . . . . 51
8 Accessories . . . . . . . . . . . . . . . . . . . . . 52
8.1 Discrete I/O modules . . . . . . . . . . . . . . . . . . . . . . 52
8.2 Rail mounting kit . . . . . . . . . . . . . . . . . . . . . . . . . . 56
9 Technical Data. . . . . . . . . . . . . . . . . . . 57
9.1 Technical Data at a Glance . . . . . . . . . . . . . . . . . . . 57
10 Operating Menu . . . . . . . . . . . . . . . . . 64
10.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
11 Appendix. . . . . . . . . . . . . . . . . . . . . . . 65
11.1 Function and system design . . . . . . . . . . . . . . . . . . 65
11.2 Tank calculations . . . . . . . . . . . . . . . . . . . . . . . . . . 66
11.3 The block model of the Tank Side Monitor . . . . . . . 68
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Safety instructions Tank Side Monitor NRF590
4
1 Safety instructions
1.1 Designated use
The Tank Side Monitor NRF590 is a monitoring unit for use with the Endress+Hauser Micropilot
M and Micropilot S-series radars and other HART compatible devices. Mounted at the tank side,
the NRF590 provides indication of measured data, allows configuration and supplies intrinsically
safe (i.s.) power to the connected sensors on the tank. Various industry standard digital gauging
communication protocols support integration into open architecture tank gauging and inventory
systems.
1.2 Installation, commissioning, operation
Mounting, electrical installation, start-up and maintenance of the instrument may only be carried
out by trained personnel authorized by the operator of the facility.
• Personnel must absolutely and without fail read and understand this Operating Manual before
carrying out its instructions.
• The instrument may only be operated by personnel who are authorized and trained by the
operator of the facility. All instructions in this Manual are to be observed without fail.
• The installer has to make sure that the measuring system is correctly wired according to the
wiring diagrams. The measuring system is to be grounded.
Please observe all provisions valid for your country and pertaining to the opening and repairing of
electrical devices.
1.3 Operational safety
1.3.1 Hazardous areas
Measuring systems for use in hazardous environments are accompanied by separate "Ex
documentation", which is an integral part of this Operating Manual. Strict compliance with the
installation instructions and ratings as stated in this supplementary documentation is mandatory.
• Ensure that all personnel are suitably qualified.
Observe the specifications in the certificate as well as national and local standards and regulations.
1.3.2 FCC approval
This device complies with part 15 of the FCC Rules. Operation is subject to the following two
conditions: (1) This device may not cause harmful interference, and (2) this device must accept any
interference received, including interference that may cause
undesired operation.
"Caution!
Changes or modifications not expressly approved by the part responsible for
compliance could void the user’s authority to operate the equipment.
Tank Side Monitor NRF590 Safety instructions
5
1.4 Return
The following procedures must be carried out before a transmitter is sent to Endress+Hauser for
repair:
• Always enclose a duly completed "Declaration of Contamination" form. Only then can Endress
+Hauser transport, examine and repair a returned device.
• Enclose special handling instructions if necessary, for example a safety data sheet as per EN 91/
155/EEC.
Remove all residue which may be present. Pay special attention to the gasket grooves and crevices
where fluid may be present. This is especially important if the fluid is dangerous to health, e.g.
corrosive, poisonous, carcinogenic, radioactive, etc.
!Note!
A copy of the “Declaration of Contamination” is included at the end of this operating manual.
"Caution!
• No instrument should be sent back for repair without all dangerous material being completely
removed first, e.g. in scratches or diffused through plastic.
• Incomplete cleaning of the instrument may result in waste disposal or cause harm to personnel
(burns, etc.). Any costs arising from this will be charged to the operator of the instrument.
Safety instructions Tank Side Monitor NRF590
6
1.5 Notes on safety conventions and symbols
In order to highlight safety-relevant or alternative operating procedures in the manual, the following
conventions have been used, each indicated by a corresponding symbol in the margin.
Safety conventions
#
Warning!
A warning highlights actions or procedures which, if not performed correctly, will lead to personal
injury, a safety hazard or destruction of the instrument
"
Caution!
Caution highlights actions or procedures which, if not performed correctly, may lead to personal
injury or incorrect functioning of the instrument
!
Note!
A note highlights actions or procedures which, if not performed correctly, may indirectly affect
operation or may lead to an instrument response which is not planned
Explosion protection
0
Device certified for use in explosion hazardous area
If the device has this symbol embossed on its name plate it can be installed in an explosion hazardous
area
-
Explosion hazardous area
Symbol used in drawings to indicate explosion hazardous areas. Devices located in and wiring
entering areas with the designation “explosion hazardous areas” must conform with the stated type
of protection.
.
Safe area (non-explosion hazardous area)
Symbol used in drawings to indicate, if necessary, non-explosion hazardous areas. Devices located in
safe areas still require a certificate if their outputs run into explosion hazardous areas
Electrical symbols
%
Direct voltage
A terminal to which or from which a direct current or voltage may be applied or supplied
&
Alternating voltage
A terminal to which or from which an alternating (sine-wave) current or voltage may be applied or
supplied
)
Grounded terminal
A grounded terminal, which as far as the operator is concerned, is already grounded by means of an
earth grounding system
*
Protective grounding (earth) terminal
A terminal which must be connected to earth ground prior to making any other connection to the
equipment
+
Equipotential connection (earth bonding)
A connection made to the plant grounding system which may be of type e.g. neutral star or
equipotential line according to national or company practice
Temperature resistance of the connection cables
States, that the connection cables must be resistant to a temperature of at least 85 °C.
t >85°C
Tank Side Monitor NRF590 Identification
7
2 Identification
2.1 Parts of the Tank Side Monitor
L00-NRF590-03-00-06-yy-001
A
AA
A: Non-i.s. terminal compartment; B
BB
B: i.s. terminal compartment; C
CC
C: graphical display; D
DD
D: optical keys; E
EE
E: cable entries for
non-i.s. connection (with glands according to product structure); F
FF
F: cable entries for i.s. connection (with glands according
to product structure); G
GG
G: nameplate; H
HH
H: grounding terminals; I
II
I: mounting plate
A
B
C
D
E
F
G
H
I
Identification Tank Side Monitor NRF590
8
2.2 Nameplate
L00-NRF590xx-18-00-00-yy-001
1
11
1: complete product designation; 2/3
2/32/3
2/3: power supply specifications; 4
44
4: year of construction; 5
55
5: NMi certification number;
6/7
6/76/7
6/7: PTB certification number; 8
88
8: serial number; 9
99
9: reference to installation drawing or safety instructions (for Ex-certified
instrument versions only); 10
1010
10: type of protection (for Ex-certified instrument versions only); 11:
11:11:
11: admissible ambient
temperature; 12:
12:12:
12: certification symbols
Dat./Insp.:
Baujahr
Year of constr.
Zertifikat-Nr.
Certification no.
Tank-Nr.
Tank-no.
IP 65
Ser.No.:
Order Code: NRF590
XA 160 F -
Made in Germany, D-79689 Maulburg
Tank Side Monitor
if modification
see sep. label
X=
T
amb
1
8
2
34
5
6
7
9
10
11
12
Tank Side Monitor NRF590 Identification
9
2.3 Product structure
10 Certificates
A For non-hazardous areas
6 ATEX II 2 (1) EEx d (ia) IIC T4
U CSA XP Cl. I, Div 1, Gr. A-D
S FM XP Cl. I, Div 1, Gr. A-D
K TIIS EEx d (ia) IIC T4 (in preparation)
Y Special version, to be specified
20 Field communication protocol
E ENRAF BPM, non-IS 4-20mA input, non-IS 4-20mA HART output
G GPE, non-IS 4-20mA HART output
1 WM550, non-IS 4-20mA output, Whessoe protocol with dual communication
3 Varec Mark/Space, non-IS 4-20mA input, non-IS 4-20mA HART output
4 Modbus w/o 4-20mA input or output, EIA 485
5 Modbus, non-IS 4-20mA input, non IS 4-20mA HART output, EIA 485
7 L&J, non-IS 4-20mA input, non-IS 4-20mA HART output
8 V1, non-IS 4-20mA output, non-IS 4-20mA HART output, relay output
9 Special version, to be specified
30 Power supply
A Power supply 18...55 VAC/DC
B Power supply 55...264V AC
Y Special version, to be specified
40 Spot RTD option
0 Without RTD temperature input
1 With spot RTD temperature input, IS
9 Special version, to be specified
50 Discrete I/O Module A
A Without discrete input/output module A
B Discrete input module A, 90...140V AC
C Discrete input module A, 3...32V DC
D Discrete input module A, 180...250V AC
E Discrete input module A, 35...60V AC/DC
G Discrete output module A, 24...250V AC
H Discrete output module A, 3...60V DC
J Discrete output module A, 24...140V AC
K Discrete output module A, 4...200V DC
R Relay output A, 0-100 VDC, 0-120VAC
Y Special version, to be specified
60 Discrete I/O Module B
A Without discrete input/output module B
B Discrete input module B, 90...140V AC
C Discrete input module B, 3...32V DC
D Discrete input module B, 180...250V AC
E Discrete input module B, 35...60V AC/DC
G Discrete output module B, 24...250V AC
H Discrete output module B, 3...60V DC
J Discrete output module B, 24...140V AC
K Discrete output module B, 4...200V DC
R Relay output B, 0-100 VDC, 0-120VAC
Y Special version, to be specified
70 Additional intrinsically safe module
0 Additional IS module not selected
1 Additional IS 4...20mA analogue input
2 Integrated 4...20mA input, two discrete inputs
9 Special version, to be specified
Product designation (part 1)
Identification Tank Side Monitor NRF590
10
2.4 Scope of delivery
• Instrument according to the version ordered
• ToF Tool - Field Tool Package (2 CD-ROMs)
• Accessories (as ordered)
2.5 Supplied documentation
80 Glands/Entries - non IS
F 2 x G 1/2" gland (in preparation)
B 2 x Ex d M20x1.5 entries
C 2 x Ex d G 1/2" entries
D 2 x Ex d 1/2" NPT entries
E 2 x Ex d 3/4" NPT entries
H 3 x Ex d M20x1.5 entries
K 3 x Ex d G 1/2" entries
L 3 x Ex d 1/2" NPT entries
G 3 x Ex d 3/4" NPT entries (in preparation)
Y Special version, to be specified
90 Gland/Entry - IS compartment
2 M25x1.5 glands, 13...18mm, intrinsically safe compartment
3 G 1/2" entries, intrinsically safe compartment
4 1/2" NPT entries, intrinsically safe compartment
5 3/4" NPT entries, intrinsically safe compartment
9 Special version, to be specified
100 Custody transfer type approvals
N Custody transfer type approval not selected
A NMi type approval
G PTB type approval
Y Special version, to be specified
110 Additional options
0 Additional option not selected
9 Special version, to be specified
NRF590 - complete product designation
Document Designation Content/Remarks
BA 256F
(this manual) Operating Instructions
describes installation and commissioning of the Tank Side Monitor. Only
those functions of the operating menu are included, which are used for a
standard measuring task. Any additional functions are not included.
BA 257F Description of
Instrument Functions
contains a detailed description of all the functions of the Tank Side
Monitor.
XA 160F
XA 169F Safety Instructions only for instrument versions approved for use in explosion hazardous
areas;
the nameplate specifies, which of these documents is relevant for your
instrument version.
ZD 084F
ZD 085F
ZD 103F
ZD 104F
Installation Drawings
ZE 253F NMi Certificate only for instrument versions with the respective custody transfer
approval
ZE 255F PTB Certificate
Tank Side Monitor NRF590 Identification
11
2.6 CE mark, declaration of conformity
The instrument is designed to meet state-of-the-art safety requirements, has been tested and left the
factory in a condition in which it is safe to operate. The instrument complies with the applicable
standards and regulations in accordance with EN 61010 "Protection Measures for Electrical
Equipment for Measurement, Control, Regulation and Laboratory Procedures". The instrument
described in this manual thus complies with the statutory requirements of the EG directives.
Endress+Hauser confirms the successful testing of the instrument by affixing to it the CE mark.
2.7 Registered trademarks
HART®
Registered trademark of HART Communication Foundation, Austin, USA
ToF®
Registered trademark of the company Endress+Hauser GmbH+Co. KG, Maulburg, Germany
Installation Tank Side Monitor NRF590
12
3 Installation
3.1 Design, dimensions
L00-NRF590-06-00-06-yy-001
3.2 Installation variants
3.2.1 Wall mounting
L00-NRF590-17-00-06-xx-001
3.94"
(100 mm)
3.94"
(100 mm)
Ø 8.6 (M8)
Tank Side Monitor NRF590 Installation
13
3.2.2 Mounting on vertical rail
L00-NRF590-17-00-06-en-002
3.2.3 Mounting on horizontal rail
L00-NRF590-17-00-06-en-003
!Note!
The rail mounting kit is available as an accessory, see chap. accessories.
3.5" (90 mm)
maximum
Rail mounting kit
(Order No.: 52013134) Grounding
connections
Rail mounting kit
(Order No.: 52013134)
maximum
Ø3.5" (90 mm)
Installation Tank Side Monitor NRF590
14
3.3 Rotating the housing
For easy access to the display or the terminal
compartment, the upper part of the housing can
be rotated into an arbitrary position. In order to
do this, perform the following steps:
1. Loosen the alignment pin using a 4 mm
Allen key (approx. 5 turns).
2. Rotate the upper part of the housing to the
desired position.
3. Tighten the pin securely.
L00-NRF590-17-00-06-yy-005
Tank Side Monitor NRF590 Installation
15
3.4 Rotating the display module
In order to facilitate operation and reading of the
measuring value, the display module can be
rotated in the following way:
#
Warning!
Danger from elctrical schock! Switch off power
supply before opening the housing.
1. Using a 3 mm /7/64") Allen wrench, losen
the safety pin for the display lid.
2. Unscrew the display lid.
!
Note!
If the display is difficult to unscrew, unplug
one of the cables from the cable gland to
allow air to enter the housing. Then,
attempt once again to unscrew the display
lid.
3. Push in the two flat areas on each side of
the display module. Remove the Module
from the holder, rotate it into the desired
position and put it back onto the holder.
Snap-in positions are located at an angle of
45° from each other.
#
Warning!
The maximum angle of rotation is 180° in
both directions (measured from the initial
position).
4. Replace the display lid on the Tank Side
Monitor housing.
!
Note!
Make sure to clean the threads of the lid to
remove any dust or paritcles. Check that
O-ring is in place and reapply anti-seize
grease.
5. Adjust the safety pin so it is set over the
display lid and tighten.
L00-NRF590-17-00-06-yy-006
4 x 45 °
4 x 45 °
Installation Tank Side Monitor NRF590
16
3.5 Grounding
The NRF590 must be grounded to the tank potential before communication and power connections
are made. The connections (A 4mm2) from each outer ground plug of the NRF590 to the tank
ground must be made before any other wiring connections are made. All grounding must be
compliant with local and company regulations and checked before the equipment is commissioned.
L00-NRF590-04-08-08-en-004
It is recommended to connect the cable shields of the tank instrumentation centrally to the NRF590,
see chap. 4.2.3.
3.6 Post-installation check
After the Tank Side Monitor has been installed, perform the following checks:
• Is the measuring instrument damaged (visual check)?
• Have the mounting bolts been tightend securely?
• Are both grounding terminals connected to tank ground?
A > 4 mm2
Tank Ground
Tank Side Monitor NRF590 Wiring
17
4 Wiring
4.1 Wiring the Non-IS (Ex d) connections
4.1.1 The procedure
!
Note!
Before starting the wiring procedure, make sure
that the supply voltage is switched off.
1. Using a 3 mm (7/64") Allen wrench, losen
the safety pin for the lid.
2. Unscrew the lid of the terminal
compartment.
3. Push the power and signal cables through
the appropriate cable glands.
4. Wire up according to the terminal
assignment diagram.
5. Screw the lid of the terminal compartment
securely back onto the transmitter housing.
!
Note!
Make sure to clean the threads of the lid to
remove any dust or particles. Check that
O-ring is in place and reapply anti-seize
grease.
6. Adjust the safety pin so it is set over the
display lid and tighten.
L00-NRF590-04-08-08-yy-005
Wiring Tank Side Monitor NRF590
18
4.1.2 Terminal assignment of the field protocol/host side
L00-NRF590-04-08-08-en-002
04 A1/+
05 A2/-
06 B1/+
07 B2/-
01 L/+
02 N/-
08 C1
09 C2
10 C3
11 C4
12 C5
13 C6
14 C7
15 C8
01 L/+
04 A1/+
07 B2/-
08 C1
10 C3
12 C5
14 C7
02 N/-
05 A2/-
06 B1/+
00 S
09 C2
11 C4
13 C6
15 C8
00 S
Power
Digital I/O A
Digital I/O B
Cable screen
Field protocol
and
Analog I/O
(for details
see table)
Power
Digital I/O A
Digital I/O B
Cable screen
Field protocol
and
Analog I/O
(for details
see table)
Standard (not certified)
ATEX
FM
CSA TIIS
Tank Side Monitor NRF590 Wiring
19
Terminal 01
L/+
02
N/-
04
A1/+
05
A2/-
06
B1/+
07
B2/-
00
S
Power supply Discrete I/O A
+
Discrete I/O A
-
Discrete I/O B
+
Discrete I/O B
-Cable screen
08
C1
09
C2
10
C3
11
C4
12
C5
13
C6
14
C7
15
C8
V1 4 ... 20 mA
output1 #2 V1A V1B 0 V10V
4 ... 20 mA
output #1
+HART
discrete output
1C
discrete output
2C
EIA-485
Modbus not used2485-B 485-A 0 V 0 V1
4 ... 20 mA
output3
+HART
4 ... 20 mA
input3+24 V1
Whessoe
WM550
4 ... 20 mA
output1 #2 Loop 1- Loop 1+ 0 V10V
4 ... 20 mA
output #1
+HART
Loop 2- Loop 2+
Enraf BPM not used2TT0 V0 V
1
4 ... 20 mA
output
+HART
4 ... 20 mA
input +24 V1
Varec
Mark/Space V+ Space Mark 0 V (V-) 0 V1
4 ... 20 mA
output
+ HART
4 ... 20 mA
input +24 V1
L&J Tankway Power Encoder Computer Ground 0 V1
4 ... 20 mA
output
+ HART
4 ... 20 mA
input +24 V1
GPE 4 ... 20 mA
output1 #2 Loop 1- Loop 1+ 0 V10V
4 ... 20 mA
output #1
+ HART
do not connect do not connect
1) In case an "Ex d" rated 4-wire level gauge version is used, the power supply can be obtained from these terminals (21V ±10%).
2) The internal voltage at this terminal is 0 V, however, shielding and signal common should be connected to terminal 11 or 12.
3) option, s. pos. 20 of the product structure
Wiring Tank Side Monitor NRF590
20
4.1.3 Connection of the field protocols
Sakura V1
The V1 protocol provides 2 wire communication allowing up to 10 devices to operate on a loop. V1
connects to terminals 9-10.
Max. distance: 6000 m
EIA-485 Modbus
The NRF590 protocol uses a shielded 3-wire EIA-485 hardware interface to communicate with the
modbus master. EIA-485 is a high speed, differential communications network that allows up to 32
devices to operate on one network.
• Using one shielded twisted pair of 18 AWG wire, connect the EIA-485 at terminal 9 and 10.
Termination of the EIA-485 bus at the NRF590 can be set in the operating menu (only enable on
end device in a loop)
• Connect the 3rd wire from the control system signal ground (0V) to terminal 8.
• Max distance: 4000 ft (1300 m)
Whessoematic WM550
The WM550 protocol provides 2 wire, current loop communication and allows up to 16 devices
per loop. For redundancy (safety function) two wire pairs are used. They always transmit the same
values. The WM550-loops connect to terminals 9 - 10 and 14 - 15.
Max. distance: 7000 m
Enraf BPM
The Enraf BPM protocol provides 2 wire communication allowing up to 10 devices to operate on a
loop. Enraf BPM connects to terminals 9-10.
Max. distance: 10000 m
Varec Mark/Space
For a NRF590 using the Mark/Space field communications option, the following additional wiring
connections must be made:
Run 2 twisted pairs (one power, one communication) of 18 AWG wire (Mark/Space wires) into
the upper terminal compartment through one of the conduit entries along with the 48 Vdc power
wiring.
• Connect the Mark line to terminal 10 and the Space line to terminal 9.
• Connect to power supply at terminals 8 and 11.
L&J Tankway
Including power and ground, L&J is a 4-wire system, allowing 50+ devices to be connected on the
communication bus. L&J connects to terminals 8 through 11.
GPE
The GPE protocol provides 2 wire current loop communication. GPE connects to terminal 9-10.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84