  • Hello! I am an AI chatbot trained to assist you with the ICP DAS USA tM-AD4P2C2 Quick Start. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
tM-AD4P2C2 4-channel Multifunction AI, 2-channel DI module- QuickStart (Jun/2016)
ICP DAS USA, Inc. | www.icpdas-usa.com | 1-310-517-9888 | 24309 Narbonne Ave. Suite 200. Lomita, CA 90717
1
tM-AD4P2C2
4-channel Multifunction Analog Input, 2-
channel Digital Input module
Quick Start Guide
Product Info:
http://www.icpdas-usa.com/tm_ad4p2c2.html
http://www.icpdas-usa.com/dcon_utility_pro.html
1. Introduction
The tM-AD4P2C2 is a multifunction module that includes 4 analog input channels, 2
digital input channels and 2 digital output channels. The module provides a
programmable analog input range that includes 2 voltage input channels (±1 V, ±2.5 V,
±5 V, and ±10 V) and 2 current input channels (±20 mA, 0 ~ 20 mA and 4 ~ 20 mA).
The analog inputs provide a high overvoltage protection of 120 VDC and an adjustable
sampling rate. The module supports sink-type digital output with short circuit protection
and the digital outputs can be used as voltage input limit alarms. The digital inputs are
source-type and all digital input channels can be used as 16-bit counters. There are
options for configuring power-on and safe digital output values. 4 kV ESD protection
and 2500 VDC intra-module isolation are also provided. The tM-AD4P2C2 supports the
DCON, Modbus RTU and Modbus ASCII protocols, which can be configured via
software.
2. Terminal Assignment
tM-AD4P2C2 4-channel Multifunction AI, 2-channel DI module- QuickStart (Jun/2016)
ICP DAS USA, Inc. | www.icpdas-usa.com | 1-310-517-9888 | 24309 Narbonne Ave. Suite 200. Lomita, CA 90717
2
3. Block/ Wiring Diagram
Use 26-12 AWG wire for signal
connections.
Strip the wire to a length of
7±0.5mm.
Use a crimp terminal for wiring.
Avoid high-voltage cables and
power equipment as much as
possible.
For RS-485 communication, use
insulated and twisted pair 24 AWG
wire, e.g. Belden 9841.
tM-AD4P2C2 4-channel Multifunction AI, 2-channel DI module- QuickStart (Jun/2016)
ICP DAS USA, Inc. | www.icpdas-usa.com | 1-310-517-9888 | 24309 Narbonne Ave. Suite 200. Lomita, CA 90717
3
4. Default Settings
Default settings for the tM-AD4P2C2 are as follows:
Protocol: Modbus RTU
Module Address: 01
Voltage Input Type: type code 08, -10V to 10V
Current Input Type: type code 0D, -20mA to 20mA
Baud Rate: 9600 bps
5. Configuration
To install the module, follow the steps below:
1. Connect the thermistor analog input.
2. Connect the module to the RS-485 network using the DATA+ and DATA- terminals.
3. Connect the module to the power supply using the +Vs and GND terminals. Note that
the voltage supplied should be in the range of +10 to +30V DC.
tM-AD4P2C2 4-channel Multifunction AI, 2-channel DI module- QuickStart (Jun/2016)
ICP DAS USA, Inc. | www.icpdas-usa.com | 1-310-517-9888 | 24309 Narbonne Ave. Suite 200. Lomita, CA 90717
4
4. Open DCON utility pro
click on COM port(first icon).
It can select multi-options such as Baud Rate, Protocol, Checksum, and Format to
search module. The default settings for the module can be found in Section 3. Click OK
after selecting the COM port setting.
tM-AD4P2C2 4-channel Multifunction AI, 2-channel DI module- QuickStart (Jun/2016)
ICP DAS USA, Inc. | www.icpdas-usa.com | 1-310-517-9888 | 24309 Narbonne Ave. Suite 200. Lomita, CA 90717
5
5. DCON utility pro will search for the selected COM port according the setting
previously set. DCON Utility Pro supports DCON and Modbus protocol for all ICPDAS
and the others modules.
tM-AD4P2C2 4-channel Multifunction AI, 2-channel DI module- QuickStart (Jun/2016)
ICP DAS USA, Inc. | www.icpdas-usa.com | 1-310-517-9888 | 24309 Narbonne Ave. Suite 200. Lomita, CA 90717
6
6. Configuration I/O module setting on PC
7. The Modbus RTU communication protocol is the default protocol of the tM series.
The communication Baud Rates for the Modbus RTU protocol can be in the range of
1200 bps to 115200 bps
tM-AD4P2C2 4-channel Multifunction AI, 2-channel DI module- QuickStart (Jun/2016)
ICP DAS USA, Inc. | www.icpdas-usa.com | 1-310-517-9888 | 24309 Narbonne Ave. Suite 200. Lomita, CA 90717
7
8. If user doesn’t know command, user can select Address and ID, it will show some
refer commands as below. User can select necessary command to test or debug
modules.
/