Spirax Sarco EP5 Series Installation And Maintenance Instructions Manual

Type
Installation And Maintenance Instructions Manual

This manual is also suitable for

3.568.5275.226
© Copyright 2016
EXPER
TISE SOLUTIONS SUST
AINABILITY
IM-P343-16
CH Issue 7 - 2016
1. Safety information
2. Introduction
3. Installation
4. Commissioning
5. Maintenance
6. Spare parts
7. Faultnding
EP5 and ISP5 Series
Electropneumatic Positioners
Installation and Maintenance Instructions
Attention: Additional instructions are required when a ATEX
intrisically safety instrument ISP5 is used in an explosion risk area.
3.568.5275.226
2
1. Safety information
Safe operation of these products can only be guaranteed if they are properly installed, commissioned,
usedandmaintainedbyqualiedpersonnel(seeparagraph1.11)incompliancewiththeoperating
instructions.Generalinstallationandsafetyinstructionsforpipelineandplantconstruction,aswell
astheproperuseoftoolsandsafetyequipmentmustalsobecompliedwith.
WARNING: The maximum process uid temperature must be suitable for use if the
unit is to be used in any potential explosive atmosphere. For the device maintenance
inapotentiallyexplosiveatmosphere,werecommendtheusageoftoolswhichdonot
produce and / or propagate sparks.
1.1 Intended use
Referring to the Installation and Maintenance Instructions, name-plate and Technical Information
Sheet, check that the product is suitable for the intended use / application. The products comply
withtherequirementsoftheEuropeanDirective2014/34/EU(ATEX).
1.2 Access
Ensuresafeaccessandifnecessaryasafeworkingplatform(suitablyguarded)beforeattempting
toworkontheproduct.Arrangesuitableliftinggearifrequired.
1.3 Lighting
Ensureadequatelighting,particularlywheredetailedorintricateworkisrequired.
1.4 Hazardous liquids or gases in the pipeline
Considerwhatisin thepipeline orwhat mayhave beenin thepipeline atsome previoustime.
Consider:ammablematerials,substanceshazardoustohealth,extremesoftemperature.
1.5 Hazardous environment around the product
Consider:explosion riskareas, lack ofoxygen (e.g.tanks, pits),dangerous gases,extremes of
temperature,hotsurfaces,rehazard(e.g.duringwelding),excessivenoise,movingmachinery.
1.6 The system
Considertheeectonthecompletesystemoftheworkproposed.Willanyproposedaction(e.g.
closingisolationvalves,electricalisolation)putanyotherpartofthesystemoranypersonnelatrisk?
Dangersmightincludeisolationofventsorprotectivedevicesortherenderingineectiveofcontrols
oralarms.Ensureisolationvalvesareturnedonandoinagradualwaytoavoidsystemshocks.
1.7 Pressure systems
Ensurethatanypressureisisolatedandsafelyventedtoatmosphericpressure.Considerdouble
isolation(doubleblockandbleed)andthelockingorlabellingofclosedvalves.Donotassumethat
thesystemhasdepressurisedevenwhenthepressuregaugeindicateszero.
1.8 Temperature
Allowtimefortemperaturetonormaliseafterisolationtoavoiddangerofburns.
1.9 Tools and consumables
Beforestartingworkensurethatyouhavesuitabletoolsand/orconsumablesavailable.Useonly
genuine Spirax Sarco replacement parts.
3.568.5275.226
3
1.10 Protective clothing
Considerwhetheryouand/orothersinthevicinityrequireanyprotectiveclothingtoprotectagainst
thehazardsof,forexample,chemicals,high/lowtemperature,radiation,noise,fallingobjects,and
dangers to eyes and face.
1.11 Permits to work
Allworkmustbecarriedoutorbesupervisedbyasuitablycompetentperson.
Installation and operating personnel should be trained in the correct use of the product according
to the Installation and Maintenance Instructions.
Whereaformal'permittowork'systemisinforceitmustbecompliedwith.Wherethereisnosuch
system,itisrecommendedthataresponsiblepersonshouldknowwhatworkisgoingonand,where
necessary,arrangetohaveanassistantwhoseprimaryresponsibilityissafety.
Post'warningnotices'ifnecessary.
1.12 Handling
Manualhandlingoflargeand/orheavyproductsmaypresentariskofinjury.Lifting,pushing,pulling,
carryingorsupportingaloadbybodilyforcecancauseinjuryparticularlytotheback.Youareadvised
toassesstheriskstakingintoaccountthetask,theindividual,theloadandtheworkingenvironment
andusetheappropriatehandlingmethoddependingonthecircumstancesoftheworkbeingdone.
1.13 Residual hazards
In normal use the external surface of the product may be very hot. If used at the maximum permitted
operating conditions the surface temperature of some products may reach temperatures of 176°F.
Manyproductsarenotself-draining.Takeduecarewhendismantlingorremovingtheproductfrom
aninstallation(referto'Maintenanceinstructions').
1.14 Freezing
Provisionmustbemadetoprotectproductswhicharenotself-drainingagainstfrostdamagein
environmentswheretheymaybeexposedtotemperaturesbelowfreezingpoint.
1.15 Disposal
UnlessotherwisestatedintheInstallationandMaintenanceInstructions,thisproductisrecyclable
andnoecologicalhazardisanticipatedwithitsdisposalprovidingduecareistaken.
1.16 Returning products
CustomersandstockistsareremindedthatunderECHealth,SafetyandEnvironmentLaw,when
returningproductstoSpiraxSarcotheymustprovideinformationonanyhazardsandtheprecautions
tobetakenduetocontaminationresiduesormechanicaldamagewhichmaypresentahealth,safety
orenvironmentalrisk.ThisinformationmustbeprovidedinwritingincludingHealthandSafetydata
sheetsrelatingtoanysubstancesidentiedashazardousorpotentiallyhazardous.
3.568.5275.226
4
2. Introduction
1 =Receiver0.2to1bar(3to15psi)
2 =Amplifierrelay
3 =Adjustableorifice:sensitivitysetting
4 =Damping:outletairflowadjustment
5 = Flapper
6 = Reaction spring
7 =Zeroscrew
8 = Positioner lever
9 =Lock-nut
10 = Slider
11 = Sector lever
A = Control signal
I = I /P converter output
S =Airsupply
O = Positioner output
U1 =Increaseactionnozzle
U2 =Decreaseactionnozzle
8
7
9
6
5
U1 U2
1
S
2
O
I
+
-
11
10
A
4
3
2.1 Introduction
TheEP5isa2wirelooppoweredpositionerrequiringa4-20mAcontrolsignal,andisdesigned
forusewithlinearpneumaticvalveactuators.Thepositionercomparestheelectricalsignalfrom
a controller with the actual valve position and varies a pneumatic output signal to the actuator
accordingly.Thedesiredvalvepositionisthereforemaintainedforanycontrolsignalandtheeects
ofvaryingdierentialpressure,stemfrictionandhysterisisareovercome.Amountingkitissupplied
tosuitallNAMURstandardcolumnsoryokes.
Note:A0-10VdcinputsignalandanintrinsicallysafeversionISP5arealsoavailable.
2.2 Operating principle
TheEP5operatesonaforcebalanceprinciplebymeansofanozzle/appermechanismanda
feedbackspring(refertoFigure1).
The electrical control signal (A) is converted into a proportional air pressure (I). This pressure is
appliedtotheapper(5) via the receiver (1),causingadeectionoftheapperrelativetothenozzles
U1/U2. From the air supply (S)areducedbleedofairisfedtotheamplierrelay(2) and into one
ofthenozzlesU1/U2.Astheappermovesthepressuredropthroughthenozzleissensedbythe
amplierrelay.Theamplierrelayoutputsasignal(O)totheactuatorwhichisproportionaltothe
pressuredropthroughthenozzle.
Astheactuatormoves,connectinglever(8) causes a change in tension of the reaction spring (6).
Thistensionisappliedtotheappercausingittomovetoanewpositionatwhichtheforcesapplied
by the spring and the applied pressure (I) balance.
Important:Thisinstrumentbleedsairinnormaloperationatarateofapproximately0.7N
/ hour at a supply pressure of 6 bar.
Fig. 1
3.568.5275.226
5
3. Installation
Note: Before starting any installation observe the 'Safety information' in Section 1.
This publication is provided as a guide and it is recommended that it is read thoroughly prior to
installation.AlsorefertotheseparateInstallationandMaintenanceInstructionsforthecontrolvalve
and actuator.
3.1 Location
Thepositionershouldbemountedinsucientspacetoallowremovalofthecoverandprovide
accesstoconnections.Whenttingtoanactuator,ensurethepositionerwillnotbeexposedtoan
ambient temperature outside the range -15°C to +65°C. The positioner enclosure is rated to IP54
seeBSEN60534-6-11998.
Connectionofairsupplypressure(1.4to6barg)andcontrolsignal(4-20mAor0-10Vdc)should
be considered prior to choice of location.
3.2 Mounting the positioner onto the actuator
TheEP5positionermayhavebeensuppliedalreadyfactoryttedontothevalveactuator.However,
using the mounting kit provided it can be attached retrospectively onto any other type of valve and
actuatorconformingtoNAMURstandards.
Step 1 Identify actuator type
Forcorrectoperationitisimportanttoknowtwofactorswhichwillaectoptimummovementofthe
positioner feedback mechanism:
- Thedistancebetweentheaxesofthevalve/actuatorstemandthepositionerslidepin.
- The travel of the valve actuator.
To ensure these are set correctly, please note the following:
- WhenattachinganEP5toanySpiraxSarcovalveactuator,ignoreStep3.
- For non-Spirax Sarco actuators, ignore Step 2.
3.568.5275.226
6
Step 2 For attachment to Spirax Sarco actuators
Usingthe2oM6panheadscrews,securelyattachthe'T'shapedslidingpinholdertothevalve
actuatorcouplingblock(Figure2).ApplyLoctitetotheslidingpinandscrewintohole'Y'(asshown)
on the sliding pin holder and tighten.
Usingthe2oM8x15hexheadscrewsand8mmspringwashers,attachthemountingplatetothe
backofthepositioner,utilisingholesNo.2inthebracket(Figure3).Takecarenottoover-tighten
thesescrewsandstripthethreads.
Step 3 For attachment to non-Spirax Sarco actuators
Usingthe2offM6panheadscrews,securelyattachthe'T'shapedslidingpinholdertothevalve
actuatorcouplingblock(Figure2).Dependingonthetravelofthevalveactuator,applyLoctiteto
slidingpinandscrewintothecorrectholeontheslidingpinholderandtighten.UseFigure2and
Table 1 to determine the correct hole to use.
Fig. 2
Close-up of
sliding pin holder
fitted to valve
coupling.
Fig. 3
Valve travel Hole to be used
8-15mm X
15-30mm Y
above30mm Z
Table 1
Usingthe2offM8x15hexheadscrewsand8mmspringwashers,attachthemountingplate
to the back of the positioner. The correct fixing hole may be determined by reference to Figure
3, Table 2 and Figure 4. Take care not to over-tighten these screws and strip the threads.
Z
X
Y
Valve
actuator
coupling
block
'T'shaped
sliding pin holder
1
3
4
2
Positioner
Mounting plate
3.568.5275.226
7
Fig. 5
Table 2
D Hole to be used
Upto125mm 1
125to150mm 2
150to175mm 3
above 175 mm 4
Fig. 4 Pillar/yoke spacing, showing 50 % travel.
Actuator
spindle
Actuatorpillar
or yoke
100%
50%
0%
D
Valve
position
indicator
Slide pin
Step 4 Temporarily apply adequate air pressure directly into the actuator so that the valve is
at50%oftravel(Figure5).
Step 5Engagetheslidepinintothepositionerlever(seeFigure5,notingthepositionofthe
spring,abovethepin)andlooselyxthepositionertotheactuator.Foryokeactuatorsusethesin-
gleelongatedscrewholewiththeM8x20screwandspringwasher,forpillarsusetheU-clamps.
Important:Slidepositionerverticallyupordowntheyoke/pillarssothepositionerleverishorizontal
at50%travel,andtheindicatoratLHSisaligned(Figure5).Securethetighteningscrews/nuts.
3.568.5275.226
8
Step 6Fittheangledprotectionplatetotherearofthepositionerusingthe2ocaptiveM3pan
headscrews.Accesstothesecaptivescrewsisfrominsidethepositioner.
Step 7 Adjusttheairsupplypressuretostroketheactuatorfrom0%to100%andensurethe
positioner lever rotates freely. Remove the temporary air supply from the actuator.
Step 8 Fitting a gauge block (optional)
ToaidcommissioningitisrecommendedtotagaugeblockandpressuregaugestoallEP5s.Please
note that gauges and gauge block can be supplied as spare parts if required.
FitgaugestotheblockbeforeattachingtheblocktotheEP5.Usethreadsealanttoensureairtight
connections.TheuppergaugedisplaystheoutputoftheI/Pconverter,andisnormally0-2barg.The
lowergaugedisplaysthepositioneroutputpressure,sothegaugerangewilldependontheactuator.
RemoveanyairttingsandblankingplugfromtheEP5,thenattachtheassembledblocktotheEP5
usingthe2osocketheadcapscrewssupplied.Ensurethesealing'O'ringsarecorrectlyttedto
sealthejointsbetweentheEP5bodyandthegaugeblock.Replacethettingsandblankingplug
into the corresponding ports on the gauge block.
3.3 Connecting up
3.3.1 Pneumatic connections (with or without a gauge block)
Warning:Airsupplymustbedry,oilanddustfreetoISO8573-1:class2:3:1.Acoalescinglter
regulatorsuchasaSpiraxSarcoMPC2willremoveoilanddirttomeetthisstandardifpro-
perlyttedandmaintained.Dirtyairsupplymaydamagetheproductandinvalidatewarranty.
The supply air pressure must not exceed the maximum allowable air pressure of the actuator.
Avoiduseoffer rouspipeworkaf tert heM PC2.Forbestper formanc e,settheairsupplypressure
toabout0.5bargabovethepressurerequiredtofullytraveltheactuator.
Chec kallco nnec tionsfo rleaks.Pleas en otehowevert hattheEP5blee dsairinnor maloper ation
atarateofapproximately0.7Nm³/hour at 6 bar supply pressure.
PneumaticconnectionsarelocatedattherighthandendofthepositionerandidentiedI, S
and Oasfollows:
I - NotusedonEP5,t¼" NPT plug.
S - Airsupply-1.4bargto6barg,dependinguponrequiredactuatorspringrange.
O - Outputsignaltotheactuator.
Connections are ¼"NPTfemale. Interconnectionbetweenpositioner andactuator shouldbeat
least6mmODtube.
3.568.5275.226
9
3.3.2 Electrical connections
CablingshouldbeinstalledinaccordancewithBS6739-InstrumentationinProcessControlSy-
stems: Installation design and practice or local equivalent.
TheEP5onlyrequiresa4-20mA(standard)or2-10Vdc(ifrequested)signal.Removethefront
coverandlocatetheterminalblockandearthterminalpost(Figure6).
Note:Ensureresistancefromearthposttolocalearth(e.g.pipework)islessthan1Ω.
ConnectiontotheunitisthroughthePg13.5cablegland(assupplied),whichwhenusedwithsuitable
cablewillensuretheIP54protectionrating.Appropriateconduitconnectionsmaybeusedinstead.
Connectconductors(0.5to2mm²)totheterminalblockandearthpost(3mm²)notingthepolarity
+/-showninFigure6.
InhazardousareasusemodelISP5withintrinsicprotection(typeEExiallCT6,T5,T4)ensuringthe
powersupplyfromadjoiningequipmentiscertiedinaccordancewithEN50.014andEN50.020
standards,inrespectofthelimitsofelectricfeaturesshownatapprovalstage.Refertoapproval
certicatesuppliedwitheachISP5product.
Fig. 6
Cable
gland
Terminal
block
-
+
Earth
terminal
post
I
S
O
3.568.5275.226
10
4. Commissioning
Once the positioner has been mounted and connected up, proceeed as follows.
Step 1 Set the valve action
Establishingthecorrectactionofthevalveisdoneby:
a. ConnectiontoeitherU1orU2nozzles(seeFigure7)and
b. Settingthesliderintheupperorlowerportionofthecrescentshapedsectorlever(Figure8).
U1 = Increase action = Withincreasingelectricalcontrolsignaltheairpressuretotheactuator
willincrease.
U2 = Decreaseaction = Withincreasingelectricalcontrolsignaltheairpressuretotheactuator
willdecrease.
To change the working nozzle connections (U1 or U2):
Disconnecttheairsupply.Loosentheretainingplateandrotateitclearofthetubeholder.Pull
the tube holder clear of its seat and re-insert the tube holder into the alternative seat location.
Lockinplacewithalternativeretainingplate(lockunusedretainingplatetopreventlossofplate).
Reconnect air supply.
Fig. 7
Connection
tonozzleU2
Connection
tonozzleU1
3.568.5275.226
11
To change the slider location:
RefertoFigure8todeterminethecorrectportion.Tochangethesliderslackenthescrewandslide
it into the correct portion of the arm.
*Thearrowshowsthestemmovementdirectionwhentheinputcontrolsignalincreases.
Fig. 8a Increase action and spring extend
Fig. 8b Increase action and spring retract
Fig. 8c Decrease action and spring extend
Fig. 8d Decrease action and spring retract
Upper
sector
Upper
sector
Lower
sector
Lower
sector
U1nozzle
*
U2nozzle
*
U2nozzle*
U1nozzle
*
I
O
S
I
O
S
I
O
S
I
O
S
3.568.5275.226
12
Step 2 Set sensitivity
Thepositionersensitivityisadjustedusingthesensitivityscrew(Xp%,seeFigure10).Itissetde-
pending on air supply pressure. Before the commissioning stage it is essential to set the sensitivity
withinaproportionalbandof(3%to6%).UseFigure10toadjustthesensitivityscrewbyrstlyfully
closingthescrew(clockwise),thenreopenthescrew:-
Supply pressure (S) 1.4 bar -
Screwopen
¾ of a turn
4.0bar -
Screwopen
¼ of a turn
6.0bar - Screwopen
of a turn
Note: AdjustmentoftheXp%screwcausesachangeofpositioner'zero'point,anditistherefore
importanttorepeatthezeroingandtravelsettingprocedures(Steps4and5)afteranychanges.
Toincreasepositionersensitivityclosetheadjustingscrew,todecreasesensitivityopenthescrew.
Do notopenthescrewbeyondthemechanicallock.
Fig. 9
Fig. 10
Xpcorrectvalue
Openingdegree
¾
½
¼
0
3
6
1.4 bar
4.0bar
6.0bar
(Xp%)
Supply pressure
Sensitivityscrew
3.568.5275.226
13
Step 3 Set damping
Thenal adjustmentofdampingscrew shouldbeperformed withplantin operation,inorder to
limit,ifnecessary,theactuationspeed.Duringthecommissioningsetthedampscrewushwith
the body see Figure 11.
Thereductionofairowratecapacitytotheactuatorwillslowdownthevalvemovementtolimitthe
eectofcyclinghunting.Closingthescrew(clockwise)increasesdamping,andviceversa.
Step 4 Set zero point
Check all air and electrical connections are in place. Check air supply pressure (S)iscorrect(see
Section3.3.2).Checkelectricalcontrolsignal(A)(seeSection3.3.3)isattheminimumrequired
(normally4mAor0V),buttheapplicationmayrequireadierentsetting.Itmayalsobeadvisable
toincreasetheminimumby0.5mAor0.25Vtoensurethevalveiscompletelyclosed.For3-port
valves(oriftheactionhasbeenreversedfor2-portvalves)ahigherelectricalsignalcorresponds
totheclosedvalveposition,itmaybebenecialtodecreasethemaximumelectricalcontrolsignal
to19.5mAor9.75V.Thiswillensurethatthevalveisrmlyseatedwhenthefullelectricalsignal
of20mAor10Visapplied.
Locatezeropointadjustmentscrew(seeFigure12)andreleasethelockingring.Adjustscrewuntil
thevalvestartstomoveandlocktheadjusterinplace.
Checkthezeropointbyreducingtheelectricalcontrolsignal(A)(seeSection3.3.3)tozero.Slowly
increasetheelectricalcontrolsignaltowardstheminimumlevelwhilstmonitoringvalvemovement.
Shouldmovementtakeplacebeforeoraftertheminimumcontrolsignalthenrepeatadjustment
untilmovementcoincideswithminimumcontrolsignal.
Fig. 11
Dampscrew
Fig. 12
Slider
Lockingring
Zero point
adjustmentscrew
Sector lever
Centrallockingscrew
Note:Positionersfittedwithagaugeblockhavethebenefitofanticipatingvalvemovementby
indicating increases of output air pressure.
3.568.5275.226
14
Step 5 Set travel
Increasetheelectricalcontrolsignaltotheuppervalue(normally20mAor10V,butthisdependson
theapplication)andnowcheckthetravelofthevalve.Ifrequired,slackenthecentrallockingscrew
(seeFigure12)andadjustthesliderupordowntheupperorlowerportionofthecrescentshaped
sectorlever.Movingthesliderawayfromthepivotwillreducethetravel,andviceversa.Normally,
exceptwith3-portvalves,thefullyopenpositionisachievedbeforethevalveplughitstheupper
mechanicalstopofthevalve/actuator.Avoidsettingsofthepositionerthatallowcontactwiththis
mechanicalstop.Varytheelectricalcontrolsignalaroundtheuppervaluetoverifythetravelsetting,
andifnecessaryrepeattheadjustmentoftheslideruntiltherequiredtraveloccursattheuppervalue.
Important:ZeroandtravelsettingsonEP5arenotindependentofeachother,sore-checkthezero
setting as described in Step 4. It may prove necessary to repeat Steps 4 and 5 several times until
acceptablezeroandtravelsettingsareachieved.Forneadjustmentofthetravel,thepotentiometer
showninFigure13canbeused.Thisshouldonlybeusedfornaladjustmentof+/-5%.
Whencomplete,lockbothzeroandtraveladjustments.
Split range operation
EP5maybesplitrangedtosequentiallyactuatetwovalvesfromonecontrolsignal
(Forexample:valve1setto4-12mAandvalve2setto12-20mA).Splitrangingisachieved
byadjustmentofthezeroandtravelsettingsrefertoSteps4and5.
Fig. 13
Traveladjustment
potentiometer
3.568.5275.226
15
5. Maintenance
5.1 Regular maintenance
1. Drainanybuild-upwithintheairsupplyltersetasimpuritiessuchasoil,wateranddirt
willcauseinconsistentoperation.
2. Ensureairsupplyisatthecorrectpressure(seeSection3.3.2andrefertoactuatorTI).
3. Make visual checks to ensure the valve is operating correctly.
5.2 Corrective maintenance
5.2.1 Removal and cleaning of sensitivity adjuster (see Figure 14):
- Loosenandremovelock.
- Notesettingthenremovesensitivityscrew.
- Washadjusterwithsolvent,checkingconditionoftheconeandensuring0.35mmside
hole is clear.
- Drywithcleancompressedairtoensurenoremainingcontaminants.
- Retthecleanedadjusterandunscrewit1turnfromitsstop.
- Retthelocktotouchtheadjustertopandsecurewithlock-nut.
- Set sensitivity see Step 2, Section 4, Commissioning.
- Resetzeroandspanifrequired.
Fig. 14
3.568.5275.226
16
5.2.3 Check damping grease:
- Ensuregapof1mmexistsbetweenfacesofdamper.Adjustifnecessary.
- Verifygreaseispresentbetweenfaces.
- Replacegreaseifnecessary(contactSpiraxSarcofordetails).
5.2.2 Removalandcleaningofcapillaryorice (see Figure 15):
- Loosenlockingplatescrew.
- Rotatelockingplatetoexposecapillaryorice.
- Usingsuppliedextractor/cleanerpulltheoricefromthebody.
- Cleanthesmalloriceandcrossdrillingusingonlythespecialcleaningwiresupplied.
- Reassembletheoriceensuringboth'O'ringsareinplaceandthelockplatecoverstheorice.
Fig. 16
Lockingplate
Capillary orifice
Dampingfaces
Capillary extractor /cleaner
Fig. 15
Extracting
thread
Cleaningwire
Extractor/cleaner
Capillary orifice
Spare'O'ring
3.568.5275.226
17
6. Spare parts
Available spares
Gaugeblock(withoutgauges) 1
Gauge0-2bar 2
Gauge0-4bar 3
Gauge0-7bar 4
Springs and tubes 5
Set of gaskets, diaphragms and orifice 6
Amplifyingrelayset 7
How to order spares and accessories
Always order spares by using the description in the column headed 'Available spares' and a
descriptionoftheproduct,togetherwiththeTAGnumber.
Example:1offGauge0-2barforaSpiraxSarcoEP5positioner,TAG907.
Product return procedure
Pleaseprovidethefollowinginformationwithanyequipmentbeingreturned:-
1. Yourname,Companyname,addressandtelephonenumber,ordernumberandinvoice
and return delivery address.
2. Descriptionofequipmentbeingreturned.
3. Descriptionofthefault.
4. Iftheequipmentisbeingreturnedunderwarranty,pleaseindicate:
i. Dateofpurchase
ii.Originalordernumber
Please return all items to:
ReturnsInvestigationsDepartment
Runnings Road,
KingsditchTradingEstate
Cheltenham
Glos,GL519NX
UnitedKingdom
Alternatively, please return any items to your local Spirax Sarco branch.
Pleaseensureallitemsaresuitablypackedfortransit(preferablyintheoriginalcartons).
Fig. 17
1
2
3 or 4
76
5
TAGnumber
3.568.5275.226
18
7.Faultnding
Output pressure too low or zero
Cause Remedy
a. No control signal a.RestoremAsignal
b.Lowairsupplypressure b.Verifyactuatorairpressurerequirement
c.Cloggedordirtysensitivityadjuster c.CleanadjusterseeSection5.2.1
d. Clogged or dirty capillary orifice d. Clean orifice see Section 5.2.2
e. Incorrect set-up e. Recalibrate see Section 4, Steps 1 to 5
f.Damagedpneumaticactuatororpiping f.Verifyreplaceasnecessary
g. Port I not blanked or leaking g. Insert ¼" NPT blank in port I
Output pressure too high
Cause Remedy
a.Sensitivityadjusteropentoofar a. Recalibrate see Section 4, Step 2
Actuator movement too slow
Cause Remedy
a.Lowairsupplycapacity a.Checksupplycapacityandpipesizes
b.Dampingscrewclosedtoofarorclogged b. Recalibrate see Section 4, Step 3
Actuator failing to close
Cause Remedy
a.Outputpressuretoolow a. Refer to previous fault
b.Incorrectzeropoint b. Recalibrate see Section 4, Step 4
c.Dampingscrewclosedorclogged c.CleanscrewandrecalibrateseeSection 4, Step 3
d.Valve / actuatorcouplingincorrect d.Reset(refertovalve/actuatorIMIs)
e.Actuatortoosmall e. Fit correct actuator
Actuator failing to fully open valve
Cause Remedy
a.Outputpressuretoolow a. Refer to previous fault
b.Incorrecttraveladjustment b. Recalibrate see Section 4, Step 5
c.Dampingscrewclosedorclogged c.Clean screw andrecalibrateseeSection 4,Step 3
d.Valve /actuatorcouplingincorrect d.Reset(refertovalve/actuatorIMIs)
e.Actuatortoosmall e. Fit correct actuator
Hunting
Cause Remedy
a.Incorrectcontrollersetup(P, I, and D) a.Verify and adjust accordingto process requirement
b. Sensitivity orifice closed too far b.Adjustbyopeningsensitivityscrew
see Section 4, Step 2
c.Excessivevalvefriction c.VerifyandmaintainasvalveIMI
d.Controlvalveover-sizing d. Verify operating conditions againstvalve capacity.
Note:Theeffectsofhuntingcausedbyvalveover-sizingorunstableprocessconditionscanbe
reducedbyadjustmentofdampingscrewseeSection4,Step3.
3.568.5275.226
19
3.568.5275.226
20
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24

Spirax Sarco EP5 Series Installation And Maintenance Instructions Manual

Type
Installation And Maintenance Instructions Manual
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI