119-1
Daker Dk
Conventional UPS - Single phase On-line double conversion VFI
3 109 533 100 54
The main parameters of the UPS, including the battery charge level and faults, are displayed on the LCD screen on the front panel
The integrated communication software not only controls the UPS and its switch-off if there is a malfunction, and enables the user to test the main
functions remotely, communicate via SNMP/Internet/network adaptor and access the functions of the UPS via the Internet, but can also send the
user an SMS if specific events occur
The internal extension connector enables a WEB/SNMP card or a relay interface to be installed which provides insulated contacts for applications
on industrial control panels or remote alarm panels
If there is an electronic fault, overload, overheating or for scheduled maintenance operations, the automatic or manual (optional) bypass ensures
continuity of the power supply for critical loads
A bypass switch is available for maintenance
3 100 50 3 107 71
Pack Cat.Nos
Convertible UPS with batteries
Nominal power
(VA)
Active power
(W)
Backup time
(min)
Weight
(kg)
3 100 50 1000 800 10 16
3 100 51 2000 1600 10 29.5
3 100 52 3000 2400 8 30
3 100 53 4500 4050 6 60
3 100 54 6000 5400 4 60
Convertible UPS without batteries
Nominal power
(VA)
Active power
(W)
Weight
(kg)
3 100 56 4500 4050 25
3 100 57 6000 5400 25
3 100 58 10000 9000 26
Battery cabinet (with batteries)
3 107 69
Battery cabinet for 3 100 50
(12 x 12 V, 7.2 Ah batteries)
3 107 70
Battery cabinet for 3 100 51
(12 x 12 V, 7.2 Ah batteries)
3 107 71
Battery cabinet for 3 100 52
(12 x 12 V, 9 Ah batteries)
3 107 72
Battery cabinet for 3 100 56 and 3 100 57
(20 x 12 V, 7.2 Ah batteries)
3 107 66
Battery cabinet for 3 100 58
(20 x 12 V, 9 Ah batteries)
Battery cabinet (empty)
3 107 50
Battery cabinet for 3 100 50
(for 12 x 12 V, 7.2 Ah batteries)
3 107 51
Battery cabinet for 3 100 51
(for 12 x 12 V, 7.2 Ah batteries)
3 107 52
Battery cabinet for 3 100 52
(for 12 x 12 V, 9 Ah batteries)
3 107 53
Battery cabinet for 3 100 56 and 3 100 57
(for 20 x 12 V, 7.2 Ah batteries)
3 107 54
Battery cabinet for 3 100 58
(for 20 x 12 V, 9 Ah batteries)
Pack Cat.Nos
Miscellaneous accessories
3 109 50
Additional 200 W charger
(for Daker DK 1000-2000-3000)
3 109 54
Additional 1000 W charger
(for Daker DK 4500-6000-10000)
3 109 52
Rack support bracket kit
3 109 53
External manual bypass
(for Daker DK 1000-2000-3000)
3 109 69
Volt-free contact card
NOTE: The backup times, expressed in minutes, are measured under
optimum operating conditions