Munters MLPlus Owner's manual

Category
Split-system air conditioners
Type
Owner's manual
Originalinstructions
Operatingmanual
MLPlus
Dehumidicationsystem
TEN-MLP-E1505©MuntersEuropeAB2015
Tableofcontents
Tableofcontents...........................iii
1Introduction.................................1
1.1Denition...............................
1
1.2Aboutthismanual.....................
1
1.3Warnings...............................
2
1.4Warranty...............................
2
1.5Inspectionofdelivery..................
2
1.6Marking................................
3
1.7Technicalspecications..............
3
1.8Unintendeduse........................
3
2Safety.........................................4
2.1Intendeduse...........................
4
2.2Safeinstallation,operationand
maintenance...........................
4
2.3Residualrisks..........................
6
2.4Warningsigns.........................
7
2.5Quickstop..............................
7
3Systemdesignandfunction..............8
3.1Mainfunction..........................
8
3.2Systemdesign.........................
8
3.3Pre-andpost-treatment..............
9
4Maincomponentsdescription............10
4.1Dehumidier...........................
10
4.1.1Principleofoperation..........
10
4.1.2Dehumidiercomponents.....
12
4.1.3Markingofconnections........
13
4.2Watercoils.............................
14
4.2.1Productdescription............
14
4.2.2Coilmaintenance..............
14
4.3Directexpansionrefrigeration........
15
4.4Electricheater.........................
15
4.5Humidier..............................
16
4.6Supplyfan..............................
16
4.7Filters...................................
17
4.7.1Filtertypes......................
17
4.7.2Filtermaintenance.............
17
4.8Dampers...............................
18
5Operation....................................19
5.1Mainpowerswitch.....................
19
5.2Controlsystem........................
19
5.3HMIconnection........................
20
5.4Operatorpanel........................
20
5.5Starttheunit...........................
21
5.6Stoptheunit............................
21
5.7Quickstop..............................
21
6Serviceandmaintenance.................22
6.1Safety..................................
22
6.2General................................
23
6.3Serviceoptions........................
23
6.4Extendedwarranty....................
23
6.5Cleaning...............................
23
6.6Maintenanceschedule................
24
6.7Preventivereplacements.............
25
7Scrappinganddisposal...................26
8ContactMunters............................27
TEN-MLP-E1505Tableofcontentsiii
MLPlusDehumidicationsystem
1Introduction
1.1Denition
TheDehumidicationsystemdescribedinthismanualishereafterreferredtoasthe“unit”.
1.2Aboutthismanual
Thisoperatingmanualcontainsimportantsafetyinformation,aproductdescriptionandmaintenance
instructionsforthedeliveredunit.
Readallrelevantpartsofthismanualbeforeoperatingorperforminganyworkontheunit.Observanceof
thisinformationwillhelpyoutoavoiddanger,tominimiserepaircostanddowntime,andtoincreasethe
reliabilityandtheservicelifeoftheunit.
Thismanualshouldbestoredinapermanentlocationclosetotheunit.
Thismanualdoesnotdescribeinfullallthemaintenanceworkrequiredtoguaranteethelongevityand
reliabilityofthistypeofequipment.AlwayscontactMuntersforserviceandrepairs,toensuresafeandlong
lastingoperationoftheunit.
Installationinstructionscanbefoundinthecorrespondingsupplement.
Thecontentsofthismanualcanbechangedwithoutpriornotice.
NOTE!Thismanualcontainsinformationwhichisprotectedbycopyrightlaws.Itisnotallowedtoreproduceor
transmitanypartofthismanualwithoutwrittenconsentfromMunters.
Sendanycommentsregardingthismanualto:
MuntersEuropeAB
TechnicalDocumentation
P.O.Box1150
SE-16426KISTASweden
e-mail:t-doc@munters.se
1IntroductionTEN-MLP-E1505
MLPlusDehumidicationsystem
1.3Warnings
Informationaboutdangersareinthismanualindicatedbythecommonhazardsymbol:
W W
W
ARNING! ARNING!
ARNING!
Indicatesapossiblehazardthatcanresultinseverepersonalinjuryordeath.
CA CA
CA
UTION! UTION!
UTION!
Indicatesapossiblehazardthatcanresultindamagetotheunitorotherproperty,orcauseenvironmental
damage.
NOTE!Highlightssupplementaryinformationforoptimaluseoftheunit.
1.4Warranty
ThewarrantyisbasedonthetermsofsaleanddeliveryofMunters.Thewarrantyisnotvalidifrepairsor
modicationsarecarriedoutwithoutthewrittenagreementofMunters,oriftheunitdoesnotoperateunder
theconditionsagreedwithMunters.Damagesresultingfromnegligence,poormaintenanceorfailureto
complywiththerecommendationswillnotbecoveredbythewarranty.
Itisaconditionofthewarrantythattheunitforthefullwarrantyperiodisservicedandmaintainedbya
qualiedMuntersengineerorMuntersapprovedengineer.Accesstospecicandcalibratedtestequipment
isnecessary.Theserviceandmaintenancemustbedocumentedforthewarrantytobevalid.
Thewarrantyislimitedtoafreeexchangeofpartsorcomponentswhichhavefailedasaresultofdefects
inmaterialsorworkmanship.
Commissioning/Start-upinspection"S"byMuntersismandatorytovalidatethefullwarranty.
AlwayscontactMuntersforserviceorrepair.Operatingfaultscanoccuriftheunitismaintained
insufcientlyorincorrectly.
1.5Inspectionofdelivery
Inspectthedeliveryandcomparewiththedeliverynote,orderconrmationorotherdelivery
documentation.Makesurethateverythingisincludedandnothingisdamaged.
ContactMuntersimmediatelyifthedeliveryisnotcompleteordamagedinordertoavoidinstallation
delays.
Removeallpackagingmaterialfromtheunit,andmakesurethatnodamagehasoccurredduring
transportation.
AnyvisibledamagemustbereportedinwritingtoMunterswithin3daysandpriortoinstallationof
theunit.
Disposeofthepackagingmaterialaccordingtolocalregulations.
TEN-MLP-E1505Introduction2
MLPlusDehumidicationsystem
1.6Marking
Type
Fa br. No. 1005 190XXX XXXXX
3N ~ 400 V 50 Hz
0,78 kW
Ma x (A)
10,3/0,8/0,8
Munte rs Europe AB
Is a fjords ga ta n 1
164 26 Kis ta , S wede n
M
IP 33
Fa br. ye a r
1,8 kW
Ma de in S wede n
MLT350 P lus 9A
2010
Ma x (kW)
2,58 kW
Figure1.1ExampleofidenticationplatecontentFigure1.2Identicationplateposition
1.7Technicalspecications
Thetechnicalspecicationsfortheunitcanbefoundinthecorrespondingsectionofthemanual.
1.8Unintendeduse
Theunitisnotintendedforoutdoorinstallation.
Theunitisnotintendedforuseinclassiedareaswhereexplosionsafetycompliantequipmentis
required.
Theunitmustnotbeinstallednearanyheatgeneratingdevicesthatcancausedamagetotheequipment.
Theunitisnotintendedfortreatingairpollutedwithsolvents,dustorotheraggressive,corrosiveor
abrasiveparticles.
3IntroductionTEN-MLP-E1505
MLPlusDehumidicationsystem
2Safety
2.1Intendeduse
TheunitdeliveredbyMuntersmustonlybeusedforthetreatmentofair.Thisincludesltering,heating,
cooling,humidifying,dehumidifyingandtransportingair.Muntersexplicitlyrulesoutanyotheruse.
Theunitisdesignedtomeetthesafetyrequirements,directivesandstandardslistedintheEUDeclarationof
Conformity.
NomodicationoftheunitisallowedwithoutpriorapprovalbyMunters.Attachmentorinstallationof
additionaldevicesisonlyallowedafterwrittenagreementbyMunters.
Theconditionsofoperationspeciedinthetechnicalspecicationsmustbeobservedabsolutely.
Anyotheruseoftheequipmentcancausepersonalinjuryanddamagetotheunitandotherproperty.
2.2Safeinstallation,operationandmaintenance
Greatefforthasbeenplacedonthedesignandmanufactureoftheunit,tocomplywithapplicablesafety
aspectsforthistypeofequipment.
Theinformationinthismanualincludessuggestionsforbestworkingpracticeandshallinnowaytake
precedenceoverindividualresponsibilitiesorlocalregulations.
Duringoperationandotherworkwithamachineitisalwaystheresponsibilityoftheindividualtoconsider:
Thesafetyofallpersonsconcerned.
Thesafetyoftheunitandotherproperty.
Theprotectionoftheenvironment.
Alwayscarryoutriskassessmentsbeforedoinganyworkontheunit.
W W
W
ARNING! ARNING!
ARNING!
-Theunitmustnotbesplashedwithorimmersedinwater.
-Theunitmustneverbeconnectedtoavoltageorfrequencyotherthanthatforwhichitwasdesigned.Refertothe
identicationplate.Linevoltagethatistoohighcancauseanelectricalshockhazardanddamagetotheunit.
-Donotinsertngersoranyobjectsintotheairvents.
-Allelectricalinstallationsmustbecarriedoutbyaqualiedelectricianandinaccordancewithlocalregulations.
-Thedehumidiercanrestartautomaticallyafterapowercut.Alwayssetandlockthemainpowerswitchinthe
OFFpositionbeforecarryingoutanyservicework.
-Useonlyapprovedliftingequipmenttopreventpersonalinjuryanddamagetotheequipment.
-AlwayscontactMuntersforserviceorrepair.
W W
W
ARNING! ARNING!
ARNING!
Installation,adjustments,maintenanceandrepairsmustonlybecarriedoutbyqualiedpersonnelwhoare
awareoftherisksinvolvedwhenworkingwithequipmentoperatingwithhighelectricalvoltageandhighmachine
temperatures.
TEN-MLP-E1505Safety4
MLPlusDehumidicationsystem
W W
W
ARNING! ARNING!
ARNING!
Commissioningandinitialstart-upoftheunitmustbecarriedoutbyauthorizedpersonnelonly.
W W
W
ARNING! ARNING!
ARNING!
Theunitcontainsrotatingfansandothermovingparts.
Keephandsawayfromfanbladesatalltimeswhileunitison.DONOTserviceunituntilthefanhascompletely
stopped.
AlwayssetandlockthemainpowerswitchintheOFFpositionbeforecarryingoutanyservicework.
Topreventpersonalinjury,theunitmustberunwithallpaneldoorsclosedandallremovablepanelsandprotective
gridsproperlyinplace.
Fansandothermovingpartscanstartautomaticallyandwithoutwarning.
W W
W
ARNING! ARNING!
ARNING!
Cleaningagents,coolingmedia,oilandgreasearesubstancesthataredangeroustopersonalhealthandtothe
environment.Theymustnotbeallowedtodrainawayintothesoilorthepublicsanitarysystem.Thedisposalof
suchsubstancesmustbeeffectedinaccordancewithlocalandnationallawandregulations.
CA CA
CA
UTION! UTION!
UTION!
Serviceandmaintenanceworkshouldonlybecarriedoutbyqualiedandtrainedpersonnel.Operatingfaultscan
occuriftheunitismaintainedinsufcientlyorincorrectly.
5SafetyTEN-MLP-E1505
MLPlusDehumidicationsystem
2.3Residualrisks
Inordertoavoidthepossibledangersinoperatingormaintainingtheunit,necessaryprotectionshavebeen
foreseen.However,therearestillsomeresidualrisksthatallpersonnelworkingwiththeunitmustbeaware
of:
Thehandlingofuidsinrefrigerating,heatingorcoolingcircuitscanbedangerous.Pleasestudythe
informationrelevantforeachtypeofuidtoavoiddangers.
Hotorcoldsurfacescancauseinjuries.Beforeintervening,waituntiltemperaturesbecomenormaloruse
protectiveclothing.
Sharpsteeledgesonboxesorcoilscancausecuts.Useprotectivegloves,particularlyduringdisassembly
orassembly.
Whenworkingwithornearfans,beawarethatremainingairowthroughtheunitcancausespontaneous
rotationofthefansandtherebycausingpersonalinjury.
Doorsforoverpressurecompartmentscanbeequippedwithadditionalsafetylocksagainstaccidental
opening.Makesurethatsuchlocksareclosedbeforestartingtheunit.
Whenworkingwithltersorinadustyarea:Toprotecttheuserfromdust,wearasuitableCEmarkedface
maskselectedandttedinaccordancewiththeapplicablesafetystandards.
Usehearingprotectionaccordingtoapplicablesafetystandardswhenworkinginanoisyenvironmentto
avoidhearingimpairment.
Dampersopenandcloseautomatically.Keephandsclearofthedamperswhentheyaremoving.
TEN-MLP-E1505Safety6
MLPlusDehumidicationsystem
2.4Warningsigns
Thefollowingwarningsignscanbepresentontheunit,towarntheusersofresidualriskswhichcancause
seriousinjuryordeath.Makesurethatallpersonnelworkingwithorneartheunitareawareofthemeaning
ofeachsign.
Figure2.1Riskofpersonal
injuryduetoelectricshock.
Figure2.2Hotairowor
surface.
Figure2.3Unitstarts
automatically.
Figure2.4Pinchhazard.
2.5Quickstop
Theunitcaninanemergencybestoppedusingthemainpowerswitch,seesection5.1,Mainpowerswitch.
CA CA
CA
UTION! UTION!
UTION!
Onlyusethemainpowerswitchtostoptheunitinthecaseofanemergency.Thenormalshutdownsequencewill
notbefollowed.Thefansstopandtheheatercanbeveryhot,whichcanresultindamagetotheheaterandother
componentsclosetoit.
7SafetyTEN-MLP-E1505
MLPlusDehumidicationsystem
3Systemdesignandfunction
3.1Mainfunction
TheMuntersPlusunitisdesignedtocontroltheairqualityinarchives,laboratories,cleanroomsorother
applicationswithhighdemandsonclimate.
Allunitsarealwaysdeliveredwithadehumidier.Othercomponentssuchascoolingandheatingcoils,
humidiersorsupplyfansaredelivereddependingontheindividualsystemspecication.
Thesystemissetupandoperatedfromtheoperatorpanel.Wallsensorsorductsensorsmeasurethe
temperatureandhumidityoftheprocessair.Thecontrolsystemandelectricalsafetyfunctionsforallthe
componentsareplacedintheelectricalpanel.
Allcomponentsareregulatedproportionatelyandconguredtoachieveoptimalcapacityandenergyuse
efciency.Theelectricheaterinthedehumidierhasthyristorcontrolandtheelectricheatersfortempering
theairarepulsecontrolled.Thesupplyairfanrunscontinuallytoensurepreciseclimatecontrol.Regulation
canbetimecontrolledonaweekly,monthlyandstipulatedfull-daybasisaswellaswinter/summerperiods
withspecicoperationaltemperatureandhumiditysettings.Severalpossibilitiesexistforconnectingto
buildingmanagementsystemsforcontrollingandmonitoringthefunctions.ContactyournearestMunters
representativeformoreinformationonautomaticsystemsorbusconnections.
3.2Systemdesign
1 2
3
4
8
7
6 5
Figure3.1MLPlussystemdesignexample*
1.Filter5.Post-coolingcoil
2.Pre-heatingcoil6.Post-heatingcoil
3.Pre-coolingcoil7.Humidier
4.Dehumidier8.Supplyfan
*Individualsystemsarebuilttospecication,andcanbedifferentfromthisexample.
TEN-MLP-E1505Systemdesignandfunction8
MLPlusDehumidicationsystem
3.3Pre-andpost-treatment
Pre-andpost-treatmentoftheprocessaircanbeperformedbythefollowingfunctionalcomponents:
Inletdamperstoenableisolationoftheunitfromtheairow.Thedampersareinstalledontheoutside
oftheunit.
Amixingboxallowingmixingfreshairwithrecirculationair.
Heatingcoil:Thecoilcanbeelectricorusehotwaterasheatingmedium.Inthecaseofhotwater,the
coilmustbeconnectedtoanexternalheatingmediumsupply.
Coolingcoil:Thecoiluseschilledwater,possiblymixedwithglycol.Thecoilmustbeconnectedto
anexternalmediumsupply.
Humidicationbyevaporationorsteaminjectioninordertoachievetheprocessairqualityspecication
duringdryambientconditions.Seethehumidiersupplement.
Filtersforvariousairqualityspecications.Filterscanbeequippedwithpressuredropsensorstoenable
"blockedlter"alarm.
Asupplyfantoachievetheexternalpressurerequirement.
9SystemdesignandfunctionTEN-MLP-E1505
MLPlusDehumidicationsystem
4Maincomponentsdescription
NOTE!Somecomponentsareoptional,andindividualsystemsarebuilttospecication.
NOTE!Allcomponentpicturesareexamples,andmaynotcorrespondtoindividualunits.
4.1Dehumidier
4.1.1Principleofoperation
3
4
1
2
Figure4.1Rotorprinciple
1.Processair
2.Dryair
3.Reactivationair
4.Wetair
Thedesiccantrotoristheadsorptiondehumidifyingcomponentintheunit.Therotorstructureis
comprisedofalargenumberofsmallairchannels.
Thedesiccantrotorismadeofacompositematerialthatishighlyeffectiveinattractingandretainingwater
vapour.Therotorisdividedintwozones.Theairowtobedehumidied,processair,passesthroughthe
largestzoneoftherotorandthenleavestherotorasdryair.Sincetherotorrotatesslowly,theincomingair
alwaysmeetsadryzoneontherotor,thuscreatingacontinuousdehumidicationprocess.
Theairowthatisusedtodrytherotor,reactivationair,isheated.Thereactivationairpassesthrough
therotorintheoppositedirectiontotheprocessairandleavestherotoraswetair(warm,moistair).This
principleenablesthedehumidiertoworkeffectively,evenatfreezingtemperatures.
TEN-MLP-E1505Maincomponentsdescription10
MLPlusDehumidicationsystem
1
2
3
4
Figure4.2Airowoverview
1.Processair
2.Dryair
3.Reactivationair
4.Wetair
11MaincomponentsdescriptionTEN-MLP-E1505
MLPlusDehumidicationsystem
4.1.2Dehumidiercomponents
1
3
2
4
5
6
7
8
9
10
11
12
13
14
15
16
Figure4.3Maincomponents
1.Electricalpanel9.
Processairfanimpeller
2.Reactivationheater10.
Processairlter
3.Drivemotor11.Lowerrotorcover
4.Pulley,beltdrive12.Roller,beltguide
5.
Reactivationairlter
13.Drivebelt
6.
Reactivationairfanimpeller
14.Rotor
7.
Reactivationairfanmotor
15.Rotor,sealingring
8.
Processairfanmotor
16.Upperrotorcover
NOTE!ML180,ML270,MLT350andML420eachhasjustonefanmotorwhichisplacedbetweenthefan
impellers.Theelectricalpanelcaninsomecaseshaveadifferentposition.
TEN-MLP-E1505Maincomponentsdescription12
MLPlusDehumidicationsystem
4.1.3Markingofconnections
Examplesoflabelswhichcanbeplacedonthedehumidierairinletsandoutlets.
3
2
4
5
4
2
3
1
Figure4.4Labelsforairinletsandoutlets
1.Processairinlet
2.Dryairoutlet
3.Reactivationairinlet
4.Wetairoutlet
13MaincomponentsdescriptionTEN-MLP-E1505
MLPlusDehumidicationsystem
4.2Watercoils
4.2.1Productdescription
Theunitcanhavewatercoilsforcoolingandheating.Thecoolingorheatingisonlyregulatedifthesupply
airfanisrunning.
CA CA
CA
UTION! UTION!
UTION!
Ifthereisariskoffreezingwhenuntreatedoutsideairisused,afrostprotectionmonitorsensormustbetted.The
coilsintheunitcanbeseriouslydamagedifthisisnotdone.
Allunitswithhotwatercoilsarealwaysdeliveredwithaninsertionsensorandoutletforaninsertionsensor.
Theheaderisprovidedwithapluggedoutletforventinganddraining.Ifthereisariskoffreezing,thesensor
mustbettedandconnectedaccordingtothewiringdiagramfortheunit.Therecanbeariskoffreezingif
theprocessairistakendirectlyfromoutside.
Ifthewaterinacoilfreezesthiscouldcauseseriousdamage.Afrozencoilmustalmostalwaysbereplaced.
Thewarrantyisnolongervalidevenifthecracksarenotvisible.
CA CA
CA
UTION! UTION!
UTION!
Hotandcoldwatersupplylinesmustonlybedesignedandexecutedbyqualiedpersonneltakingintoaccount
therespectiverelevantlocalregulations.
4.2.2Coilmaintenance
W W
W
ARNING! ARNING!
ARNING!
Coilnshavesharpedges.Alwayswearprotectivegloveswhenworkingwithcoils.
Checkforsignsofcorrosiononsurfaceswithanges.Cleanandrepairifnecessary.
Ifapplicable,removethedropletseparator.
Inspecttheinletsurface(towardsthecoolingcoil).Ifdirty,rinsewithwarmwater.
Airinthepipingreducesthecapacityofthecoil.Ventofftheairviatheairnippleonthehighesthorizontal
partoftheheader.
Inthecaseofalongoperationstoporwhenthetemperatureisbelowfreezingpoint,emptythewaterout
ofthecoil.Dothisviathenippleonthelowesthorizontalpartoftheheader.Notethatsomecoilscannot
bedrained.
CA CA
CA
UTION! UTION!
UTION!
Donotattempttocleanthewatercoilsmechanically.
NOTE!Inthecaseofdamage,contactMuntersService.Donotattempttocarryoutrepairs.
1.Thecoilsshouldbecheckedatleastonceayear,andcleanedifrequired.
2.Someofthedustwhichpassesthroughthelterscomestorestonthecoilcells.Thislayerofdust
affectstheairowandreducestherateofexchangeleadingtodecreasedunitefciency.
3.Thecoilsshouldthereforebekeptclean.Cleaningcanbedonebyusingavacuumcleaner,lowpressure
compressedairorlowpressurewaterandasoftbrush.Donotforgettocleantheunitinternallyafterthe
coilcleaning.Neveruseahighpressurecleaner,thiswilldamagethecoilns.
TEN-MLP-E1505Maincomponentsdescription14
MLPlusDehumidicationsystem
4.Furthermore,inthecaseofcoolingcoils,cleanthedriptrayandsiphonforthecondensationwateronce
peryear.Notethatsiphonsneedtoberelledwithwaterafterthewinterseason.
4.3Directexpansionrefrigeration
AppliestounitswithDXrefrigeration.
AdetaileddescriptionoftheDXcoolingfunctionandthecorrespondingcomponentsisfoundintheDX
Supplement.
ImportantinformationfortheoperatoroftheDXrefrigerationsystemisfoundintheDXSupplement.
ThemandatoryCommissioningandServiceLogbookisalsoavailableintheDXSupplement.
W W
W
ARNING! ARNING!
ARNING!
StrictlegalrequirementsapplyfortheoperationofDXcoolingsystemscontaininguorinatedgreenhousegases.
ReadmoreintheDXSupplement.
4.4Electricheater
Allelectricheatershaveminimallytwohightemperaturecut-outs,anautomaticresettingfunctionandcan
bemanuallyreset.Thehightemperaturecut-outcanberesetonthecoverofalltheelectricheaters.
Theelectricheaterpowerisproducedonatimebasisusingpulse-pausetechnology.Whenheatisrequired
theinbuiltregulationequipmentsignalsforfullpower(pulse)forasettime,dependingontheheat
requirement.Iftheheatrequirementincreases,thepulsetimeincreasesandthepausetimedecreases.When
theheatrequirementisreduced,thepulsetimedecreasesandthepausetimeincreases.
15MaincomponentsdescriptionTEN-MLP-E1505
MLPlusDehumidicationsystem
4.5Humidier
Humidiersareusedasneededtoachievetheprocessairqualityspecication.
Unitscanbeequippedwitheitheranevaporativehumidierorasteamhumidier.
Formoreinformationabouthumidiersifapplicable,seetherelevantdocumentationunderthesection
Othercomponents.
4.6Supplyfan
Theunitisequippedwithaplugtypesupplyfan.Thefanisdrivenbyanelectricmotorwhichiscontrolled
byafrequencyconverter.Thismakesitpossibletoadjusttheairpressureandairowfromtheoperator
paneltoachievetheexternalpressurerequirement.
Forspecicinformationaboutthefan,seetheOEMmanualunderthesectionOthercomponents.
TEN-MLP-E1505Maincomponentsdescription16
MLPlusDehumidicationsystem
4.7Filters
4.7.1Filtertypes
Figure4.5BaglterFigure4.6Panellters
4.7.2Filtermaintenance
W W
W
ARNING! ARNING!
ARNING!
Thereisarehazard,orriskofunitmalfunction,ifltersaremaintainedinsufcientlyorincorrectly.
W W
W
ARNING! ARNING!
ARNING!
Whenreplacingtheltersorworkinginadustyarea:Toprotecttheuserfromdust,wearasuitableCEmarkedface
maskselectedandttedinaccordancewiththeapplicablesafetystandards.
Theltersrequireregularreplacement.Thefrequencydependsontheamountofdustintheairandthe
operatingconditions.
Blockedlterscanreducetheairowintheunit.Incorrectairowwillreducethecapacityandtheenergy
efciencyoftheunit.
Checkthedegreeofdirtaccumulationbymeasuringthedifferentialpressureorbyinspectingthelters
visually.
Altermonitorwillactivateanalarmifthepressuredropacrossthelteristoogreat.
ThepermittedpressuredropsetpointissetbyMuntersatthefactory.Ifthelterclassicationsarechanged,
adjustthesetpointtosuitthenewlter.
Replacethelterswhen:
Finalpressuredropisreached.
Thereisalteralarm.
Thelterisdamagedandairispassingwithoutltration.
Cleantheltersection,checkthatthereisnodirtbeyondthelter.
Makesurethattheframesaresealedandifnecessaryreplacetheseals.
Replacethelterandcheckitstightness.
17MaincomponentsdescriptionTEN-MLP-E1505
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32