Munters MLPlus Owner's manual

  • Hello! I am an AI chatbot trained to assist you with the Munters MLPlus Owner's manual. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
Originalinstructions
Operatingmanual
MLPlus
Dehumidicationsystem
TEN-MLP-E1505©MuntersEuropeAB2015
Tableofcontents
Tableofcontents...........................iii
1Introduction.................................1
1.1Denition...............................
1
1.2Aboutthismanual.....................
1
1.3Warnings...............................
2
1.4Warranty...............................
2
1.5Inspectionofdelivery..................
2
1.6Marking................................
3
1.7Technicalspecications..............
3
1.8Unintendeduse........................
3
2Safety.........................................4
2.1Intendeduse...........................
4
2.2Safeinstallation,operationand
maintenance...........................
4
2.3Residualrisks..........................
6
2.4Warningsigns.........................
7
2.5Quickstop..............................
7
3Systemdesignandfunction..............8
3.1Mainfunction..........................
8
3.2Systemdesign.........................
8
3.3Pre-andpost-treatment..............
9
4Maincomponentsdescription............10
4.1Dehumidier...........................
10
4.1.1Principleofoperation..........
10
4.1.2Dehumidiercomponents.....
12
4.1.3Markingofconnections........
13
4.2Watercoils.............................
14
4.2.1Productdescription............
14
4.2.2Coilmaintenance..............
14
4.3Directexpansionrefrigeration........
15
4.4Electricheater.........................
15
4.5Humidier..............................
16
4.6Supplyfan..............................
16
4.7Filters...................................
17
4.7.1Filtertypes......................
17
4.7.2Filtermaintenance.............
17
4.8Dampers...............................
18
5Operation....................................19
5.1Mainpowerswitch.....................
19
5.2Controlsystem........................
19
5.3HMIconnection........................
20
5.4Operatorpanel........................
20
5.5Starttheunit...........................
21
5.6Stoptheunit............................
21
5.7Quickstop..............................
21
6Serviceandmaintenance.................22
6.1Safety..................................
22
6.2General................................
23
6.3Serviceoptions........................
23
6.4Extendedwarranty....................
23
6.5Cleaning...............................
23
6.6Maintenanceschedule................
24
6.7Preventivereplacements.............
25
7Scrappinganddisposal...................26
8ContactMunters............................27
TEN-MLP-E1505Tableofcontentsiii
MLPlusDehumidicationsystem
1Introduction
1.1Denition
TheDehumidicationsystemdescribedinthismanualishereafterreferredtoasthe“unit”.
1.2Aboutthismanual
Thisoperatingmanualcontainsimportantsafetyinformation,aproductdescriptionandmaintenance
instructionsforthedeliveredunit.
Readallrelevantpartsofthismanualbeforeoperatingorperforminganyworkontheunit.Observanceof
thisinformationwillhelpyoutoavoiddanger,tominimiserepaircostanddowntime,andtoincreasethe
reliabilityandtheservicelifeoftheunit.
Thismanualshouldbestoredinapermanentlocationclosetotheunit.
Thismanualdoesnotdescribeinfullallthemaintenanceworkrequiredtoguaranteethelongevityand
reliabilityofthistypeofequipment.AlwayscontactMuntersforserviceandrepairs,toensuresafeandlong
lastingoperationoftheunit.
Installationinstructionscanbefoundinthecorrespondingsupplement.
Thecontentsofthismanualcanbechangedwithoutpriornotice.
NOTE!Thismanualcontainsinformationwhichisprotectedbycopyrightlaws.Itisnotallowedtoreproduceor
transmitanypartofthismanualwithoutwrittenconsentfromMunters.
Sendanycommentsregardingthismanualto:
MuntersEuropeAB
TechnicalDocumentation
P.O.Box1150
SE-16426KISTASweden
e-mail:t-doc@munters.se
1IntroductionTEN-MLP-E1505
MLPlusDehumidicationsystem
1.3Warnings
Informationaboutdangersareinthismanualindicatedbythecommonhazardsymbol:
W W
W
ARNING! ARNING!
ARNING!
Indicatesapossiblehazardthatcanresultinseverepersonalinjuryordeath.
CA CA
CA
UTION! UTION!
UTION!
Indicatesapossiblehazardthatcanresultindamagetotheunitorotherproperty,orcauseenvironmental
damage.
NOTE!Highlightssupplementaryinformationforoptimaluseoftheunit.
1.4Warranty
ThewarrantyisbasedonthetermsofsaleanddeliveryofMunters.Thewarrantyisnotvalidifrepairsor
modicationsarecarriedoutwithoutthewrittenagreementofMunters,oriftheunitdoesnotoperateunder
theconditionsagreedwithMunters.Damagesresultingfromnegligence,poormaintenanceorfailureto
complywiththerecommendationswillnotbecoveredbythewarranty.
Itisaconditionofthewarrantythattheunitforthefullwarrantyperiodisservicedandmaintainedbya
qualiedMuntersengineerorMuntersapprovedengineer.Accesstospecicandcalibratedtestequipment
isnecessary.Theserviceandmaintenancemustbedocumentedforthewarrantytobevalid.
Thewarrantyislimitedtoafreeexchangeofpartsorcomponentswhichhavefailedasaresultofdefects
inmaterialsorworkmanship.
Commissioning/Start-upinspection"S"byMuntersismandatorytovalidatethefullwarranty.
AlwayscontactMuntersforserviceorrepair.Operatingfaultscanoccuriftheunitismaintained
insufcientlyorincorrectly.
1.5Inspectionofdelivery
Inspectthedeliveryandcomparewiththedeliverynote,orderconrmationorotherdelivery
documentation.Makesurethateverythingisincludedandnothingisdamaged.
ContactMuntersimmediatelyifthedeliveryisnotcompleteordamagedinordertoavoidinstallation
delays.
Removeallpackagingmaterialfromtheunit,andmakesurethatnodamagehasoccurredduring
transportation.
AnyvisibledamagemustbereportedinwritingtoMunterswithin3daysandpriortoinstallationof
theunit.
Disposeofthepackagingmaterialaccordingtolocalregulations.
TEN-MLP-E1505Introduction2
MLPlusDehumidicationsystem
1.6Marking
Type
Fa br. No. 1005 190XXX XXXXX
3N ~ 400 V 50 Hz
0,78 kW
Ma x (A)
10,3/0,8/0,8
Munte rs Europe AB
Is a fjords ga ta n 1
164 26 Kis ta , S wede n
M
IP 33
Fa br. ye a r
1,8 kW
Ma de in S wede n
MLT350 P lus 9A
2010
Ma x (kW)
2,58 kW
Figure1.1ExampleofidenticationplatecontentFigure1.2Identicationplateposition
1.7Technicalspecications
Thetechnicalspecicationsfortheunitcanbefoundinthecorrespondingsectionofthemanual.
1.8Unintendeduse
Theunitisnotintendedforoutdoorinstallation.
Theunitisnotintendedforuseinclassiedareaswhereexplosionsafetycompliantequipmentis
required.
Theunitmustnotbeinstallednearanyheatgeneratingdevicesthatcancausedamagetotheequipment.
Theunitisnotintendedfortreatingairpollutedwithsolvents,dustorotheraggressive,corrosiveor
abrasiveparticles.
3IntroductionTEN-MLP-E1505
MLPlusDehumidicationsystem
2Safety
2.1Intendeduse
TheunitdeliveredbyMuntersmustonlybeusedforthetreatmentofair.Thisincludesltering,heating,
cooling,humidifying,dehumidifyingandtransportingair.Muntersexplicitlyrulesoutanyotheruse.
Theunitisdesignedtomeetthesafetyrequirements,directivesandstandardslistedintheEUDeclarationof
Conformity.
NomodicationoftheunitisallowedwithoutpriorapprovalbyMunters.Attachmentorinstallationof
additionaldevicesisonlyallowedafterwrittenagreementbyMunters.
Theconditionsofoperationspeciedinthetechnicalspecicationsmustbeobservedabsolutely.
Anyotheruseoftheequipmentcancausepersonalinjuryanddamagetotheunitandotherproperty.
2.2Safeinstallation,operationandmaintenance
Greatefforthasbeenplacedonthedesignandmanufactureoftheunit,tocomplywithapplicablesafety
aspectsforthistypeofequipment.
Theinformationinthismanualincludessuggestionsforbestworkingpracticeandshallinnowaytake
precedenceoverindividualresponsibilitiesorlocalregulations.
Duringoperationandotherworkwithamachineitisalwaystheresponsibilityoftheindividualtoconsider:
Thesafetyofallpersonsconcerned.
Thesafetyoftheunitandotherproperty.
Theprotectionoftheenvironment.
Alwayscarryoutriskassessmentsbeforedoinganyworkontheunit.
W W
W
ARNING! ARNING!
ARNING!
-Theunitmustnotbesplashedwithorimmersedinwater.
-Theunitmustneverbeconnectedtoavoltageorfrequencyotherthanthatforwhichitwasdesigned.Refertothe
identicationplate.Linevoltagethatistoohighcancauseanelectricalshockhazardanddamagetotheunit.
-Donotinsertngersoranyobjectsintotheairvents.
-Allelectricalinstallationsmustbecarriedoutbyaqualiedelectricianandinaccordancewithlocalregulations.
-Thedehumidiercanrestartautomaticallyafterapowercut.Alwayssetandlockthemainpowerswitchinthe
OFFpositionbeforecarryingoutanyservicework.
-Useonlyapprovedliftingequipmenttopreventpersonalinjuryanddamagetotheequipment.
-AlwayscontactMuntersforserviceorrepair.
W W
W
ARNING! ARNING!
ARNING!
Installation,adjustments,maintenanceandrepairsmustonlybecarriedoutbyqualiedpersonnelwhoare
awareoftherisksinvolvedwhenworkingwithequipmentoperatingwithhighelectricalvoltageandhighmachine
temperatures.
TEN-MLP-E1505Safety4
MLPlusDehumidicationsystem
W W
W
ARNING! ARNING!
ARNING!
Commissioningandinitialstart-upoftheunitmustbecarriedoutbyauthorizedpersonnelonly.
W W
W
ARNING! ARNING!
ARNING!
Theunitcontainsrotatingfansandothermovingparts.
Keephandsawayfromfanbladesatalltimeswhileunitison.DONOTserviceunituntilthefanhascompletely
stopped.
AlwayssetandlockthemainpowerswitchintheOFFpositionbeforecarryingoutanyservicework.
Topreventpersonalinjury,theunitmustberunwithallpaneldoorsclosedandallremovablepanelsandprotective
gridsproperlyinplace.
Fansandothermovingpartscanstartautomaticallyandwithoutwarning.
W W
W
ARNING! ARNING!
ARNING!
Cleaningagents,coolingmedia,oilandgreasearesubstancesthataredangeroustopersonalhealthandtothe
environment.Theymustnotbeallowedtodrainawayintothesoilorthepublicsanitarysystem.Thedisposalof
suchsubstancesmustbeeffectedinaccordancewithlocalandnationallawandregulations.
CA CA
CA
UTION! UTION!
UTION!
Serviceandmaintenanceworkshouldonlybecarriedoutbyqualiedandtrainedpersonnel.Operatingfaultscan
occuriftheunitismaintainedinsufcientlyorincorrectly.
5SafetyTEN-MLP-E1505
MLPlusDehumidicationsystem
2.3Residualrisks
Inordertoavoidthepossibledangersinoperatingormaintainingtheunit,necessaryprotectionshavebeen
foreseen.However,therearestillsomeresidualrisksthatallpersonnelworkingwiththeunitmustbeaware
of:
Thehandlingofuidsinrefrigerating,heatingorcoolingcircuitscanbedangerous.Pleasestudythe
informationrelevantforeachtypeofuidtoavoiddangers.
Hotorcoldsurfacescancauseinjuries.Beforeintervening,waituntiltemperaturesbecomenormaloruse
protectiveclothing.
Sharpsteeledgesonboxesorcoilscancausecuts.Useprotectivegloves,particularlyduringdisassembly
orassembly.
Whenworkingwithornearfans,beawarethatremainingairowthroughtheunitcancausespontaneous
rotationofthefansandtherebycausingpersonalinjury.
Doorsforoverpressurecompartmentscanbeequippedwithadditionalsafetylocksagainstaccidental
opening.Makesurethatsuchlocksareclosedbeforestartingtheunit.
Whenworkingwithltersorinadustyarea:Toprotecttheuserfromdust,wearasuitableCEmarkedface
maskselectedandttedinaccordancewiththeapplicablesafetystandards.
Usehearingprotectionaccordingtoapplicablesafetystandardswhenworkinginanoisyenvironmentto
avoidhearingimpairment.
Dampersopenandcloseautomatically.Keephandsclearofthedamperswhentheyaremoving.
TEN-MLP-E1505Safety6
MLPlusDehumidicationsystem
2.4Warningsigns
Thefollowingwarningsignscanbepresentontheunit,towarntheusersofresidualriskswhichcancause
seriousinjuryordeath.Makesurethatallpersonnelworkingwithorneartheunitareawareofthemeaning
ofeachsign.
Figure2.1Riskofpersonal
injuryduetoelectricshock.
Figure2.2Hotairowor
surface.
Figure2.3Unitstarts
automatically.
Figure2.4Pinchhazard.
2.5Quickstop
Theunitcaninanemergencybestoppedusingthemainpowerswitch,seesection5.1,Mainpowerswitch.
CA CA
CA
UTION! UTION!
UTION!
Onlyusethemainpowerswitchtostoptheunitinthecaseofanemergency.Thenormalshutdownsequencewill
notbefollowed.Thefansstopandtheheatercanbeveryhot,whichcanresultindamagetotheheaterandother
componentsclosetoit.
7SafetyTEN-MLP-E1505
MLPlusDehumidicationsystem
3Systemdesignandfunction
3.1Mainfunction
TheMuntersPlusunitisdesignedtocontroltheairqualityinarchives,laboratories,cleanroomsorother
applicationswithhighdemandsonclimate.
Allunitsarealwaysdeliveredwithadehumidier.Othercomponentssuchascoolingandheatingcoils,
humidiersorsupplyfansaredelivereddependingontheindividualsystemspecication.
Thesystemissetupandoperatedfromtheoperatorpanel.Wallsensorsorductsensorsmeasurethe
temperatureandhumidityoftheprocessair.Thecontrolsystemandelectricalsafetyfunctionsforallthe
componentsareplacedintheelectricalpanel.
Allcomponentsareregulatedproportionatelyandconguredtoachieveoptimalcapacityandenergyuse
efciency.Theelectricheaterinthedehumidierhasthyristorcontrolandtheelectricheatersfortempering
theairarepulsecontrolled.Thesupplyairfanrunscontinuallytoensurepreciseclimatecontrol.Regulation
canbetimecontrolledonaweekly,monthlyandstipulatedfull-daybasisaswellaswinter/summerperiods
withspecicoperationaltemperatureandhumiditysettings.Severalpossibilitiesexistforconnectingto
buildingmanagementsystemsforcontrollingandmonitoringthefunctions.ContactyournearestMunters
representativeformoreinformationonautomaticsystemsorbusconnections.
3.2Systemdesign
1 2
3
4
8
7
6 5
Figure3.1MLPlussystemdesignexample*
1.Filter5.Post-coolingcoil
2.Pre-heatingcoil6.Post-heatingcoil
3.Pre-coolingcoil7.Humidier
4.Dehumidier8.Supplyfan
*Individualsystemsarebuilttospecication,andcanbedifferentfromthisexample.
TEN-MLP-E1505Systemdesignandfunction8
MLPlusDehumidicationsystem
3.3Pre-andpost-treatment
Pre-andpost-treatmentoftheprocessaircanbeperformedbythefollowingfunctionalcomponents:
Inletdamperstoenableisolationoftheunitfromtheairow.Thedampersareinstalledontheoutside
oftheunit.
Amixingboxallowingmixingfreshairwithrecirculationair.
Heatingcoil:Thecoilcanbeelectricorusehotwaterasheatingmedium.Inthecaseofhotwater,the
coilmustbeconnectedtoanexternalheatingmediumsupply.
Coolingcoil:Thecoiluseschilledwater,possiblymixedwithglycol.Thecoilmustbeconnectedto
anexternalmediumsupply.
Humidicationbyevaporationorsteaminjectioninordertoachievetheprocessairqualityspecication
duringdryambientconditions.Seethehumidiersupplement.
Filtersforvariousairqualityspecications.Filterscanbeequippedwithpressuredropsensorstoenable
"blockedlter"alarm.
Asupplyfantoachievetheexternalpressurerequirement.
9SystemdesignandfunctionTEN-MLP-E1505
MLPlusDehumidicationsystem
4Maincomponentsdescription
NOTE!Somecomponentsareoptional,andindividualsystemsarebuilttospecication.
NOTE!Allcomponentpicturesareexamples,andmaynotcorrespondtoindividualunits.
4.1Dehumidier
4.1.1Principleofoperation
3
4
1
2
Figure4.1Rotorprinciple
1.Processair
2.Dryair
3.Reactivationair
4.Wetair
Thedesiccantrotoristheadsorptiondehumidifyingcomponentintheunit.Therotorstructureis
comprisedofalargenumberofsmallairchannels.
Thedesiccantrotorismadeofacompositematerialthatishighlyeffectiveinattractingandretainingwater
vapour.Therotorisdividedintwozones.Theairowtobedehumidied,processair,passesthroughthe
largestzoneoftherotorandthenleavestherotorasdryair.Sincetherotorrotatesslowly,theincomingair
alwaysmeetsadryzoneontherotor,thuscreatingacontinuousdehumidicationprocess.
Theairowthatisusedtodrytherotor,reactivationair,isheated.Thereactivationairpassesthrough
therotorintheoppositedirectiontotheprocessairandleavestherotoraswetair(warm,moistair).This
principleenablesthedehumidiertoworkeffectively,evenatfreezingtemperatures.
TEN-MLP-E1505Maincomponentsdescription10
MLPlusDehumidicationsystem
1
2
3
4
Figure4.2Airowoverview
1.Processair
2.Dryair
3.Reactivationair
4.Wetair
11MaincomponentsdescriptionTEN-MLP-E1505
MLPlusDehumidicationsystem
4.1.2Dehumidiercomponents
1
3
2
4
5
6
7
8
9
10
11
12
13
14
15
16
Figure4.3Maincomponents
1.Electricalpanel9.
Processairfanimpeller
2.Reactivationheater10.
Processairlter
3.Drivemotor11.Lowerrotorcover
4.Pulley,beltdrive12.Roller,beltguide
5.
Reactivationairlter
13.Drivebelt
6.
Reactivationairfanimpeller
14.Rotor
7.
Reactivationairfanmotor
15.Rotor,sealingring
8.
Processairfanmotor
16.Upperrotorcover
NOTE!ML180,ML270,MLT350andML420eachhasjustonefanmotorwhichisplacedbetweenthefan
impellers.Theelectricalpanelcaninsomecaseshaveadifferentposition.
TEN-MLP-E1505Maincomponentsdescription12
MLPlusDehumidicationsystem
4.1.3Markingofconnections
Examplesoflabelswhichcanbeplacedonthedehumidierairinletsandoutlets.
3
2
4
5
4
2
3
1
Figure4.4Labelsforairinletsandoutlets
1.Processairinlet
2.Dryairoutlet
3.Reactivationairinlet
4.Wetairoutlet
13MaincomponentsdescriptionTEN-MLP-E1505
MLPlusDehumidicationsystem
4.2Watercoils
4.2.1Productdescription
Theunitcanhavewatercoilsforcoolingandheating.Thecoolingorheatingisonlyregulatedifthesupply
airfanisrunning.
CA CA
CA
UTION! UTION!
UTION!
Ifthereisariskoffreezingwhenuntreatedoutsideairisused,afrostprotectionmonitorsensormustbetted.The
coilsintheunitcanbeseriouslydamagedifthisisnotdone.
Allunitswithhotwatercoilsarealwaysdeliveredwithaninsertionsensorandoutletforaninsertionsensor.
Theheaderisprovidedwithapluggedoutletforventinganddraining.Ifthereisariskoffreezing,thesensor
mustbettedandconnectedaccordingtothewiringdiagramfortheunit.Therecanbeariskoffreezingif
theprocessairistakendirectlyfromoutside.
Ifthewaterinacoilfreezesthiscouldcauseseriousdamage.Afrozencoilmustalmostalwaysbereplaced.
Thewarrantyisnolongervalidevenifthecracksarenotvisible.
CA CA
CA
UTION! UTION!
UTION!
Hotandcoldwatersupplylinesmustonlybedesignedandexecutedbyqualiedpersonneltakingintoaccount
therespectiverelevantlocalregulations.
4.2.2Coilmaintenance
W W
W
ARNING! ARNING!
ARNING!
Coilnshavesharpedges.Alwayswearprotectivegloveswhenworkingwithcoils.
Checkforsignsofcorrosiononsurfaceswithanges.Cleanandrepairifnecessary.
Ifapplicable,removethedropletseparator.
Inspecttheinletsurface(towardsthecoolingcoil).Ifdirty,rinsewithwarmwater.
Airinthepipingreducesthecapacityofthecoil.Ventofftheairviatheairnippleonthehighesthorizontal
partoftheheader.
Inthecaseofalongoperationstoporwhenthetemperatureisbelowfreezingpoint,emptythewaterout
ofthecoil.Dothisviathenippleonthelowesthorizontalpartoftheheader.Notethatsomecoilscannot
bedrained.
CA CA
CA
UTION! UTION!
UTION!
Donotattempttocleanthewatercoilsmechanically.
NOTE!Inthecaseofdamage,contactMuntersService.Donotattempttocarryoutrepairs.
1.Thecoilsshouldbecheckedatleastonceayear,andcleanedifrequired.
2.Someofthedustwhichpassesthroughthelterscomestorestonthecoilcells.Thislayerofdust
affectstheairowandreducestherateofexchangeleadingtodecreasedunitefciency.
3.Thecoilsshouldthereforebekeptclean.Cleaningcanbedonebyusingavacuumcleaner,lowpressure
compressedairorlowpressurewaterandasoftbrush.Donotforgettocleantheunitinternallyafterthe
coilcleaning.Neveruseahighpressurecleaner,thiswilldamagethecoilns.
TEN-MLP-E1505Maincomponentsdescription14
MLPlusDehumidicationsystem
4.Furthermore,inthecaseofcoolingcoils,cleanthedriptrayandsiphonforthecondensationwateronce
peryear.Notethatsiphonsneedtoberelledwithwaterafterthewinterseason.
4.3Directexpansionrefrigeration
AppliestounitswithDXrefrigeration.
AdetaileddescriptionoftheDXcoolingfunctionandthecorrespondingcomponentsisfoundintheDX
Supplement.
ImportantinformationfortheoperatoroftheDXrefrigerationsystemisfoundintheDXSupplement.
ThemandatoryCommissioningandServiceLogbookisalsoavailableintheDXSupplement.
W W
W
ARNING! ARNING!
ARNING!
StrictlegalrequirementsapplyfortheoperationofDXcoolingsystemscontaininguorinatedgreenhousegases.
ReadmoreintheDXSupplement.
4.4Electricheater
Allelectricheatershaveminimallytwohightemperaturecut-outs,anautomaticresettingfunctionandcan
bemanuallyreset.Thehightemperaturecut-outcanberesetonthecoverofalltheelectricheaters.
Theelectricheaterpowerisproducedonatimebasisusingpulse-pausetechnology.Whenheatisrequired
theinbuiltregulationequipmentsignalsforfullpower(pulse)forasettime,dependingontheheat
requirement.Iftheheatrequirementincreases,thepulsetimeincreasesandthepausetimedecreases.When
theheatrequirementisreduced,thepulsetimedecreasesandthepausetimeincreases.
15MaincomponentsdescriptionTEN-MLP-E1505
MLPlusDehumidicationsystem
4.5Humidier
Humidiersareusedasneededtoachievetheprocessairqualityspecication.
Unitscanbeequippedwitheitheranevaporativehumidierorasteamhumidier.
Formoreinformationabouthumidiersifapplicable,seetherelevantdocumentationunderthesection
Othercomponents.
4.6Supplyfan
Theunitisequippedwithaplugtypesupplyfan.Thefanisdrivenbyanelectricmotorwhichiscontrolled
byafrequencyconverter.Thismakesitpossibletoadjusttheairpressureandairowfromtheoperator
paneltoachievetheexternalpressurerequirement.
Forspecicinformationaboutthefan,seetheOEMmanualunderthesectionOthercomponents.
TEN-MLP-E1505Maincomponentsdescription16
MLPlusDehumidicationsystem
4.7Filters
4.7.1Filtertypes
Figure4.5BaglterFigure4.6Panellters
4.7.2Filtermaintenance
W W
W
ARNING! ARNING!
ARNING!
Thereisarehazard,orriskofunitmalfunction,ifltersaremaintainedinsufcientlyorincorrectly.
W W
W
ARNING! ARNING!
ARNING!
Whenreplacingtheltersorworkinginadustyarea:Toprotecttheuserfromdust,wearasuitableCEmarkedface
maskselectedandttedinaccordancewiththeapplicablesafetystandards.
Theltersrequireregularreplacement.Thefrequencydependsontheamountofdustintheairandthe
operatingconditions.
Blockedlterscanreducetheairowintheunit.Incorrectairowwillreducethecapacityandtheenergy
efciencyoftheunit.
Checkthedegreeofdirtaccumulationbymeasuringthedifferentialpressureorbyinspectingthelters
visually.
Altermonitorwillactivateanalarmifthepressuredropacrossthelteristoogreat.
ThepermittedpressuredropsetpointissetbyMuntersatthefactory.Ifthelterclassicationsarechanged,
adjustthesetpointtosuitthenewlter.
Replacethelterswhen:
Finalpressuredropisreached.
Thereisalteralarm.
Thelterisdamagedandairispassingwithoutltration.
Cleantheltersection,checkthatthereisnodirtbeyondthelter.
Makesurethattheframesaresealedandifnecessaryreplacetheseals.
Replacethelterandcheckitstightness.
17MaincomponentsdescriptionTEN-MLP-E1505
/