Page: 5
Solatron™: Three-Phase Voltage Regulator — 20, 30, 50, 75 kVA
Electrical Considerations
The nominal input voltage applied to the Solatron™ unit shall be as listed on the unit nameplate� The nominal
operating frequency must match the nameplate frequency. The maximum continuous load must not exceed
the kVA nameplate rating� The unit must be grounded using the provided ground lugs�
!
WARNING
Failure to follow all instructions herein will cause death, severe injury, or significant equipment
damage, and void the unit warranty�
The unit must be installed in a location appropriate for industrial electrical equipment, which includes
but is not limited to the following characteristics:
• Compliance with IEEE 519�
• The input voltage waveform shall maintain 5% or less THD. If the THD percentage exceeds this value,
the unit’s performance may be adversely affected�
To Maintain UL1012 Listing
Each AC output power circuit shall be provided with overcurrent protection for all ungrounded conductors�
The voltage rating of the overcurrent protection shall not be less than the rating of the circuit which
with which it is used� The overcurrent protection device shall be a circuit breaker or a fuse evaluated
for use as branch circuit protection. The rating of the overcurrent protection device must meet NEC Article
240 requirements�
The output overcurrent protection devices are not included with the unit and must be provided by the end
user or purchaser� Failure to install the output overcurrent protection devices voids the UL1012 listing for
the unit�
Lug Size Tables
Input Circuit Breaker Lug Sizes (Copper wire only)
208V 240V 480V 600V
Cable
Range
Torque
Cable
Range
Torque
Cable
Range
Torque
Cable
Range
Torque
20kVA #14-1/0 7Nm or 61.95in-lb. #14-1/0 7Nm or 61.95in-lb. #14-1/0 7Nm or 61.95in-lb. #14-1/0 7Nm or 61.95in-lb.
30kVA #14-1/0 7Nm or 61.95in-lb. #14-1/0 7Nm or 61.95in-lb. #14-1/0 7Nm or 61.95in-lb. #14-1/0 7Nm or 61.95in-lb.
50kVA #10-250mcm 14Nm or 123.91in-lb. #10-250mcm 14Nm or 123.91in-lb. #14-1/0 7Nm or 61.95in-lb. #14-1/0 7Nm or 61.95in-lb.
75kVA (2) 3/0-250mcm 18Nm or 159.31in-lb. #10-250mcm 14Nm or 123.91in-lb. #14-1/0 7Nm or 61.95in-lb. #14-1/0 7Nm or 61.95in-lb.
Output Distribution Block Sizes (Copper wire only)
208V 240V 480V 600V
Cable
Range
Torque
Cable
Range
Torque
Cable
Range
Torque
Cable
Range
Torque
20kVA #14-2/0
#14-8: 5.6Nm or 50in-lb.
#6-2/0: 13.56Nm or 120in-lb.
#14-2/0
#14-8: 5.6Nm or 50in-lb.
#6-2/0: 13.56Nm or 120in-lb.
#14-2/0
#14-8: 5.6Nm or 50in-lb.
#6-2/0: 13.56Nm or 120in-lb.
#14-2/0
#14-8: 5.6Nm or 50in-lb.
#6-2/0: 13.56Nm or 120in-lb.
30kVA #14-2/0
#14-8: 5.6Nm or 50in-lb.
#6-2/0: 13.56Nm or 120in-lb.
#14-2/0
#14-8: 5.6Nm or 50in-lb.
#6-2/0: 13.56Nm or 120in-lb.
#14-2/0
#14-8: 5.6Nm or 50in-lb.
#6-2/0: 13.56Nm or 120in-lb.
#14-2/0
#14-8: 5.6Nm or 50in-lb.
#6-2/0: 13.56Nm or 120in-lb.
50kVA #14-2/0
#14-8: 5.6Nm or 50in-lb.
#6-2/0: 13.56Nm or 120in-lb.
#14-2/0
#14-8: 5.6Nm or 50in-lb.
#6-2/0: 13.56Nm or 120in-lb.
#14-2/0
#14-8: 5.6Nm or 50in-lb.
#6-2/0: 13.56Nm or 120in-lb.
#14-2/0
#14-8: 5.6Nm or 50in-lb.
#6-2/0: 13.56Nm or 120in-lb.
75kVA #4-500mcm 56.49Nm or 500in-lb. #4-500mcm 56.49Nm or 500in-lb. #14-2/0
#14-8: 5.6Nm or 50in-lb.
#6-2/0: 13.56Nm or 120in-lb.
#14-2/0
#14-8: 5.6Nm or 50in-lb.
#6-2/0: 13.56Nm or 120in-lb.