3.Technicalinformation
Hot/coldwaterconnectionfor
oor-standingDHWcylinder
TheDHWcylindermustbeconnectedinaccordancewiththefollowingpipework
diagram.
Thereshouldbenoshut-offsysteminstalledbetweentheoor-standingDHW
cylinder and the safety valve.
Ifthecylinderisconnectedtothehotandcoldwaterconnectionswith
non-metallicpipematerials,thecylindermustbeearthed.
Installingdirttrapsorothermodicationswhichconstricttheconnecting
linebetweentheoor-standingDHWcylinderandthesafetyvalveisnot
permitted.
- Observe the connection thread types:
- Flatgasketconnections(typeG),suchascoldwaterandDHWconnections:
Thesemustbettedwithaatgasket.
- Thread-sealing connections (type R): Using too much sealing material (e.g.
hemp),resultsinexcessivestressontheconnection.Thiscanresultinthe
enamel cracking. Make sure the thread between cylinder connection and
pipework is fully covered.
- ThecoldwaterandDHWconnections maycontainplasticsleeveinserts.
These must remain in the cylinder. Do not pull them out before installation.
Whenselectingtheinstallationmaterialforthesystem,observeengineering
standardsandanypossibleelectro-chemicalprocesses(mixedinstallation). The
cylindercanbeequippedwithanelectricboosterheaterwhichisttedwitha
highlimitsafetycut-out.Intheeventofamalfunction,thehighlimitsafetycut-
outdeactivatesfurtherheatingwhenamax.temperatureof110°Cisreached.
Therelevantconnectionsmustbedesignedforthistemperature,orelse
thetemperaturemustbelimitedbymeansofamixingvalve.
ItisgenerallyrecommendedthatDHWtemperaturesabove60°Carelimited
to60°Cbymeansofamixingvalve.
Hotwatercancauseinjuries,inparticularscalding.
Please note
Please note
Please note
Connectiontotheheatingsystem Thecylindermustbeequippedwithitsownsafetydevices(safetyvalve,
expansionvessel)ifitcanbeshutofffromtheheatingsystemorifthe
existingcomponentsarenotdesignedfortheadditionalbuffervolume.
Installingdirttrapsorothermodicationswhichconstrictthesupplylineto
the safety valve is not permitted. When selecting the installation material
forthesystem,observeengineeringstandardsandanypossibleelectro-
technicalprocesses(mixedinstallation).
Please note
Siting Thecylindersmayonlybeinstalledinroomswhichareprotectedfromfrost,
otherwisethecylinderandallwater-carryingttingsandsupplypipesmustbe
drained if there is a risk of frost.
Theformationoficeinthesystemmayresultinleaksandcould
destroythecylinder.
The installation room must provide enough space for maintenance and repair
workandthegroundmusthavesufcientload-bearingcapacity.
Drinkingwaterlter
Werecommend the installationofadrinkingwaterlterintothecold water
supply,asforeignbodiesintroducedintothesystemcanblockttingsandmay
lead to pipe corrosion.
Please note