  • Hello! I've reviewed the Network Installation Sheet for the Anybus X-gateway INTERBUS Slave Interface. This document outlines the features, installation, and setup of the device, including its top/bottom mounting options, baud rate settings, and LED indicators. I'm ready to answer your questions about this product.
  • What baud rate options are available for the INTERBUS slave interface?
    What items are required for installation?
    How can I set the correct baud rate?
Anybus X-gateway - INTERBUS Slave Interface Network Installation Sheet
www.anybus.comSP1748, rev. 3.00, Apr 2015
Accessories Checklist
The following items are required for installation:
USB cable (included)
INTERBUS cables (not included)
Installation and Startup Summary
1. Set the correct baud rate using the baud rate jumper
2. Connect the gateway to the network
3. Connect a PC to the gateway via USB (optional)
4. Power up and con gure the gateway
Baud Rate Jumper
The baud rate for the INTERBUS slave interface can be set to either
500 kbit/s or 2 Mbit/s by moving the Baud Rate Jumper.
2 Mbit/s
500 kbit/s
Technical Support
Technical support, documentation and software downloads are
available at www.anybus.com.
Technical questions regarding the INTERBUS eldbus system should
be directed to the INTERBUS homepage at www.interbus.com.
LED Indicators
LED Indication Meaning
GW Status See Gateway Installation Sheet
CC/RC Green Connection OK, INTERBUS master not in reset mode
Off -
BA Green Bus active
Off -
RD Yellow Remote bus disabled
Off -
TR Green PCP communication active
Off -
Product Overview
The INTERBUS interface can be either top- or bottom-mounted.
Both of these options are illustrated below.
Top-mounted Interface
Bus In Connector
(X1.1)
Bus Out Connector
(X1.2)
Power Connector (X3
)
Baud Rate Jumper
Bottom-mounted Interface
Bus In Connector
(X2.1)
Bus Out Connector
(X2.2) Baud Rate Jumper
Bus In Connector
Pin Signal
15
96
1 Non-inverted data output (DO1)
2 Non-inverted data input (DI1)
3 Signal ground
4, 5, 8, 9 (not connected)
6 Inverted data output (/DO1)
7 Inverted data input (/DI1)
Housing PE
Bus Out Connector
Pin Signal
96
15
1 Non-inverted data output (DO2)
2 Non-inverted data input (DI2)
3, 5 Signal ground
4, 8, 9 (not connected)
6 Inverted data output (/DO2)
7 Inverted data input (/DI2)
Housing PE
Top-mounted
GW Status
BA
CC/RC
RD
TR
GW Status
BA
CC/RC
RD
TR
USB
(X4)
USB
(X4)
B
otto
m-m
ou
n