  • Hello! I am an AI chatbot trained to assist you with the Takagi T?K4?OS Installation Manual And Owner's Manual. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!





‐Do not store or use gasoline or  other
flammablevaporsandliquidsinthevicinityof
thisoranyotherappliance.
‐WHATTODOIFYOUSMELLGAS
β€’ Donottrytolightanyappliance.
β€’ Do not touch any electric switch, do not
useanyphonein
yourbuilding.
β€’ Immediately callyourgassupplierfroma
neighbor's phone. Follow the gas
supplier'sinstructions.
β€’ Ifyoucannotreachyourgassupplier, call
thefiredepartment.
‐Installation and service must be performed
byaqualifiedinstaller,serviceagencyorthe
gassupplier.


TAKAGI



FEATURING
β€’ ENDLESSHOTWATER
β€’ ONDEMANDUSAGE
β€’ COMPACT,SPACESAVING
β€’ ENERGYCONSERVATION
β€’ COMPUTERIZEDSAFETY
β€’ NOPILOTLIGHT
β€’ EASY‐LINKSYSTEM(OnlyT‐D2‐IN&T‐D2‐OS)
GasTanklessWaterHeater
Suitablefor p otablewaterheatingandspace‐heating
*
*Pleaserefertolocalcodesforspace‐heatingcompliance.
Ifyouhaveanyquestions,please
callorwriteto:
5Whatney
Irvine,CA92618
TollFree:1‐888‐882‐5244
On‐DemandWaterHeater
InstallationManualandOwner’sGuide
Model
・T‐KJr2‐IN・T‐KJr2‐OS
・T‐K4‐IN・T‐K4‐OS
・T‐D2‐IN・T‐D2‐OS
WARNING
Iftheinformationinthese
instructionsisnotfollowed
exactly,afireorexplosion
mayresultcausing
propertydamage,personalinjuryordeath.
β€œANSIZ21.10.3”
andξ€ƒβ€œCSA4.3”
OnlyT‐D2models
Contents
2β”‚Page
CONTENTS


































SPECIFICATIONS…………………………………………………………………………………………..………………………...
INTRODUCTION…………………………………………………………………………………………………..………………….
SAFETYGUIDELINES…………….………………………………………………………………………………………..………..
INSTALLATION………………………………………………………………………………………………..…………………..….
General………………………………………………………………………………………………………………………..…..…
Clearances……………………………………………………………………… ……………………………………………………
IncludedAccessories…………….………………………………………………………………………………………..…..
OptionalItems……………………………………………………………………………………………………………………..
High‐AltitudeInstallations……………………………………………………………………………………………………
.
VentingInstructions…………………………………………………………………………………………………………….
.
GasSupplyandGasPipeSizing………......................................................................................…
WaterConnections……………..…………………………………………………………………………………………….…
ElectricalConnections……………………………………………………………………..…………………………….......
RemoteControllerConnections.……..……………………………………………………………………………….…
PumpControlMode(OnlyT‐D2‐IN&T‐D2‐OS)………………………….……………………………….………
Easy‐LinkSystem(OnlyT‐D2‐IN&T‐D2‐OS)…….……………………...…………………………………..…....
APPLICATIONS...………………………………………………………………………………………………………………………
INITIALOPERATION..………………………………………………………………………………………………………….……




OPERATINGSAFETY…………………………………………………………………………………………………………………
NORMALOPERATION…………………………………………………………………………………………………………..…
General………..……….………….…………………………………………………………………………………………………
TemperatureSettings.…….……..……………………………………………………………………………………………
Flow…………………………………………………………………………………………………………………………………….
FreezeProtectionSystem…….…………………………………………………………………………………………..…
MaintenanceandService………………………………………………………………………………………………….…
UnitDrainingandFilterCleaning…………………………………………………………………………………………
TROUBLESHOOTING……..……………………………………………………………………………………………………..…
General………..……….………….…………………………………………………………………………………………………
ErrorCodes.…………………….…..………………………………………………………………………………………………
COMPONENTSDIAGRAM……………………………………………………………………………………………………..…
PARTSLIST………………….………………………………………………………………………………………………..…………
OUTPUTTEMPERATURECHART…………………………………………………………………………………………...…
PRODUCTREGISTRATIONANDLIMITEDWARRANTY…………....…………………………………………….…
…

3
4
5
6
6
8
8
9
11
12
17
20
21
22
23
24
28
30




31
33
33
33
35
35
36
36
37
37
39
42
46
48
50




InstallationManual
Owne
r
’sGuide
Specifications
3β”‚Page

SPECIFICATIONS
Model T‐KJr2‐IN T‐KJr2‐OS T‐K4‐IN T‐K4‐OS T‐D2‐IN T‐D2‐OS
NaturalGasInput
(OperatingRange)
Min:19,500Btu/h
Max:140,000Btu/h
Min:11,000Btu/h
Max:190,000Btu/h
Min:11,000Btu/h
Max:199,000Btu/h
PropaneInput
(OperatingRange)
Min:19,500Btu/h
Max:140,000Btu/h
Min:11,000Btu/h
Max:190,000Btu/h
Min:11,000Btu/h
Max:199,000Btu/h
GasConnection ¾”NPT
WaterConnections
¾”NPT
WaterPressure 15‐150psi*
NaturalGas
InletPressure
Min.5.0”WC
Max.10.5”WC
Propane
InletPressure
Min.8.0”WC
Max.14.0”WC
Manifold
Pressure**
Natural 2.0”WC 2.5”WC 2.0”WC 2.5”WC 2.0”WC 2.5”WC
Propane 2.5”WC 3.1”WC 3.7”WC 4.0”WC 3.7”WC 4.5”WC
Weight 28.7lbs. 34.6lbs.
Dimensions
H20.5”xW13.8”xD6.7”
 H20.5”xW13.8”xD8.5”
Ignition ElectricIgnition
Electric
Supply 120VAC/60Hz
Consumption
Operation
73.1W/0.61A 87.6W/0.73A 89.8W/0.75A
Standby 6.2W/0.05A 6.2W/0.05A 6.2W/0.05A
Freeze‐
Protection
111W/0.93A 111W/0.93A 111W/0.93A
*40psioraboveisrecommendedformaximumflow.
**TheManifoldPressureisthefactorysettingandgenerallyshouldnotneedadjustment.
NOTE:
β€’ Checktheratingplatetoensurethisproductmatchesyourspecifications.
β€’ InaccordancewithANSIZ21.10.3,COemissiondoesnotexceed400PPMfor
normalinput.
β€’ Themanufacturerreservestherighttodiscontinue,orchangeatanytime,
specificationsordesignswithoutnoticeandwithoutincurringobligations
.
I
I
I
n
n
n
s
s
s
t
t
t
a
a
a
l
l
l
l
l
l
a
a
a
t
t
t
i
i
o
o
o
n
n
n
M
M
M
a
a
a
n
n
n
u
u
u
a
a
a
l
l
l


Introduction
4β”‚Page
INTRODUCTION
*Thisdiagram
illustratestankless
waterheaterdesign
conceptsonlyand
doesnotaccurately
representtothewater
heater’sphysical
description.
β€’ This manual provides information necessary for the installation, operation, and
maintenanceofthewaterheater.
β€’ Themodeldescriptionislistedontheratingplatewhichisattachedtothefrontpanel
ofthewaterheater.
β€’ Pleasereadallinstallationinstructionscompletelybeforeinstallingthisproduct.
β€’ If you have any problems or questions regarding this equipment, consult with the
manufactureroritslocalrepresentative.
β€’ Thisequipmentisanon‐demand,tanklesswaterheaterdesignedtoefficientlysupply
endlesshotwaterforyourneeds.
β€’ Theprinciplebehindtanklesswaterheatersissimple:













1. Ahotwatertapisturnedon.
2. Waterenterstheheater.
3. Thewaterflowsensordetectsthewaterflow.
4. Thecomputerinitia testhefanmotorandsendsasignaltotheignitertocreateanignition
spark.
5. Thegasignitesandflames
appearwithintheburnerchamber.
6. Watercirculatesthroughtheheatexchangerandthengetshot.
7. Usingthermistorstomeasuretemperaturesthroughoutthewaterheater,thecomputer
modulatesthegasandwatervalvestoensureproperoutputwatertemperature.
8. Whentheta
p
isturnedoff
,
theunitshutsdown.
β€’ The T‐KJr2‐IN, T‐K4‐IN, & T‐D2‐IN are to be only installed indoor (direct‐vent
convertible).TheT‐KJr2‐OS,T‐K4‐OS,&T‐D2‐OSaretobeonlyinstalledoutdoor.
SafetyGuidelines
5β”‚Page



β€’ Watertemperaturesover125Β°F (52
Β°
C) cancausesevereburnsinstantlyordeath
fromscalding. The water temperatureisset at 122Β°F (50Β°C) from the factory to
minimizeanyscaldingrisk.Beforebathingorshoweringalwayscheckthewater 
temperature.
β€’ Do notstoreorusegasolineorotherfl ammables,vapors,orliquidsinthevicinity
ofthisappliance.
β€’ Do  not reverse the water and/or gas connections as this will damage the gas
valves and can cause severe injury or death. Follow the diagram on p. 20 when
installingyourwaterheater.
β€’ Do notusethisapplianceifanyparthasbeenincontactwithorbeenimmersed
in water. Immediately call a licensed plumber, a licensed gas fitter, or a
professionalservicetechniciantoinspectand/orservicetheunitifnecessary.
β€’ Do  not disco nnect  the electrical supply if the  ambient temperature will drop
belowfreezing.TheFreezePreventionSystemonlyworksiftheunithaselectrical
power.Thew a rrantywillnotbecoverediftheheatexchangerisdamageddueto
freezing.RefertothesectionontheFreezePreventionSystemon
p.35formore
information.
SAFETYGUIDELINES

SAFETYDEFINITIONS
Indicatesanimminentlyhazardoussituationwhich,ifnotavoided,willresultin
deathorseriousinjury.
Indicatesanimminentlyhazardoussituationwhich,ifnotavoided,couldresult
indeathorseriousinjury.
Indicatesanimminentlyhazardoussituationwhich,ifnotavoided,couldresult
inminorormoderateinjury.
GENERAL
1. Follow all local codes, or in the absence of local codes, follow the most recent edition of the
NationalFuelGasCode:ANSIZ223.1/NFPA54intheUSAorCAN/CSAB149.1NaturalGas,Propane
InstallationCodeinCanada.
2. Properlygroundtheunit inaccordance withall localcodes or
intheabsenceoflocalcodes,with
the National Electrical Codes:ANSI/NFPA70 in the USA or CSA standard C22.1CanadaElectrical
CodePart1inCanada.
3. Carefullyplanwhereyouintendtoinstallthewaterheater.Pleaseensure:
β€’ Yourwaterheaterwillhaveenoughcombustibleairand
properventilation.
β€’ Locateyourheaterwherewaterleakagewillnotdamagesurroundingareas(pleaserefer
top.7).
4. ChecktheratingplateforthecorrectGASTYPE,GASPRESSURE,WATERPRESSUREandELECTRIC
RATING.
*If this unit does not match your requirements, do not install and consult with the

manufacturer.
5. Ifany problem should occur, turn off all hot water taps and turn off the gas. Then call  a trained
technicianortheGasCompanyorthemanufacturer.
WARNING
CAUTION
DANGER
WARNING
Installation
6β”‚Page
INSTALLATION
GENERAL

1. Follow all local codes, or in the absence of local codes, follow the most recent edition of the
National Fuel Gas Code: ANSI Z223.1/NFPA 54 in the USA or CAN/CSA B149.1 Natural Gas,
PropaneInstallationCodeinCanada.

2. Allgaswaterheatersrequirecarefulandcorrectinstallationto
ensuresafeandefficient
operation.Thismanualmustbefollowedexactly.Readtheξ€ƒβ€œSafetyGuidelines”section.

3. Themanifoldgaspressureispresetatthefactory.Itiscomputercontrolledandshouldnot
needadjustment.

4. Maintainproperspaceforservicing.Installtheunitsothatitcanbeconnected
orremoved
easily.RefertotheClearancesSectiononp.8forproperclearances.


5. Thewaterheatermustbeinstalledinalocationwheretheproperamountofcombustibleair
willbeavailabletoitatalltimeswithoutobstructions.

6. Theelectricalconnectionrequiresameansofdisconnection, toterminatepowertothewater
heaterforservicingandsafetypurposes.


7. Donotinstalltheunitwheretheexhaustventispointingintoanyopeninginabuildingorwhere
thenoisemaydisturbyourneighbors.Makesuretheventterminationmeetstherequired
distancebylocalcodefromanydoorwayoropeningtopreventexhaustfromenteringabuilding
(refer
top.15).

8. Particlesfromflour,aerosols,andothercontaminantsmayclogtheairventorreducethe
functionsoftherotatingfanandcauseimproperburningofthegas.Regularlyensurethatthe
areaaroundtheunitisdust‐ordebris‐free;regularmaintenanceisrecommendedforthese

typesofenvironment.

9. Ifyouwillbeinstallingthewaterheaterinacontaminatedareawithahighlevelofdust,sand,
flour,aerosolsorothercontaminants/chemicals,theycanbecomeairborneandenterandbuild
upwithinthefanandburnercausingdamagetothewaterheater.


10. FortheT‐KJr2‐IN,T‐K4‐IN,andT‐D2‐INmodels:
β€’ Theseunitsmaybeconv ertedtoadirect‐vent(sealedcombustion)appliancebyinstalling a
direct‐ventconversionkit(PartNo. TK‐TV10)whichwillbringinallrequiredcombustibleair
from outside the building.When
 installing the TK‐TV10 conversion kit, please follow all
instructionsincludedwiththekit.
β€’ Ifthewaterheaterisusedasadirect‐ventappliance, theunitrequiresa3”combustibleair
supply pipe. Theintakepipe mustbesealed airtight. Air supply pipe can bemadeof ABS,
PVC, galvanized steel, corrugated aluminum, corrugated stainless steel or Category III
stainlesssteel.
β€’ Terminatingtheventingthroughasidewallisrecommendedforthedirect‐ventsystem.
β€’ Runningtheexhaustventandtheintakepipeparallelisrecommended.
β€’ Terminating the exhaust and intake on the same wall / surface
 is recommended.
Terminating in the same pressure zone allows for pressure balancing, which prevents
nuisanceshutdowns.

11. ForT‐KJr2‐OS,T‐K4‐OS,&T‐D2‐OS:
β€’ Tobeinstalledoutdoorsandonlyinareaswithmild,temperateclimates.
Installation
7β”‚Page
β€’ Installation and service must be performed by a qualified installer (for
example, a licensed plumber or gas fitter), otherwise the warranty will be
void.
β€’ Theinstaller(licensedprofessional)is responsibleforthecorrec tinstallation
of the water heater and for compliance with all national, state/provincial,
andlocalcodes.
β€’ Themanufacturerdoesnotrecommendinstallingthewaterheaterinapitor
locationwheregasandwatercanaccumulate.
β€’ Do nothavetheventterminalpointingtowardanyoperatingwindow,door,or
openingintoabuilding.
β€’ Do  not install next to any source  of airborne  debris, such as a clothes dryer,
that can cause debris to be trapped inside the combustion chamber, unless
thesystemisdirect‐vented.
β€’ The manufacturer does not recommend  installing the water heater in an
atticduetosafetyissues.Ifyouinstallthewaterheaterinanattic:

β€’ Makesuretheunitwillhaveenoughcombustionairandproperventilation.
β€’ Keep the area around the water heater clean. When dust collects on the
flamesensor,thewaterheaterwillshutdownonanerrorcode.

β€’ If the above conditions cannot be met, use the direct vent conversion kit
TK‐TV10.

β€’ Placetheunitforeasyaccessforserviceandmaintenance.
β€’ A drain pan, or other means of protection  against water  damage, is
re
q
uiredtobeinstalledunderthewaterheaterincaseofleaks.
β€’ Thewarrantywillnotcoverdamagecausedbywaterquality.
β€’ Onlypotablewaterorpotablewater/glycolmixturescanbeusedwiththis
water heater.Do not introduce pool or spa  water, or any chemically
treatedwaterintothewaterheater.
β€’ Water hardness levels must not exceed 7 grains per gallon (120 ppm) for
single family domestic applications or more than 4 grains per gallon (70
ppm) for all other types of applications.Water hardness leads to scale
formation and may affect/damage the water heater.Hard water scaling
mustbeavoidedor
controlledbyproperwatertreatment.
β€’ WaterpHlevelsmustbebetween6.5and8.5
β€’ Wellwatermustbetreated.
β€’ Do notinstalltheunitwherewater,debris,orflammablevaporsmaygetinto
theflueterminal.
β€’ The manufacturer recommends using the direct vent kit when the water
heater is inst alled ina beauty salon. Somechemicalsusedinabeauty salon
mayaffecttheflamesensor.Waterheatermaynotworkproperly.
β€’ Although the water heater is designed to operate with minimal sound, the
manufacturerdoesnotrecommendinstallingtheunitonawalladjacenttoa
bedroom,oraroomthatisintendedforquietstudyormeditation,etc.
β€’ Locateyourheaterclosetoadrainwherewaterleaka gewillnotdodamageto
surrounding areas.As with any water heating appliance, the potential for
leakageatsome timein thelifeoftheproductdoesexist.Themanufacturer
willnot beresponsibleforanywaterdamagethatmay occur.
Ifyouinstall a
drain pan under the unit, ensure that it will not  restrict the combustion air
flow.




CAUTION
WARNING
Installation
8β”‚Page


CLEARANCES













Model Top Bottom Front Back Sides
T‐KJr2‐IN* 12” 12” 24” 1” 2ξ€ƒβ€œξ€ƒ
T‐KJr2‐OS 36” 12” 24” 1” 2ξ€ƒβ€œξ€ƒ

Model Top Bottom Front Back Sides
T‐K4‐IN* 12” 12” 24” 1” 2ξ€ƒβ€œξ€ƒ
T‐K4‐OS 36” 12” 24” 1” 2ξ€ƒβ€œξ€ƒ

Model Top Bottom Front Back Sides
T‐D2‐IN* 12” 12” 24” 1” 2ξ€ƒβ€œξ€ƒ
T‐D2‐OS 36”  12” 24” 1” 2ξ€ƒβ€œξ€ƒ
*Standardindoorinstallations&direct‐ventindoorinstallationshavethesameclearances.





INCLUDEDACCESSORIES

Checkthattheseitemsbelowareincludedwiththewaterheater.

1. Installation Manual &
Owner’sGuide

2.
ProductRegistrationCard
 3.CommunicationCable
(OnlyT‐D2‐IN&T‐D2‐OSmodels)










Qty:1
Qty:1
Qty:1
Bottom
Side
Top
Side
Front
Back
Maintain all clearances around
thewaterheater.
Installation
9β”‚Page

OPTIONALITEMS
Model T‐KJr2‐IN T‐KJr2‐OS T‐K4‐IN T‐K4‐OS T‐D2‐IN T‐D2‐OS
TK‐RE02
βœ”ξ€ƒ βœ”ξ€ƒ βœ”ξ€ƒ βœ”ξ€ƒ
 
TM‐RE30    
βœ”ξ€ƒ βœ”ξ€ƒ
TK‐BF01
βœ”ξ€ƒ

βœ”ξ€ƒ

βœ”ξ€ƒ

TK‐TV10
βœ”ξ€ƒ

βœ”ξ€ƒ

βœ”ξ€ƒ

TK‐PC01  
βœ”ξ€ƒ βœ”ξ€ƒ βœ”ξ€ƒ βœ”ξ€ƒ
TK‐PCJr2
βœ”ξ€ƒ βœ”ξ€ƒ
   
TK‐RB02 
βœ”ξ€ƒ

βœ”ξ€ƒ

βœ”ξ€ƒ
TK‐KPWL4
TK‐KPWH4
βœ”ξ€ƒ

βœ”ξ€ƒ

βœ”ξ€ƒ

TK‐KPCT43
βœ”ξ€ƒ

βœ”ξ€ƒ

βœ”ξ€ƒ

1.TemperatureRemoteController:TK‐RE02
The Temperature Remote
Controllerhastwofunctions.It
allowstheoutputtemperature
from the water heater to be
adjusted within the range of
99 Β°F to 167 Β°F, and it  also 
worksasa diagnostic tool that will give a concise
error code whenever
 there is a problem with the
unit. The temperature options are 99Β°F, 100Β°F,
102Β°F, 104Β°F, 106Β°F, 108Β°F, 109Β°F, 111Β°F, 113Β°F,
115Β°F, 117Β°F, 122Β°F, 131Β°F, 140Β°F, 158Β°F, and
167Β°F. See the trouble shooting section for
informationonpossibleerrorcodes.
2.TemperatureRemoteController:TM‐RE30 
The Temperature Remote
Controller has
 two functions. It
allows the output temperature
from the water heater to be
adjustedwithin therangeof99
Β°Fto185°F,anditalsoworksas
adiagnostictoolthatwillgiveaconciseerrorcode
whenever there is a problem with the unit. The
temperature options are
99Β°F, 100Β°F, 102Β°F, 
104Β°F, 106Β°F, 108Β°F, 110Β°F, 111Β°F, 113Β°F, 115Β°F,
117Β°F, 122Β°F, 131Β°F, 140Β°F, 149Β°F, 158Β°F, 167Β°F,
176Β°Fand185Β°F.Seethetroubleshootingsection
forinformationonpossibleerrorcodes.
3.BackflowPreventer:TK‐BF01
The Backflow preventer prevents
the backflow of air through the
exhaust vent. This helps prevent
harmful exhaust gases from
entering the home, as well as
helpingtopreventtheunitfromfreezing inareas
where cold air can be blown or drawn into the
exhaust system.
 Install this vent damper in
accordance with the installation instructions and
anyapplicablecodes.

4.Direct‐VentConversionKit:TK‐TV10
Thiskitcanbeusedto
convertthewater
heaterfroma
standardventsystem
toadirect‐vent(or
sealedcombustion)
system.Installthis
conversionkitinaccordancewiththeinstallation
instructionsandanyapplicablecodes.
Installation
10β”‚Page
5.PipeCovers:TK‐PC01andTK‐PCJr2
The pipe cover protects the
plumbingpipestothewaterheater
from unexpected adjustments.
This pipe cover is fixed to the
bottom of the water heater, which
hides the plumbing and improves 
the visual aspects of the whole
installationforthewater
heater.
6. Recessbox:TK‐RB02
TheRecessboxwillallowfor
β€œclean”installations.Thewater
heaterfitsinsidetherecessbox,
whichhidesandprotectsthe
wholewaterheaterandplumbing.
TheRecessboxwillfitin‐between
mostwallstuds.
7.T‐VentWallThimblewithTermination:TK‐KPWL4andTK‐KPWH4

Theseterminationsareusedwhenventingoutthroughthewall
andarecompatiblewiththeT‐Ventpipesystem.
Theseterminationsarespecialstainlessstee lventsforgas
appliancesandareULlistedasCategoryII,II IandIV.Thereare
twotypesofterminations:theLouverterminationandtheHood

termination.Fordifferentwallthicknesses,therearetworanges
oflength savailable(refertotheT‐Ventbrochurefordetails).
Installtheseventterminat ionsinaccordancewiththeir
installationinstructi on sandanyapplicable localcodes.

8.Direct‐VentConcentricTermination:TK‐KPCT43

Usedwhenterminatingdirect‐vent(sealed‐combustion)systems,
withdirect‐ventmodelsthatrequirea3”intakeand a4”exhaust.
Thisconcentricterminationprovidestheconvenienceofonly
havingtomakeonepenetrationthroughasidewallinsteadoftwo
separatepenetrationsfortheintakeandexhaustpiping.The
terminationincludes
abirdscreen,restrictingsmallanimals,
pests,andforeignobjectsfromenteringintotheventsystem.
Thissidewallterminationisavailableinthreedifferentsizes,to
coverallrangesofwallthicknesses.
Direct‐ventConcentricTermination
Part# Coveringwallthickness
TK‐KPCT43‐1 3.9”–7.1”
TK‐KPCT43‐2 6.9”–10.1”
TK‐KPCT43‐3 9.8”–13.0”
Louver
Termination
TK‐KPWL4
Hood
Termination
TK‐KPWH4
Installation
11β”‚Page
β€’ DONOTadjustanydipswitchesontherightbankfortheT‐D2‐IN/OS
models.
β€’ Thedarksquaresindicatethedirectionthedipswitchesshouldbesetto.
Dipswitches
HIGH‐ALTITUDEINSTALLATIONS

Checktheelevationwhereyourwaterheaterisinstalled.Setdipswitchesshowninthetablebelow
dependingonthealtitude.



Altitude
0to2,000ft
(DEFAULT)
2,000to4,000ft
4,000to6,000ft Over6,000ft
SwitchNo.3 OFF
ON
OFF
Consult
our Technical
Services
Department
at1‐888‐
882‐5244
SwitchNo.4 OFF
OFF
ON

Altitude
0to2,000ft
(DEFAULT)
2,000to4,000ft
4,000to6,000ft Over6,000ft
SwitchNo.4 OFF
ON
OFF
Consult
our Technical
Services
Department
at1‐888‐
882‐5244
SwitchNo.5 OFF
OFF
ON
T‐KJr2‐IN/OS&T‐K4‐IN/OS
T‐D2‐IN/OS(Leftbankofdipswitches)
T‐KJr2‐IN
/
OS&T‐K4‐IN
/
OSCom
p
uterboard
WARNING
T‐D2‐IN
/
OSCom
p
uterboard
Leftbankofdipswitches
O
F
F
O
N
1
2
3
4
5
6
7
8
O
F
F
O
N
1
2
3
4
5
6
7
8
O
F
F
O
N
1
2
3
4
5
6
7
8
O
F
F
O
N
1
2
3
4
5
6
O
F
F
O
N
1
2
3
4
5
6
O
F
F
O
N
1
2
3
4
5
6
Installation
12β”‚Page
Improperventingofthisappliancecanresultinexcessivelevelsofcarbon
monoxidewhichcanresultinseverepersonalinjuryordeath.

Improperinstallationcancausenauseaorasphyxiation,severeinjuryordeathfrom
carbonmonoxideandfluegasespoisoning.Improperinstallationwillvoidproduct
warranty.

Wheninstallingtheventsystem,allapplicablenationalandlocalcodesmustbe
followed.Ifyouinstallthimbles,firestopsorotherprotectivedevicesandthey
penetrateanycombustibleornoncombustibleconstruction,besuretofollowall
applicablenationalandlocalcodes.

VENTINGINSTRUCTIONS
‐General‐
Thewaterheatermustbe vented inaccordancewith thesectionξ€ƒβ€œVentingof Equipment" ofthelatest
editionoftheNationalFuelGasCode:ANSIZ223.1/NFPA54intheUnitedStatesand/orSection7ofthe
CAN/CSA B149.1 Natural Gas and Propane Installation Code in Canada, as well
 as applicable local
buildingcodes.

The manufacturer recommends the β€œT‐Vent” line manufactured by TAKAGI (Refer to β€œT‐Vent”
brochure for details). However, the following are also UL listed manufacturers: ProTech Systems Inc.
(FasNSeal),Flex‐LInc.,Z‐FlexInc.(Z‐VentIII),Metal‐FabInc.,andHeat‐FabInc.(Saf‐TVent).


Generalrulesforventingwaterheatersare:
β€’ Placethewaterheaterascloseaspossibletotheventterminator.
β€’ Thevent coll arofthewaterheatermustbefasteneddirectlytoanunobstructedventpipe.
β€’ Donotweldtheventpipetothewaterheater’sventcollar.
β€’ Donotcuttheventcollaroftheunit.
β€’ Theventmustbeeasily removablefromthetopofthewaterheaterfornormalserviceand
inspectionoftheunit.
β€’ Thewaterheaterventmustnotbeconnectedtoanyothergasapplianceorventstack.
β€’ Avoid
usinganoversizedventpipeorusingextremelylongrunsofthepipe.
β€’ Forrooftopventing, araincaporotherformofterminationthatpreventsrainwater from
enteringintothewaterheatermustbeinstalled.
β€’ Donotcommonventorconnectanyventfromotherappliances
tothewaterheatervent.

Generalrulesforventterminations:
β€’ Avoidlocatingthewaterheaterventterminatornearanyairintakedevices.Thesefanscan
pick uptheexhaust flue productsfromthe water heater andreturnthemto thebuilding.
Thiscancreateahealthhazard.
β€’ Locate the vent terminator so that
 it cannot be blocked by any de bris, at any time. Most
codesrequir e thattheterminatorbe atleast12inchesabovegrade,butthe installermay
determineifitshouldbehigherdependingonthejobsitecondi tionandapplicablecodes.
β€’ A propersidewall terminatorisrecommendedwhen
thewa ter heaterisventedthrough  a
sidewall.
β€’ Regarding the clearances fromtheexhaustterm inatortotheairinlet or opening, refer to
thenextfewpages.
CAUTION
DANGER
Installation
13β”‚Page
‐Exhaustventing‐
(FortheT‐KJr2‐IN,T‐K4‐IN,&T‐D2‐INmodels)

ThisisaCategoryIIIapplianceandmustbeventedaccordingly.Theventsystemmustbesealedairtight.
Allseamsandjointswithoutgasketsmustbesealedwithhighheatresistantsilicone sealantorULlisted
aluminumadhesivetapehavingaminimumtemperatureratingof350Β°F.Forbestresults,a
ventsystem
shouldbeasshortandstraightaspossible.
β€’ ThiswaterheaterisaCategoryIIIapplianceandmustbeventedaccordinglywithany4”vent 
approvedforusewithCategoryIIIorSpecialBHtypegasvent.
β€’ Followtheventpipemanufacturer’sinstructionswheninstallingthe
ventpipe.
β€’ Donotcommonventthisappliancewithanyotherventedappliance(Donotterminatevent
into a chimney.If the vent must go through the chimney, the vent must run all the way
throughthechimneywithCategoryIIIapprovedorSpecialBHventpipe).
β€’ When
the horizontal vent run exceeds 5 ft., support the vent run at 3 ft. intervals with
overheadhangars.
β€’ Themaximumlengthofexhaustventpiping mustnotexceed50ft.(deducting5 ft.foreach
elbowusedintheventingsystem).Donotusemorethan5elbows.

Diameter Max.No.ofElbow Max.Vertical&Horizontal(Total)VentLength
4” 5 50ft.
*Foreachelbowadded,deduct5ft.frommax.Ventlength.
No.ofElbows Max.VerticalorHorizontalLength
0 50ft.
1 45ft.
2 40ft.
5 25ft.
‐VentingIllustrations‐
(FortheT‐KJr2‐IN,T‐K4‐IN,&T‐D2‐INmodels)

HorizontalInstallationDiagram
VerticalInstallationDiagram
SidewallVent
Terminator
Wall
BackflowPreventer*
VerticalCondensationDrain**
Fordetailsoftheoptionalitems,refertothe InstallationmanualforeachOptionalitem.
Roof
VerticalCondensation
Drain**
RoofFlashing
RainCap
BackflowPreventer*
Installation
14β”‚Page

*BackflowPreventer(Recommendedforfreezingweatherconditions:36
Β°
F andbelow)
**VerticalCondensationDrainmustbeinstalledaccordancewithlocalcodes.
HorizontalInstallationDiagram
WithDirect‐VentConcentric
Termination
HorizontalInstallationDiagram
(Withdirect‐venting)
VerticalInstallationDiagram
(Withdirect‐venting)
Thewaterheater
Intakeportof
Direct‐Vent
ConversionKit

InstallationDiagramofDirect‐Vent
ConversionKitwithwaterheater
Wall
Direct‐vent
Concentric
Termination
PlateofDirect‐VentConversionKit

Seethepicturebelowfordetailedconnection
instructionstotheDirect‐VentConversionKit.
VerticalCondensationDrain**

Backflow
Preventer*
Wall
Sidewall
Vent
Terminator
RoofFlashing
Vertical
Condensation
Drain**
Backflow
Preventer*
RainCap
Roof
Firestop
Installation
15β”‚Page

‐Ventterminationclearances‐


Canada U.S.A
Directventand
otherthanDirect
Vent
Directvent OtherthanDirectVent
A
Clearanceabovegrade,veranda,porch,deck,
orbalcony.
1foot 1foot 1foot
B
Clearancetowindowordoorthatmaybe
opened.
3feet 1foot
4feetfrombeloworside
opening.1footfrom
aboveopening.
C
Clearancetopermanentlyclosedwindow * * *
D
Verticalclearancetoventilatedsoffitlocated
abovetheventterminatorwithinahorizontal
distanceof2feet(61cm)fromthecenterline
oftheterminator.
* * *
E
Clearancetounventilatedsoffit * * *
F
Clearancetooutsidecorner * * *
G
Clearancetoinsidecorner * * *
H
Clearancetoeachsideof centerlineextended
abovemeter/regulatorassembly
3feet * *
I
Clearancetoserviceregulatorventoutlet. 3feet * *
J
Clearancetonon‐mechanicalairsupplyinlet
tobuildingorthecombustionairinlettoany
otherapplication.
3feet 1foot
4feetfrombeloworside
opening.1footfrom
aboveopening.
K
Clearancetomechanicalairsupplyinlet. 6feet 3feet 3feet
L
Clearanceabovepavedsidewalkorpaved
drivewaylocatedonpublicproperty.
7feet * 7feet
M
Clearanceunderveranda,porchdeck,or
balcony.
1foot * *
*ForclearancesnotspecifiedinANSIZ223.1/NFPA54orCAN/CSA‐B149.1,pleaseuseclearancesinaccordancewith
localinstallationcodesandtherequirementsofthegassupplier.
Installation
16β”‚Page
Pleasefollowalllocalandnationalcodesinregardstoproperterminationclea rances.
Intheabsenceofsuchcodes,thefollowingclearancescanbeusedasguidelines.Local
codessupersedetheseguidelines.



Forsidewallterminations

Exhausttermination
1ft.
1ft.
2ft.
Inside
corner
Formultiplesidewallexhaust
terminations(e.g.multi‐unit
systems),anexhausttermination
mustbeatleast1ft.awayfrom
anotherexhaustterminati on.An
exhaustterminationmustalsobe
atleast2ft.awayfromaninside
corner(iftheadjacentwallisless
than2ft.oflength,theminimum

requireddistanceawayfromthe
insidecornerwillbeequaltothe
lengthofthatadjacentwall).
Fordirect‐ventsidewall
terminationsthatusetwo
separatepenetrationsforthe
intakeandexhaust,distance
theintakeandexhaust
terminationsatleast3ft.away
fromeachother,nomatterthe
orientation.
Formultiple‐unit,direct‐ventsidewall
terminationsthatcombinetheintake
andexhaustintoasinglepenetration,
spaceeachdirect‐ventterminationat
least1ft.awayfromeachother,no
mattertheorientation.Adirect‐vent
terminationmustalsobeatleast2ft.
awayfromaninsidecorner(if
the
adjacentwallislessthan2ft.of
length,theminimumrequired
distanceawayfromtheinsidecorner
willbeequaltothelengthofthat
adjacentwall).
Formultiple‐unitrooftopterminations(whetherforstandardindooror
direct‐ventinstallations)spaceallexhaustandintaketerminationsin
accordance
withlocalcodes.Anexhaustterminationmustbespacedfrom
awallorsurfaceinaccordancewithlocalcodesaswell.Intheabsenceof
suchacode,anexhaustterminationmustbeahorizontaldistanceofat
least2ft.awayfromawallorsurface.
A:Inaccordancewith
localcodes
Forrooftopterminations

Airintake
Exhaust termination
A
A
A
A
A
2ft.
Airintake
Exhaust
termination
Exhaustand/ordirect‐vent
sidewallterminationsshould
beatleast2ft.awayfroman
oppositesurface/wall.Do
notplacethetermina tion
directlyinfrontofan
openingintoabuilding.
2ft.
Exhaust
termination
Airsupplyinlet
3ft.
3ft.
3ft.
Directventtermination
1ft.
1ft.
Inside
corner
2ft.
CAUTION
Installation
17β”‚Page
Sizethegaspipeappropriatelytosupplythenecessaryvolumeofgasrequiredfor
thewaterheaterusingANSI233.1/NFPA54intheUSAorCAN/CSAB149.1inCanada
orlocalcodes.Otherwise,flowcapabilitiesandoutputtemperatureswillbelimited.
β€’ Checkthatthetypeofgasmatchestheratingplatefirst.
β€’ Ensure that any and all gas regulators used are operating properly and
providing gas pressures within the specified range shown below. Excess gas
inletpressuremaycauseseriousaccidents.
β€’ Conversion of this unit from natural gas to propane or vise versa will void all
warranty. Contact your local distributor to get the correct unit for your gas
type.The manufacturer is not liable for any property and/or personal
damageresultingfromgasconversions.

GASSUPPLYANDGASPIPESIZING
‐General‐

β€’ Theminimumandmaximuminletgaspressuresare:
Gastype Inletgaspressure
NaturalGas Min.5.0”WC–Max.10.5”WC
Propane Min.8.0”WC–Max.14.0”WC
β€’ Gas pressure above this specified range for the water heater and/or insufficient gas volume will
adversely affect  performance.These pressures are measured when the water heater is in full
operation.
β€’ Inlet gas pressure must not exceed the above  maximum values; gas pressure above the specified
rangewillcausedangerous
operatingconditionsanddamagetotheunit.
β€’ Until testing of the main gas line  supply pressure is completed, ensure the gas line to the water
heaterisdisconnectedtoavoidanydamagetothewaterheater.



‐Gasconnections‐
1. Installamanualgasshut‐offvalvebetweenthewaterheaterandthegassupplyline.
2. When the gas connections are completed, it is necessary to perform a gas leak test (see below)
eitherbyapplyingsoapywatertoallgasfittingsandobservingfor bubblesor byusing
a gasleak
detectiondevice.
β€’ Thewaterheater anditsindividualshutoff  valvemustbe disconnected fromthe gassupply
pipingsystemduringanypressuretestingofthatsystemattestpressures inexcessof1/2psi
(3.5kPa).
β€’ Thewaterheatermustbeisolatedfromthegassupplypipingsystembyclosingitsindividual
manual shutoff valve during any pressure testing of the gas supply piping system at test
pressuresequaltoorlessthan1/2psi(3.5kPa).
3. Alwayspurgethegaslineofanydebrisand/orwater
beforeconnectingtothegasinlet.






WARNING
NOTICE
Installation
18β”‚Page


‐NaturalGasSupplyPiping‐
MaximumDeliveryCapacityofCubicFeetofGasperHourofIPSPipeCarryingNaturalGasof0.60SpecificGravity
BasedonPressureDropof0.5”WC

BasedonEnergyContentof1,000BTU/CubicFt.:Thewaterheaterrequires140CubicFt./hrfortheT‐KJr2‐IN/OS,
190CubicFt./hrfortheT‐K4‐IN/OS,and199CubicFt./hrfortheT‐D2‐IN/OS.
Unit:CubicFeetperHour
PipeSize LengthinFeet
Inches 10’ 20’ 30’ 40’ 50’ 60’ 70’ 80’ 90’ 100’ 125’ 150’ 200’
¾” 363 249 200 171 152 138 127 118 111 104 93 84 72
1” 684 470 377 323 286 259 239 222 208 197 174 158 135
1¼” 1,404 965 775 663 588 532 490 456 428 404 358 324 278
1½” 2,103 1,445 1,161 993 880 798 734 683 641 605 536 486 416
2” 4,050 2,784 2,235 1,913 1,696 1,536 1,413 1,315 1,234 1,165 1,033 936 801
‐Propane(LP)SupplyPiping‐
MaximumCapacityofPropane(LP)Basedon11”WCsupplypressureata0.5”WCpressuredrop
Unit:kBTUperHour
PipeSize
LengthinFeet
Inches
10’ 20’ 30’ 40’ 50’ 60’ 70’ 80’ 90’ 100’ 125’ 150’ 200’
¾” 567 393 315 267 237 217 196 185 173 162 146 132 112
1” 1,071 732 590 504 448 409 378 346 322 307 275 252 213
1¼” 2,205 1,496 1,212 1,039 913 834 771 724 677 630 567 511 440
1½” 3,307 2,299 1,858 1,559 1,417 1,275 1,181 1,086 1,023 976 866 787 675
2” 6,221 4,331 3,465 2,992 2,646 2,394 2,205 2,047 1,921 1,811 1,606 1,496 1,260
Formoreinformation,pleaseseethebelow.





BasedonEnergyContentof1,000BTU/CubicFt:

Divideeachappliance’sBTUrequirementby1,000BTUtoget
theappliancesCubicFt.requirement.

Takeintoaccountthedistancetheapplianceisfromthegas
meter,lookintheabovegascharttoproperlysizetheline.

Forsectionsofthegaslinesupplyinggastomorethanone
appliance(Ex:PointAtoPointB),addupthecubicft.
requirementsoftheappliancesthatarebeingsuppliedbythat
section,andsizetothefarthestappliance.

ForExample:ThesectionfromAtoBsuppliesgastothe
furnace,range,anddryer.AddinguptheBTUrequirements
anddividingby1,000yieldsacubicft.requirementof220
cubicft.ofgas.Thefarthestapplianceistherange,whichis50
ft.awayfromthemeter.Lookingattheabovechart,and
underthecolumnof50ft.,SectionAtoBneedstobe 1”in
ordertosupply220cubicft.
10’Length
1”PipeSize
C
GasSizingExample
(NaturalGas)
10’Length
3/4”PipeSize
15’Length
1/2”PipeSize
10’Length
1/2”PipeSize
Furnace
120,000BTU
Water
Heater
199,000BTU
5’Length
1‐1/4”PipeSize
Range
65,000BTU
10’Length
3/4”PipeSize
Dryer
35,000BTU
15’Length
1”PipeSize
5’Length
1‐1/4”PipeSize
GasMeter
B
A
Installation
19β”‚Page
1. Turnoffallelectricpowertothewaterheaterifserviceistobeperformed.
2. Turnthemanualgasvalvelocatedontheoutsideoftheunitclockwise3to
theoffposition.



‐Measuringinletgaspressure‐







Thewaterheatercannotperformproperlywithoutsufficientinletgaspressure.Belowareinstructions
onhowtochecktheinletgaspressure.THISISONLYTOBEDONEBYALICENSEDPROFESSIONAL.

1. Shutoffthemanualgasvalveonthesupplygasline.
2. Removethescrewforthe
pressureportlocatedon
thegasinletofthewaterheatershowninthe
diagramtotheright.
3. Connectthemanometertothepressureport.
4. Re‐openthemanualgasvalve.Checktoseethat
therearenogasleaks.Opensomeofthefixtures
thatusethehighest
flowratetoturnonthewater
heater.
5. Checktheinletgaspressure.Whenthewaterheater
isonmaximumburn,themanometershouldread
from5.0”to10.5”WCforNaturalgas,from8.0”to
14.0”WCforPropane.





Pressureport
Installation
20β”‚Page
β€’ Do not use this water heater if any part has been submersed under water.
Immediatelycallalicensedprofessionaltoinspectthewaterheatertoreplace
anydamagedparts.
β€’ Donot reversethehot outletandcold inletconnectionstothe waterheater.
Thiswillnotproperlyactivatethewaterheater.
WATERCONNECTIONS
Allpipes,pipefittings,valvesandothercomponents,includingsolderingmaterials,mustbesuitablefor
potablewatersystems.
1. Amanual shutoffvalvemust be installed on the coldwaterinlet to the water heater between
themainwatersupplylineandthewaterheater.
2. In addition, a manual
 shut off valve is also
recommended on the hot  water outlet of the
unit. If the water heater is installed within, or
subjected to, a closed loop water system, a
thermalexpansiontankmustbeinstalled.
3. Before installing the water heater, flush the
water line to remove all debris,
and after
installation is complete, purge the air from the
line.Failuretodosomaycausedamagetothe
heater.
4. Thereis a wiremeshfilterwithinthe coldinlet
to trap debris from entering your heater. This
willneedtobecleanedperiodicallytomaintain
optimumflow.
‐Pressurereliefvalve‐
Thewaterheaterhas  a high‐temperature shutoff switch built inas astandard safetyfeature(calleda
Hi‐Limitswitch)thereforeaξ€ƒβ€œpressureonly”reliefvalveisrequired.
β€’ Thisunitdoesnotcomewithanapprovedpressurereliefvalve.
β€’ Anapprovedpressurereliefvalvemustbeinstalled
onthehotwateroutlet.
β€’ ThepressurereliefvalvemustconformtoANSIZ21.22orCAN1‐4.4andinstallationmustfollow
localcode.
β€’ The discharg e capacity must be at least 140,000 BTU/h for the T‐KJr2‐IN/OS, 190,000 BTU/h for
theT‐K4‐IN/OS,and199,000BTU/h
fortheT‐D2‐IN/OS.
β€’ Thepressurereliefvalveneedstoberatedforamaximumof150psi.
β€’ The dischargepipingfor thepressurereliefvalve mustbedirected sothatthehot watercannot
splashonanyoneoronnearbyequipment.
β€’ Attach the discharge tube to
 the pressure relief  valve and run the end of the tube to within 6"
from the floor. This discharge tube must allow free and complete drainage without any
restrictions.
β€’ Ifthepressurereliefvalve  installedonthewaterheaterdischargesperiodically,thismaybedue
toadefectivethermal
expansiontankordefectivepressurereliefvalve.
β€’ Thepressurereliefvalvemustbemanuallyoperatedperiodicallytocheckforcorrectoperation.
β€’ Novalvemustbepla cedbetweenthereliefvalveandthewaterheater.
Pressure
ReliefValve
Hot
outle
t

Cold
inle
t

Gas
inle
t
AsCloseas
Possible
CAUTION
/