A.O. Smith ATI-310-P Technical Documents

Category
Water heaters & boilers
Type
Technical Documents
Do not store or use gasoline or other
flammablevaporsandliquidsinthevicinityof
thisoranyotherappliance.
WHATTODOIFYOUSMELLGAS
Donottrytolightanyappliance.
Do not touch any electric switch, do not
useanyphonein
yourbuilding.
Immediatelycallyourgassupplierfroma
neighbor's phone. Follow the gas
supplier'sinstructions.
Ifyoucannotreachyourgassupplier,call
thefiredepartment.
Installation and service must be performed
byaqualifiedinstaller,serviceagencyorthe
gassupplier.
FEATURING
ENDLESSHOTWATER
ONDEMANDUSAGE
COMPACT,SPACESAVING
ENERGYCONSERVATION
COMPUTERIZEDSAFETY
NOPILOTLIGHT
EASYLINKSYSTEM
510(TD2)modelsonly
GasTanklessWaterHeater
Suitableforpotablewater heating andspacehea ting
*
*Pleaserefertolocalcodesforspaceheatingcompliance.
Ifyouhaveanyquestions,please
callorwriteto:
500TennesseeWaltzParkway
AshlandCity,TN37015
TollFree:1 8777372840
OnDemandWaterHeater
InstallationManualandOwner’sGuide
Models
110Indoor(TKJr2IN)
110Outdoor(TKJr2OS)
310Indoor(TK4IN)
310Outdoor(TK4OS)
510Indoor(TD2IN)
510Outdoor(TD2OS)
WARNING
Iftheinformationinthese
instructionsisnotfollowed
exactly,afireorexplosion
mayresultcausing
propertydamage,personalinjuryordeath.
ANSI Z21.10.3 andCSA4.3
510(TD2)models
only
Contents
2Page
CONTENTS

SPECIFICATIONS…………………………………………………………………………………………..………………………...
INTRODUCTION…………………………………………………………………………………………………..………………….
SAFETYGUIDELINES…………….………………………………………………………………………………………..………..
INSTALLATION………………………………………………………………………………………………..…………………..….
General………………………………………………………………………………………………………………………..…..…
WarningforInstallations……………………………………………………………………………………………………
Clearances……………………………………………………………………………………………………………………………
IncludedAccessories…………….………………………………………………………………………………………..…..
OptionalItems……………………………………………………………………………………………………………………..
HighAltitudeInstallations……………………………………………………………………………………………………
.
VentingInstructions…………………………………………………………………………………………………………….
.
GasSupplyandGasPipeSizing………......................................................................................…
WaterConnections……………..…………………………………………………………………………………………….…
ElectricalConnections……………………………………………………………………..…………………………….......
RemoteControllerConnections……..………………………………………………………………………………….
PumpControlConnections…………………………………………..………..………..…………………………………
EasyLinkSystem...…………………………....…………………………………………………………………………..…...
APPLICATIONS...………………………………………………………………………………………………………………………
INITIALOPERATION..………………………………………………………………………………………………………….……
OPERATINGSAFETY…………………………………………………………………………………………………………………
NORMALOPERATION…………………………………………………………………………………………………………..…
General………..……….………….…………………………………………………………………………………………………
TemperatureSettings.…….……..……………………………………………………………………………………………
Flow…………………………………………………………………………………………………………………………………….
FreezeProtectionSystem…….…………………………………………………………………………………………..…
MaintenanceandService………………………………………………………………………………………………….…
UnitDrainingandFilterCleaning…………………………………………………………………………………………
TROUBLESHOOTING……..……………………………………………………………………………………………………..…
General………..……….………….…………………………………………………………………………………………………
ErrorCodes.…………………….…..………………………………………………………………………………………………
COMPONENTSDIAGRAM……………………………………………………………………………………………………..…
PARTSLIST………………….………………………………………………………………………………………………..…………
OUTPUTTEMPERATURECHART…………………………………………………………………………………………...…
LIMITEDWARRANTY…………………………………………………………....…………………………………………….….
3
4
5
6
6
8
9
9
9
11
12
17
20
21
22
23
24
28
30
31
33
33
33
35
35
36
36
37
37
39
42
46
49
51
InstallationManual
Owner’sGuide
Specifications
3Page
SPECIFICATIONS
Model
110
Indoor
(TKJr2IN)
110
Outdoor
(TKJr2OS)
310
Indoor
(TK4IN)
310
Outdoor
(TK4OS)
510
Indoor
(TD2IN)
510
Outdoor
(TD2OS)
NaturalGasInput
(OperatingRange)
Min:19,500Btu/h
Max:140,000Btu/h
Min:11,000Btu/h
Max:190,000Btu/h
Min:11,000Btu/h
Max:199,000Btu/h
PropaneInput
(OperatingRange)
Min:19,500Btu/h
Max:140,000Btu/h
Min:11,000Btu/h
Max:190,000Btu/h
Min:11,000Btu/h
Max:199,000Btu/h
GasConnection ¾”NPT
WaterConnections
¾”NPT
WaterPressure 15‐150psi*
NaturalGas
InletPressure
Min.5.0”WC
Max.10.5”WC
Propane
InletPressure
Min.8.0”WC
Max.14.0”WC
Manifold
Pressure**
Natural 2.0”WC 2.5”WC 2.0”WC 2.5”WC 2.0”WC 2.5”WC
Propane 2.5”WC 3.1”WC 3.7”WC 4.0”WC 3.7”WC 4.5”WC
Weight 33lbs. 38lbs. 39lbs.
Dimensions
H20.5”xW13. 8”xD6.7”
H20.5”xW13.8”xD8.5”
Ignition ElectricIgnition
Electric
Supply 120VAC/60Hz
Consumption
Operation
73.1W/0.61A 87.6W/0.73A 89.8W/0.75A
Standby 6.2W/0.05A 6.2W/0.05A 6.2W/0.05A
Freeze
Protection
111W/0.93A 111W/0.93A 111W/0.93A
*40psioraboveisrecommendedformaximumflow.
**TheManifoldPressureisthefactorysettingandgenerallyshouldnotneedadjustment.
NOTE:
Checktheratingplatetoensurethisproductmatchesyourspecifications.
InaccordancewithANSIZ21.10.3,COemissiondoesnotexceed400PPMfor
normalinput.
Themanufacturerreservestherighttodiscontinue,orchangeatanytime,
specificationsordesignswithoutnoticeandwithoutincurringobligations
.
I
I
I
n
n
n
s
s
s
a
a
a
l
l
l
l
l
l
a
a
a
i
i
i
o
o
o
n
n
n
M
M
M
a
a
a
n
n
n
u
u
u
a
a
a
l
l
l
Introduction
4Page
INTRODUCTION
*Thisdiagram
illustratestankless
waterheaterdesign
conceptsonlyand
doesnotaccurately
representtothewater
heater’sphysical
description.
This manual provides information necessary for the installation, operation, and
maintenanceofthewaterheater.
Themodeldescriptionislistedontheratingplatewhichisattachedtothefrontpanel
ofthewaterheater.
Pleasereadallinstallationinstructionscompletelybeforeinstallingthisproduct.
If you have any problems or questions regarding this equipment, consult with the
manufactureroritslocalrepresentative.
Thisequipmentisanondemand,tanklesswaterheaterdesignedtoefficientlysupply
endlesshotwaterforyourneeds.
Theprinciplebehindtanklesswaterheatersissimple:
1. Ahotwatertapisturnedon.
2. Waterenterstheheater.
3. Thewaterflowsensordetectsthewaterflow.
4. Thecomputerinitiatesthefanmoto randsendsasignaltotheignitertocreateanignition
spark.
5. Thegasignitesandflamesappear
withintheburnerchamber.
6. Watercirculatesthroughtheheatexchangerandthengetshot.
7. Usingthermistorstomeasuretemperaturesthroughoutthewaterheater,thecomputer
modulatesthegasandwatervalvestoensureproperoutputwatertemperature.
8. Whenthetapisturnedoff,theunitshutsdown.
The 110 Indoor(TKJr2IN), 310 Indoor(TK4IN)and 510 Indoor(TD2IN) models are
tobeonlyinstalledindoor(directventconvertible).The110Outdoor(TKJr2OS),310
Outdoor(TK4OS)and510Outdoor(TD2OS)modelsaretobeonlyinstalledoutdoor.
SafetyGuidelines
5Page
Watertemperaturesover125°F (52
°
C) cancausesevereburnsinstantlyordeath
from scalding. The watertemperature isset at 122°F (50°C)fromthe factory to
minimizeanyscaldingrisk.Beforebathingorshoweringalwayscheckthewater
temperature.
Donotstoreorusegasolineorotherflammables,vapors,orliquidsinthevicinity
ofthisappliance.
Do not reverse the water and/or gas connections as this will damage the gas
valvesand can cause severe injury ordeath.Followthediagramon p.20when
installingyourwaterheater.
Donotusethisapplianceifanyparthasbeenincontactwithorbeenimmersed
in water. Immediately call a licensed plumber, a licensed gas fitter, or a
professionalservicetechniciantoinspectand/orservicetheunitifnecessary.
Do not disconnect the electrical supply if the ambient temperature will drop
belowfreezing.TheFreezePreventionSystemonlyworksiftheunithaselectrical
power.Thewarrantywillnotbecoverediftheheatexchangerisdamageddueto
freezing.RefertothesectionontheFreezePreventionSystemon
p.35formore
information.
SAFETYGUIDELINES
SAFETYDEFINITIONS
Indicatesanimminentlyhazardoussituationwhich,ifnotavoided,willresultin
deathorseriousinjury.
Indicatesanimminentlyhazardoussituationwhich,ifnotavoided,couldresult
indeathorseriousinjury.
Indicatesanimminentlyhazardoussituationwhich,ifnotavoided,couldresult
inminorormoderateinjury.
GENERAL
1. Follow all local codes, or in the absence of local codes, follow the most recent edition of the
NationalFuelGasCode:ANSIZ223.1/N FPA54intheUSAorCAN/CSAB149.1NaturalGas,Propane
InstallationCodeinCanada.
2. Properlygroundtheunitinaccordancewithalllocalcodesor
intheabsenceoflocalcodes,with
theNationalElectrical Codes:ANSI/NFPA 70in the USA orCSAstandard C22.1 Canada Electrical
CodePart1inCanada.
3. Carefullyplanwhereyouintendtoinstallthewaterhe ater.Pleaseensure:
Yourwaterheaterwillhaveenoughcombustibleairand
properventilation.
Locateyourheaterwherewaterleakagewillnotdamagesurround ingareas(pleaserefer
top.7).
4. ChecktheratingplateforthecorrectGASTYPE,GASPRESSURE,WATERPRESSUREandELECTRIC
RATING.
*Ifthisunitdoesnotmatchyourrequirements,donotinstallandcon sultwiththe
manufacturer.
5. Ifany problemshould occur, turnoffall hot water tapsand turnoffthe gas.Then call a trained
technicianortheGasCompanyorthemanufacturer.
WARNING
CAUTION
DANGER
WARNING
Installation
6Page
INSTALLATION
GENERAL
1. Follow all local codes, or in the absence of local codes, follow the most recent edition of the
National Fuel Gas Code: ANSI Z223.1/NFPA 54 in the USA or CAN/C SA B149.1 Natural Gas,
PropaneInstallationCodeinCanada.
2. Allgaswaterheatersrequirecarefulandcorrectinstallationto
ensuresafeandefficient
operation.Thismanualmustbefollowedexactly.Readthe“SafetyGuidelines”se ction.
3. Themanifoldgaspre s sureispresetatthefactory.Itiscomputercontrolledandshouldnot
needadjustment.
4. Maintainproperspaceforservicing.Installtheunitsothatitcanbe
connectedorremo ved
easily.RefertotheClearancesSectiononp.9forproperclearances.
5. Thewaterheatermustbeinstalledinalocationwheretheproperamountofcombustibleair
willbeavailabletoitatalltimeswithoutobstructions.
6. Theelectricalconnectionrequiresameansofdisconnection,toterminatepowertothewater
heaterforservicingandsafetypurposes.
7. Donotinstalltheunitwheretheexhaustventispointingintoanyopeninginabuildingorwhere
thenoisemaydisturbyourneighbors.Makesuretheventterminationmeetstherequired
distancebylocalcodefromanydoorwayoropeningtopreventexhaustfromenteringabuilding
(refer
top.15).
8. Particlesfromflour,aerosols,andothercontaminantsmayclogtheairventorreducethe
functionsoftherotatingfanandcauseimproperburningofthegas.Regularlyensurethatthe
areaaroundtheunitisdust‐ordebrisfree;regularmaintenanceisrecommendedforthese
typesofenvironment.
9. Ifyouwillbein stallingthewaterheaterinacontaminatedareawithahighlevelofdust,sand,
flour,aerosolsorothercontaminants/chemicals,theycanbecomeairborneandenterandbuild
upwithinthefanandburnercausingdamagetothewaterheater.
10. Forthe110Indoor(TKJr2IN),310Indoor(TK4IN)and510Indoor(TD2IN)models:
Theseunitsmaybeconvertedtoadire ctvent(sealedcombustion)appliancebyinstallinga
directvent conversion kit Part No. 9007667005 (TKTV10) which will bring in all required
combustible air fromoutside thebuilding.When installingthe directvent conversion kit,
pleasefollowallinstructionsincludedwiththekit.
Ifthewaterheaterisusedasadirectventappliance,theunitrequiresa3”combustibleair
supply pipe. Theintakepipe mustbesealed airtight.Air
supply pipecan be made of ABS,
PVC, galvanized steel, corrugated aluminum, corrugated stainless steel or Category III
stainlesssteel.
Terminatingtheventingthroughasidewallisrecommendedforthedirectventsystem.
Runningtheexhaustventandtheintakepipeparallelisrecommended.
Terminating the exhaust and
intake on the same wall / surface is recommended.
Terminating in the same pressure zone allows for pressure balancing, which prevents
nuisanceshutdowns.
11. Forthe110Outdoor(TKJr2OS),310Outdoor(TK4OS)and510Outdoor(TD2OS)models:
Tobeinstalledoutdoorsandonlyinareaswithmild,temperateclimates.
Installation
7Page
Installation and service must be performed by a qualified installer (for
example, a licensed plumber or gas fitter), otherwise the warranty will be
void.
The installer(licensedprofessional)isresponsibleforthecorrectinstallation
of the water heater and for compliance with all national, state/provincial,
andlocalcodes.
The manufacturerdoesnotrecommendinstallingthewaterheaterin apitor
locationwheregasandwatercanaccumulate.
Donothavetheventterminalpointingtowardanyoperatingwindow,door,or
openingintoabuilding.
Do not install next to any source ofairborne debris, such as a clothes dryer,
that can cause debris to be trapped inside the combustion chamber, unless
thesystemisdirectvented.
The manufacturer does not recommend installing the water heater in an
atticduetosafetyissues.Ifyouinstallthewaterheaterinanattic:
Makesuretheunitwillhaveenoughcombustionairandproperventilation.
Keep the area around the water heater clean. When dust collects on the
flamesensor,thewaterheaterwillshutdownonanerrorcode.
If the above conditions cannot be met, use the direct vent conversion kit
PartNo.9007667005(TKTV10).
Placetheunitforeasyaccessforserviceandmaintenance.
A drain pan, or other means of protection against water damage, is
re
q
uiredtobeinstalledunderthewaterheaterincaseofleaks.
The warrantywillnotcoverdamagecausedbywaterquality.
Onlypotablewaterorpotablewater/glycolmixturescanbeusedwiththis
water heater.Do not introduce pool or spa water, or any chemically
treatedwaterintothewaterheater.
Water hardness levels must not exceed 7 grains per gallon (120 ppm) for
single family domestic applications or more than 4 grains per gallon (70
ppm) for all other types of applications.Water hard ness leads to scale
formation and may affect/damage the water heater.Hard water scaling
mustbeavoidedor
controlledbyproperwatertreatment.
WaterpHlevelsmustbebetween6.5and8.5
Wellwatermustbetreated.
Donotinstalltheunitwherewater,debris,orflammablevaporsmaygetinto
theflueterminal.
The manufacturer recommends using the direct vent kit when the water
heateris installed in abeauty salon. Some chemicalsusedin a beautysalon
mayaffecttheflamesensor.Waterheatermaynotworkproperly.
Although the water heater is designed to operate with minimal sound, the
manufacturerdoesnotrecommendinstallingtheunitonawalladjacenttoa
bedroom,oraroomthatisintendedforquietstudyormeditation,etc.
Locateyourheaterclosetoadrainwherewaterleakagewillnotdodamageto
surrounding areas.As with any water heating appliance, the potential for
leakageatsometimein thelifeoftheproductdoesexist.Themanufacturer
willnotberesponsibleforanywaterdamagethatmayoccur.
Ifyou installa
drain pan under the unit, ensure that it will not restrict the combustion air
flow.
CAUTION
WARNING
Installation
8Page
WARNINGFORINSTALLATIONS
FORYOURSAFETY,READBEFOREINSTALLATION:
Do not install the heater where water, debris or
flammablevaporsmaygetintotheflueterminal.
This may cause damage to the heater and void
thewarranty.
Do not have the vent terminal pointing toward
any opening into a building. Do not locate your
heater in a pit or
location where gas and water
canaccumulate.
Donotinstallthiswaterheaterunderan
overhanglessthan3feetfromitstoporeaves.
Theareaunderanoverhangmustbeopento
threesides.(Outdoormodelsonly)
Do not install the water heater vent terminator
within1ft.intheUSAofanyairintake
orbuilding
opening, and within 3 ft. in Canada of any air
intake or building opening. (Outdoor models
only)(Refertop.15)
Donotinstallnexttoadryeroranysourceof
airbornedebristhatcanbetrappedinsidethe
combustionchamber,unlessthesystemisdirect
vented.
Prohibited
Prohibited
FORYOURSAFETY,READBEFOREINSTALLATION:
3ft.
Installation
9Page
CLEARANCES
Model Top Bottom Front Back Sides
110Indoor*(TKJr2IN)* 12” 12 24” 1” 2
110Outdoor(TKJr2OS) 36” 12” 24” 1” 2
Model Top Bottom Front Back Sides
310Indoor*(TK4IN)* 12” 12” 24” 1” 2
310Outdoor(TK4OS) 36” 12” 24” 1” 2
Model Top Bottom Front Back Sides
510Indoor*(TD2IN)* 12” 12” 24” 1” 2
510Outdoor(TD2OS) 36” 12” 24” 1” 2
*Standardindoorinstallationsanddirectventindoorinstallationshavethesameclearances.
INCLUDEDACCESSORIES
Checkthattheseitemsbelowareincludedwiththewaterheater.
1. InstallationManualand
Owner’sGuide
2.
TemperatureRemoteController
3.CommunicationCable
510(TD2)modelsonly
OPTIONALITEMS
Model
110Indoor
(TKJr2IN)
110Outdoor
(TKJr2OS)
310Indoor
(TK4IN)
310Outdoor
(TK4OS)
510Indoor
(TD2IN)
510Outdoor
(TD2OS)
9007666005
(TKRE02)
9007603005
(TMRE30)
9007678005
(TKBF01)
9007667005
(TKTV10)
9007670005
(TKPC01)
9007671005
(TKPCJr2)
9007674005
(TKRB02)
9007608005
(TKKPWL4)
9007609005
(TKKPWH4)
9007680005
(TKKPCT43)
Qty:1
Qty:1
Maintain all clearances around
thewaterheater.
Bottom
Side
Top
Side
Front
Back
Seethetablebelow.
Qty:1
or
Installation
10Page
1. Temperature Remote Controller: 9007666005
(TKRE02)
The Temperature Remote Controller
has two functions. It allows the
output temperature from the water
heater to be adjusted within the
range of 99 °F to 167 °F, and it also
works as a diagnostic tool that will
give a concise error code whenever
there is a problem with the unit.
The temperature
options are 99°F, 100°F, 102°F, 104°F, 106°F, 108°F,
109°F,111°F,113°F,115°F,117°F,122°F,131°F,140°F,
158°F,and167°F.See the trouble shooting sectionfor
informationonpossibleerrorcodes.
2. Temperature Remote Controller: 9007603005
(TMRE30)
The Temperature Remote Controller
has two functions. It allows the
output temperature from the water
heater to be adjusted within the
range of 99 °F to 185 °F, and it also
works as a diagnostic tool that will
giveaconciseerrorcodewheneverthereisaproblem
withtheunit.
Thetemperatureoptionsare99°F,100°F,
102°F,104°F,106°F,108°F,110°F,111°F,113°F,115°F,
117°F, 122°F, 131°F, 140°F, 149°F, 158°F, 167°F, 176°F
and 185°F. See the trouble shooting section for
informationonpossibleerrorcodes.
3.BackflowPreventer:9007678005(TKBF01)
The Backflow preventer prevents the
backflow of air through the exhaust
vent.Thishelpspreventharmfulexhaust
gasesfromenteringthehome,aswellas
helpingtopreventtheunitfromfreezing
inareaswherecoldaircanbeblown or
drawnintotheexhaustsystem.Installthisventdamper
in
accordancewiththeinstallationinstructionsandany
applicablecodes.
4.DirectVent ConversionKit:9007667005
(TKTV10)
Thiskitcanbeusedtoconvert
thewaterheaterfroma
standardventsystemtoa
directvent(orsealed
combustion)system.Install
thisconversionkitin
accordancewiththe
installationinstructionsand
anyapplicablecodes.
5.PipeCovers:9007670005(TKPC01)and
9007671005(TKPCJr2)
The pipe cover protects the plumbing
pipes to the water heater from
unexpected adjustments.This pipe
cover is fixed to the bottom of the
water heater, which hides the
plumbing and improves the visual
aspects of the whole installation for
thewaterheater.
6. Recessbox:9007674005(TKRB02)
TheRecessboxwillallowfor“clean”
installations.Thewaterheaterfitsinside
therecessbox,whichhidesandprotects
thewholewaterheaterandplumbing.
TheRecessboxwillfitinbetweenmost
wallstuds.
7.TVentWallThimblewithTermination:9007608005(TKKPWL4)and9007609005(TKKPWH4)
Theseterm in ation s are usedwhenventingoutthrough thewalland are
compatiblewith theTVentpipesystem.
Theseterm inationsarespecialstainlesssteelventsforgasappliancesandare
ULlistedasCategoryII,IIIand IV.Therear etwotyp es of termination s:the
Louverterminat ionandtheHo od
termination .Fo rdifferentwallthi cknesses,
thereare tworangesoflengthsavailable(refertotheventingbrochurefor
details).
Installtheseventt er min ationsinaccordancewithth ei r installation
instructionsand anyapplicablelocalcodes.
8.DirectVentConcentricTermination:9007680005(TKKPCT43 )
Usedwhenterminatingdirectvent(sealedcombustion)systems,withdirect
ventmodelsthatrequirea3”intakeanda4”exhaust.Thisconcentric
terminationprovidestheconvenienceofonlyhavingtomakeonepenetration
throughasidewallinsteadoftwoseparatepenetrationsfortheintakeand
exhaustpiping.Theterminationincludes
abirdscreen,restrictingsmallanimals,
pests,andforeignobjectsfromenteringintotheventsystem.Thissidewall
terminationisavailableinthreedifferentsizes,tocoverallrangesofwall
thicknesses.
DirectventConcentricTermination
Part# Coveringwallthickness
9007680005(TKKPCT431) 3.9”
7.1”
9007772005(TKKPCT432) 6.9”
10.1”
9007773005(TKKPCT433) 9.8”
13.0”
Louver
Termination
9007608005
(TKKPWL4)
Hood
Termination
9007609005
(TKKPWH4)
Installation
11Page
DONOTadjustanydipswitchesontherightbankforthe510(TD2)models.
Thedarksquaresindicatethedirectionthedipswitchesshouldbesetto.
Dipswitches
HIGHALTITUDEINSTALLATIONS
Checktheelevationwhereyourwaterheaterisinstalled.Setdipswitchesshowninthetablebelow
dependingonthealtitude.
Altitude
0to2,000ft
(DEFAULT)
2,000to4,000ft
4,000to6,000ft Over6,000ft
SwitchNo.3 OFF
ON
OFF
Consult
our Technical
Services
Department
at1877‐
7372840
SwitchNo.4 OFF
OFF
ON
Altitude
0to2,000ft
(DEFAULT)
2,000to4,000ft
4,000to6,000ft Over6,000ft
SwitchNo.4 OFF
ON
OFF
Consult
our Technical
Services
Department
at1877‐
7372840
SwitchNo.5 OFF
OFF
ON
110(TKJr2)and310(TK4)models
510(TD2)models(Leftbankofdipswitches)
110(TKJr2)and310(TK4)models
Computerboard
WARNING
510
(
TD2
)
modelsCom
p
uterboard
Leftbankofdipswitches
O
F
F
O
N
1
2
3
4
5
6
7
8
O
F
F
O
N
1
2
3
4
5
6
7
8
O
F
F
O
N
1
2
3
4
5
6
7
8
O
F
F
O
N
1
2
3
4
5
6
O
F
F
O
N
1
2
3
4
5
6
O
F
F
O
N
1
2
3
4
5
6
Installation
12Page
Improperventingofthisappliancecanresultinexcessivelevelsofcarbon
monoxidewhichcanresultinseverepersonalinjuryordeath.
Improperinstallationcancausenauseaorasphyxiation,severeinjuryordeathfrom
carbonmonoxideandfluegasespoisoning.Improperinstallationwillvoidproduct
warranty.
Wheninstallingtheventsystem,allapplicablenationalandlocalcodesmustbe
followed.Ifyouinstallthimbles,firestopsorotherprotectivedevicesandthey
penetrateanycombustibleornoncombustibleconstruction,besuretofollowall
applicablenationalandlocalcodes.
VENTINGINSTRUCTIONS
General
Thewaterheatermustbeventedinaccordance withthesection“VentingofEquipment"ofthelatest
editionoftheNationalFuelGasCod e : ANSIZ223.1/NFPA54intheUnitedStatesand/orSection7ofthe
CAN/CSA B149.1 Natural Gas and Propane Installation Code in
Canada, as well as applicable local
buildingcodes.
The manufacturer recommends the “TVent” line manufactured by TAKAGI (Refer to “TVent”
brochure for det ails). However, the following are also UL listed manufacturers: ProTech Syste ms Inc.
(FasNSeal),FlexLInc.,ZFlexInc.(ZVentIII),MetalFabInc.,andHeatFabInc.(SafTVent) .
Generalrulesforventingwaterheatersare:
Placethewaterheaterascloseaspossibletotheventterminator.
Theventcollarofthewaterheatermustbefasteneddirectlytoanunobstructedventpipe.
Donotweldtheventpipetothewaterheater’sventcollar.
Donotcuttheventcollaroftheunit.
Theventmustbeeasilyremovablefromthetopofthewaterheaterfornormalserviceand
inspectionoftheunit.
Thewaterheaterventmustnotbeconnectedtoanyothergasapplianceorventstack.
Avoid
usinganoversizedventpipeorusingextremelylongrunsofthepipe.
Forrooftopventing,araincaporotherformofterminationthatpreventsrainwaterfrom
enteringintothewaterheatermustbeinstalled.
Donotcommonventorconnectanyventfromotherappliances
tothewaterheatervent.
Generalrulesforventterminations:
Avoidlocatingthewaterheaterventterminatornearanyairintakedevices.Thesefanscan
pickupthe exhaust flueproducts fromthewater heater andreturnthem to the building.
Thiscancreateahealthhazard.
Locate the vent terminator so that
it cannot be blocked by any debris, at any time. Most
codesrequirethattheterminatorbeatleast12inchesabove grade,buttheinstallermay
determineifitshouldbehigherdependingonthejobsiteconditionandapplicablecodes.
Apropersidewall terminatoris recommendedwhen
thewaterheaterisventedthrougha
sidewall.
Regardingtheclearancesfrom the exhaustterminator tothe airinlet or opening, referto
thenextfewpages.
CAUTION
DANGER
Installation
13Page
Exhaustventing‐
Forthe110Indoor(TKJr2IN),310Indoor(TK4IN)and510Indoor
(TD2IN)models
ThisisaCategoryIIIapplianceandmustbeventedaccordingly.Theventsystemmustbesealedairtight.
AllseamsandjointswithoutgasketsmustbesealedwithhighheatresistantsiliconesealantorULlisted
aluminumadhesivetapehavingaminimumtemperatureratingof350°F.Forbestresults,a
vent system
shouldbeasshortandstraightaspossible.
ThiswaterheaterisaCategoryIIIapplianceandmustbeventedaccordinglywithany4”vent
approvedforusewithCategoryIIIorSpecialBHtypegasvent .
Followtheventpipemanufacturer’sinstructionswheninstallingthe
ventpipe.
Donotcommonventthisappliancewithanyotherventedappliance(Donotterminatevent
into a chimney.If the vent must go through the chimney, the vent must run all the way
throughthechimneywithCategoryIIIapprovedorSpecialBHventpipe).
When
the horizontal vent run exceeds 5 ft., support the vent run at 3 ft. intervals with
overheadhangars.
The maximumlengthofexhaust ventpipingmustnotexceed50ft.(deducting5ft.foreach
elbowusedintheventingsystem).Donotusemorethan5elbows.
Diameter Max.No.ofElbow Max.VerticalandHorizontal(Total)VentLength
4” 5 50ft.
*Foreachelbowadded,deduct5ft.frommax.Ventlength.
No.ofElbows Max.VerticalorHorizontalLength
0 50ft.
1 45ft.
2 40ft.
5 25ft.
VentingIllustrations‐
Forthe110Indoor(TKJr2IN),310Indoor(TK4IN)and510Indoor
(TD2IN)models
HorizontalInstallationDiagram
VerticalInstallationDiagram
SidewallVent
Terminator
Wall
BackflowPreventer*
VerticalCondensationDrain**
Fordetailsoftheoptionalitems,refertothe InstallationmanualforeachOptionalitem.
Roo
f
VerticalCondensation
Drain**
RoofFlashing
RainCap
BackflowPreventer*
Installation
14Page
*BackflowPreventer (Recommendedforfreezingweatherconditions:36
°
F andbelow)
**VerticalCondensationDrainmustbeinstalledaccordancewithlocalcodes.
HorizontalInstallationDiagram
WithDirectVentConcentric
Termination
HorizontalInstallationDiagram
(Withdirectventing)
VerticalInstallationDiagram
(Withdirectventing)
Thewaterheater
Intakeportof
DirectVent
ConversionKit
InstallationDiagramofDirectVent
ConversionKitwithwaterheater
Wall
Directvent
Concentric
Termination
PlateofDirectVentConversionKit
Seethepicturebelowfordetailedconnection
instructionstotheDirectVentConversionKit.
VerticalCondensationDrain**
Backflow
Preventer*
Wall
Sidewall
Vent
Terminator
RoofFlashing
Vertical
Condensation
Drain**
Backflow
Preventer*
RainCap
Roo
f
Firestop
Installation
15Page
Ventterminationclearances‐

Canada U.S.A
Directventand
otherthanDirect
Vent
Directvent OtherthanDirectVent
A
Clearanceabovegrade,veranda,porch,deck,
orbalcony.
1foot 1foot 1foot
B
Clearancetowindowordoorthatmaybe
opened.
3feet 1foot
4feetfrombeloworside
opening.1footfrom
aboveopening.
C Clearancetopermanentlyclosedwindow * * *
D
Verticalclearancetoventilatedsoffitlocated
abovetheventterminatorwithinahorizontal
distanceof2feet(61cm)fromthecenterline
oftheterminator.
* * *
E Clearancetounventilatedsoffit * * *
F Clearancetooutsidecorner * * *
G Clearancetoinsidecorner * * *
H
Clearancetoeachsideofcenterlineextended
abovemeter/regulatorassembly
3feet * *
I Clearancetoserviceregulatorventoutlet. 3feet * *
J
Clearancetononmechanicalairsupplyinlet
tobuildingorthecombustionairinlettoany
otherapplication.
3feet 1foot
4feetfrombeloworside
opening.1footfrom
aboveopening.
K Clearancetomechanicalairsupplyinlet. 6feet 3feet 3feet
L
Clearanceabovepavedsidewalkorpaved
drivewaylocatedonpublicproperty.
7feet * 7feet
M
Clearanceunderveranda,porchdeck,or
balcony.
1foot * *
*ForclearancesnotspecifiedinANSIZ223.1/NFPA54orCAN/CSAB149.1,pleaseuseclearancesinaccordancewith
localinstallationcodesandtherequirementsofthegassupplier.
Installation
16Page
Pleasefollowalllocalandnationalcodesinregardstoproperterminationclearances.
Intheabsenceofsuchcodes,thefollowingclearancescanbeusedasguidelines.Local
codessupersedetheseguidelines.
Forsidewallterminations
Exhausttermination
1ft.
1ft.
2ft.
Inside
corner
Formultiplesidewallexhaust
terminations(e.g.multiunit
systems),anexhausttermination
mustbeatleast1ft.awayfrom
anotherexhausttermination.An
exhaustterminationmustalsobe
atleast2ft.awayfromaninside
corner(iftheadjacentwallisless
than2ft.oflength,theminimum
requireddistanceawayfromthe
insidecornerwillbeequaltothe
lengthofthatadjacentwall).
Fordirectventsidewall
terminationsthatusetwo
separatepenetrationsforthe
intakeandexhaust,distance
theintakeandexhaust
terminationsatleast3ft.away
fromeachother,nomatterthe
orientation.
Formultipleunit,directventsidewall
terminationsthatcombinetheintake
andexhaustintoasinglepenetration,
spaceeachdirectventterminationat
least1ft.awayfromeachother,no
mattertheorientation.Adirectvent
terminationmustalsobeatleast2ft.
awayfromaninsidecorner(if
the
adjacentwallislessthan2ft.of
length,theminimumrequired
distanceawayfromtheinsidecorner
willbeequaltothelengthofthat
adjacentwall).
Formultipleunitrooftopterminations(whetherforstandardindooror
directventinstallations)spaceallexhaustandintaketerminationsin
accordance
withlocalcodes.Anexhaustterminationmustbespacedfrom
awallorsurfaceinaccordance withlocalcodes aswell.Intheabsenceof
suchacode,anexhaustterminationmustbeahorizontaldistanceofat
least2ft.awayfromawallorsurface.
A:Inaccordancewith
localcodes
Forrooftopterminations
Airintake
Exhausttermination
A
A
A
A
A
2ft.
Airintake
Exhaust
termination
Exhaustand/ordirectvent
sidewallterminationsshould
beatleast2ft.awayfroman
oppositesurface/wall.Do
notplacethetermination
directlyinfrontofan
openingintoabuilding.
2ft.
Exhaust
termination
Airsupplyinlet
3ft.
3ft.
3ft.
Directventtermination
1ft.
1ft.
Inside
corner
2ft.
CAUTION
Installation
17Page
Sizethegaspipeappropriatelytosupplythenecessaryvolumeofgasrequiredfor
thewaterheaterusingANSI233.1/NFPA54intheUSAorCAN/CSAB149.1inCanada
orlocalcodes.Otherwise,flowcapabilitiesandoutputtemperatureswillbelimited.
Checkthatthetypeofgasmatchestheratingplatefirst.
Ensure that any and all gas regulators used are operating properly and
providing gas pressures within the specified range shown be low. Excess gas
inletpressuremaycauseseriousaccidents.
Conversion of thisunit from naturalgas to propane orvise versa will void all
warranty. Contact your local distributor to get the correct unit for your gas
type.The manufacturer is not liable for any property and/or personal
damageresultingfromgasconversions.
GASSUPPLYANDGASPIPESIZING
General‐
Theminimumandmaximuminletgaspressuresare:
Gastype Inletgaspressure
NaturalGas Min.5.0”WCMax.10.5”WC
Propane Min.8.0”WCMax.14.0”WC
Gas pressure above this specified range for the water heater and/or insufficient gas volume will
adversely affect performance.These pressures are measured when the water heater is in full
operation.
Inlet gas pressuremust not exceedthe above maximumvalues; gas pressureabove the specified
rangewillcausedangerous
operatingconditionsanddamagetotheunit.
Until testing of the main gas line supply pressure is completed, ensure the gas line to the water
heaterisdisconnectedtoavoidanydamagetothewaterheater.
Gasconnections‐
1. Installamanualgasshutoffvalvebetweenthewaterheaterandthegassupplyline.
2. When the gas connections are completed, it is necessary to perform a gas leak test (see below)
eitherbyapplyingsoapywatertoallgasfittingsandobserving for bubblesorbyusing
agasleak
detectiondevice.
Thewaterheater anditsindividualshutoff valve mustbedisconnectedfromthegassupply
pipingsystemduringanypressuretestingofthatsystemattestpressuresinexcessof1/2psi
(3.5kPa).
Thewaterheatermustbeisolatedfromthegassupplypipingsystembyclosingitsindividual
manual shutoff valve during any pressure testing of the gas supply piping system at test
pressuresequaltoorlessthan1/2psi(3.5kPa).
3. Alwayspurgethegaslineofanydebrisand/orwater
beforeconnectingtothegasinlet.
WARNING
NOTICE
Installation
18Page
NaturalGasSupplyPiping‐
MaximumDeliveryCapacityofCubicFeetofGasperHourofIPSPipeCarryingNaturalGasof0.60SpecificGravity
BasedonPressureDropof0.5WC
BasedonEnergyContentof1,000BTU/CubicFt.:Thewaterheaterrequires140CubicFt./hrforthe110(TKJr2)
models,190CubicFt./hrforthe310(TK4)models,and199CubicFt./hrforthe510(TD2)models.
Unit:CubicFeetperHour
PipeSize Length
Diameter 10’ 20’ 30’ 40’ 50’ 60’ 70’ 80’ 90’ 100’ 125’150’ 200’
¾” 363 249 200 171 152 138 127 118 111 104 93 84 72
1” 684 470 377 323 286 259 239 222 208 197 174 158 135
1¼” 1,404 965 775 663 588 532 490 456 428 404 358 324 278
1½” 2,103 1,445 1,161 993 880 798 734 683 641 605 536 486 416
2” 4,050 2,784 2,235 1,913 1,696 1,536 1,413 1,315 1,234 1,165 1,033 936 801
Propane(LP)SupplyPiping‐
MaximumCapacityofPropane(LP)Basedon11”WCsupplypressureata0.5”WCpressuredrop
Unit:kBTUperHour
PipeSize
Length
Diameter
10’ 20’ 30’ 40’ 50’ 60’ 70’ 80 90’ 100’ 125’ 150’ 200’
¾” 567 393 315 267 237 217 196 185 173 162 146 132 112
1” 1,071 732 590 504 448 409 378 346 322 307 275 252 213
1¼” 2,205 1,496 1,212 1,039 913 834 771 724 677 630 567 511 440
1½” 3,307 2,299 1,858 1,559 1,417 1,275 1,181 1,086 1,023 976 866 787 675
2” 6,221 4,331 3,465 2,992 2,646 2,394 2,205 2,047 1,921 1,811 1,606 1,496 1,260
Formoreinformation,pleaseseethebelow.
BasedonEnergyContentof1,000BTU/CubicFt:
Divideeachappliance’sBTUrequirementby1,000BTUtoget
theappliancesCubicFt.requirement.
Takeintoaccountthedistancetheapplianceisfromthegas
meter,lookintheabovegascharttoproperlysizetheline.
Forsectionsofthegasline
supplyinggastomorethanone
appliance(Ex:PointAtoPointB),addupthecubicft.
requirementsoftheappliancesthatarebeingsuppliedbythat
section,andsizetothefarthestappliance.
ForExample:ThesectionfromAtoBsuppliesgastothe
furnace,range,anddryer.
AddinguptheBTUrequirements
anddividingby1,000yieldsacubicft.requirementof220
cubicft.ofgas.Thefarthestapplianceistherange,whichis50
ft.awayfromthemeter.Lookingattheabovechart,and
underthecolumnof50ft.,SectionAtoBneeds
tobe1”in
ordertosupply220cubicft.
10’Length
1”PipeSize
C
GasSizingExample
(NaturalGas)
10’Length
3/4”PipeSize
15’Length
1/2”PipeSize
10’Length
1/2”PipeSize
Furnace
120,000BTU
Water
Heater
199,000BTU
5’Length
11/4”PipeSize
Range
65,000BTU
10’Length
3/4”PipeSize
Dryer
35,000BTU
15’Length
1”PipeSize
5’Length
11/4”PipeSize
GasMeter
B
A
Installation
19Page
1. Turnoffallelectricpowertothewaterheaterifserviceistobeperformed.
2. Turnthemanualgasvalvelocatedontheoutsideoftheunitclockwiseto
theoffposition.
Measuringinletgaspressure‐
Thewaterheatercannotperformproperlywithoutsufficientinletgaspressure.Belowareinstructions
onhowtochecktheinletgaspressure.THISISONLYTOBEDONEBYALICENSEDPROFESSIONAL.
1. Shutoffthemanualgasvalveonthesupplygasline.
2. Removethescrewforthe
pressureportlocatedon
thegasinletofthewaterheatershowninthe
diagramtotheright.
3. Connectthemanometertothepressureport.
4. Reopenthemanualgasvalve.Checktoseethat
therearenogasleaks.Opensomeofthefixtures
thatusethehighest
flowratetoturnonthewater
heater.
5. Checktheinletgaspressure.Whenthewaterheater
isonmaximumburn,themanometershouldread
from5.0”to10.5”WCforNaturalgas,from8.0”to
14.0”WCforPropane.
Pressureport
Installation
20Page
Do not use this water heater if any part has been submersed under water.
Immediatelycallalicensedprofessionaltoinspectthewaterhe atertoreplace
anydamagedparts.
Donotreverse thehotoutletandcold inletconnections tothewaterheater.
Thiswillnotproperlyactivatethewaterheater.
WATERCONNECTIONS
Allpipes,pipefittings,valvesandothercomponents,includingsolderingmaterials,mustbesuitablefor
potablewatersystems.
1. A manualshutoff valvemust be installedon the cold waterinlet to thewaterheaterbetween
themainwatersupplylineandthewaterheater.
2. In addition, a manual
shut off valve is also
recommended on the hot water outlet of the
unit. If the water heater is installed within, or
subjected to, a closed loop water system, a
thermalexpansiontankmustbeinstalled.
3. Before installing the water heater, flush the
water line to remove all debris,
and after
installation is complete, purge the air fromthe
line.Failuretodosomaycausedamagetothe
heater.
4. The re is awiremesh filterwithinthecold inlet
to trap debris from entering your heater. This
willneedtobecleanedperiodicallytomaintain
optimumflow.
Pressurereliefvalve‐
Thewaterheaterhasahightemperatureshutoffswitchbuiltinas a standard safety feature(calleda
HiLimitswitch)thereforea“pressureonly”reliefvalveisrequired.
Thisunitdoesnotcomewithanapprovedpressurereliefvalve.
Anapprovedpressurereliefvalvemustbeinstalled
onthehotwateroutlet.
ThepressurereliefvalvemustconformtoANSIZ21.22orCAN14.4andinstallationmustfollow
localcode.
The discharge capacity must be at least 140,000 BTU/h for the 110 (TKJr2) models, 190,000
BTU/hforthe310(TK4)models,and
199,000BTU/hforthe510(TD2)models.
Thepressurereliefvalveneedstoberatedforamaximumof150psi.
Thedischargepipingforthepressurereliefvalvemustbedirectedsothatthehotwatercannot
splashonanyoneoronnearbyequipment.
Attach the
discharge tube to the pressure relief valve and run the end of the tube to within 6"
from the floor. This discharge tube must allow free and complete drainage without any
restrictions.
Ifthepressurereliefvalveinstalledonthewaterheaterdischargesperiodically,thismaybedue
to
adefectivethermalexpansiontankordefectivepressurereliefvalve.
Thepressurereliefvalvemustbemanuallyoperatedperiodicallytocheckforcorrectoperation.
Novalvemustbeplacedbetweenthereliefvalveandthewaterheater.
Pressure
ReliefValve
Hot
outlet
Cold
inlet
Gas
inlet
AsCloseas
Possible
CAUTION
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52