Operating Instructions
Proline Prowirl F 200
PROFIBUS PA
Vortex flowmeter
BA01222D/06/EN/01.13
71225412
Valid as of version
01.00.zz
(Device firmware)
Proline Prowirl F 200 PROFIBUS PA
2 Endress+Hauser
Make sure the document is stored in a safe place such that it is always available when
working on or with the device.
To avoid danger to individuals or the facility, read the "Basic safety instructions" section
carefully, as well as all other safety instructions in the document that are specific to
working procedures.
The manufacturer reserves the right to modify technical data without prior notice. Your
Endress+Hauser Sales Center will supply you with current information and updates to
these Instructions.
Proline Prowirl F 200 PROFIBUS PA Table of contents
Endress+Hauser 3
Table of contents
1 Document information .............. 6
1.1
Document function ..................... 6
1.2 Symbols used .......................... 6
1.2.1 Safety symbols .................. 6
1.2.2 Electrical symbols ................ 6
1.2.3 Tool symbols .................... 7
1.2.4 Symbols for certain types of
information .................... 7
1.2.5 Symbols in graphics ............... 7
1.3 Documentation ........................ 8
1.3.1 Standard documentation ........... 8
1.3.2 Supplementary device-dependent
documentation .................. 8
1.4 Registered trademarks ................... 8
2 Basic safety instructions ............ 9
2.1 Requirements for the personnel ............ 9
2.2 Designated use ........................ 9
2.3 Workplace safety ...................... 10
2.4 Operational safety ..................... 10
2.5 Product safety ........................ 10
2.6 IT security ........................... 10
3 Product description ................ 11
3.1 Product design ........................ 11
4 Incoming acceptance and product
identification ..................... 12
4.1 Incoming acceptance ................... 12
4.2 Product identification ................... 13
4.2.1 Transmitter nameplate ........... 13
4.2.2 Sensor nameplate ............... 14
4.2.3 Symbols on measuring device ...... 16
5 Storage and transport ............. 17
5.1 Storage conditions ..................... 17
5.2 Transporting the product ................ 17
5.3 Packaging disposal ..................... 18
6 Mounting ......................... 19
6.1 Installation conditions .................. 19
6.1.1 Mounting position ............... 19
6.1.2 Requirements from environment and
process ....................... 21
6.1.3 Special mounting instructions ...... 24
6.2 Mounting the measuring device ........... 25
6.2.1 Required tools .................. 25
6.2.2 Preparing the measuring device ..... 25
6.2.3 Mounting the measuring device ..... 26
6.2.4 Mounting the sensor ............. 26
6.2.5 Mounting the transmitter of the
remote version ................. 26
6.2.6
Turning the transmitter housing .... 28
6.2.7 Turning the display module ........ 29
6.3 Post-installation check .................. 29
7 Electrical connection .............. 30
7.1 Connection conditions .................. 30
7.1.1 Required tools .................. 30
7.1.2 Requirements for connecting cable ... 30
7.1.3 Terminal assignment ............. 33
7.1.4 Pin assignment, device plug ........ 34
7.1.5 Shielding and grounding .......... 34
7.1.6 Requirements for the supply unit .... 36
7.1.7 Preparing the measuring device ..... 36
7.2 Connecting the measuring device .......... 36
7.2.1 Connecting the transmitter ........ 36
7.2.2 Connecting the remote version ..... 38
7.3 Special connection instructions ............ 42
7.3.1 Connection examples ............. 42
7.4 Hardware settings ..................... 43
7.4.1 Setting the device address ......... 43
7.5 Ensuring the degree of protection .......... 44
7.6 Post-connection check .................. 44
8 Operability ........................ 45
8.1 Overview of operation options ............ 45
8.2 Structure and function of the operating
menu .............................. 46
8.2.1 Structure of the operating menu .... 46
8.2.2 Operating philosophy ............ 47
8.3 Access to the operating menu via the local
display ............................. 48
8.3.1 Operational display .............. 48
8.3.2 Navigation view ................ 50
8.3.3 Editing view ................... 52
8.3.4 Operating elements .............. 53
8.3.5 Opening the context menu ......... 54
8.3.6 Navigating and selecting from list ... 56
8.3.7 Calling the parameter directly ...... 56
8.3.8 Calling up help text .............. 57
8.3.9 Changing the parameters ......... 58
8.3.10 User roles and related access
authorization .................. 59
8.3.11 Disabling write protection via access
code ......................... 59
8.3.12 Enabling and disabling the keypad
lock ......................... 59
8.4 Access to the operating menu via the
operating tool ........................ 60
8.4.1 Connecting the operating tool ...... 61
8.4.2 FieldCare ..................... 62
8.4.3 SIMATIC PDM .................. 63
Table of contents Proline Prowirl F 200 PROFIBUS PA
4 Endress+Hauser
9 System integration ................ 64
9.1
Overview of device description files ......... 64
9.1.1 Current version data for the device ... 64
9.1.2 Operating tools ................. 64
9.2 Device master file (GSD) ................. 64
9.2.1 Manufacturer-specific GSD ........ 64
9.2.2 Profile GSD .................... 65
9.2.3 Compatibility with other Endress
+Hauser measuring devices ........ 65
10 Commissioning .................... 67
10.1 Function check ....................... 67
10.2 Switching on the measuring device ......... 67
10.3 Configuring the device address via software .. 67
10.3.1 PROFIBUS network .............. 67
10.4 Setting the operating language ............ 67
10.5 Configuring the measuring device .......... 69
10.5.1 Overview of the wizards in the
"Setup" menu ................... 69
10.5.2 Defining the tag name ............ 69
10.5.3 Setting the system units .......... 70
10.5.4 Selecting and setting the medium ... 73
10.5.5 Configuring the analog inputs ...... 75
10.5.6 Configuring the local display ....... 75
10.5.7 Configuring the communication
interface ...................... 77
10.5.8 Configuring the low flow cut off ..... 78
10.6 Advanced settings ..................... 79
10.6.1 Setting the medium properties ...... 80
10.6.2 Performing external compensation .. 85
10.6.3 Carrying out a sensor adjustment .... 85
10.6.4 Configuring the pulse/frequency/
switch output .................. 86
10.6.5 Configuring the totalizer .......... 94
10.6.6 Carrying out additional display
configurations .................. 96
10.7 Configuration management .............. 98
10.7.1 Function scope of the "Configuration
management" parameter .......... 99
10.8 Simulation ........................... 99
10.9 Protecting settings from unauthorized
access ............................. 101
10.9.1 Write protection via access code ... 101
10.9.2 Write protection via write protection
switch ....................... 102
11 Operation ....................... 104
11.1 Reading device locking status ............ 104
11.2 Adjusting the operating language ......... 104
11.3 Configuring the display ................ 104
11.4 Reading measured values ............... 104
11.4.1 Process variables ............... 104
11.4.2 Totalizer ..................... 105
11.4.3 Output values ................. 106
11.5 Adapting the measuring device to the process
conditions .......................... 107
11.6 Performing a totalizer reset ............. 107
11.6.1
Function scope of "Control Totalizer "
parameter .................... 108
11.7 Showing data logging ................. 108
12 Diagnostics and troubleshooting .. 110
12.1 General troubleshooting ................ 110
12.2 Diagnostic information on local display ..... 112
12.2.1 Diagnostic message ............. 112
12.2.2 Calling up remedial measures ..... 114
12.3 Diagnostic information in FieldCare ....... 114
12.3.1 Diagnostic options .............. 114
12.3.2 Calling up remedy information .... 115
12.4 Adapting the diagnostic information ...... 116
12.4.1 Adapting the measured value and
device status .................. 116
12.4.2 Adapting the diagnostic behavior ... 117
12.5 Overview of diagnostic information ....... 120
12.5.1 Diagnostics for the sensor ........ 120
12.5.2 Diagnostics for the electronics ..... 122
12.5.3 Diagnostics for the configuration ... 128
12.5.4 Diagnostics for the process ....... 133
12.6 Pending diagnostic events .............. 138
12.7 Diagnostic list ....................... 139
12.8 Event logbook ....................... 140
12.8.1 Event history .................. 140
12.8.2 Filtering the event logbook ....... 140
12.8.3 Overview of information events .... 140
12.9 Resetting the measuring device .......... 141
12.10 Device information ................... 142
12.11 Firmware history ..................... 143
13 Maintenance .................... 144
13.1 Maintenance tasks .................... 144
13.1.1 Exterior cleaning ............... 144
13.1.2 Interior cleaning ............... 144
13.1.3 Replacing seals ................ 144
13.2 Measuring and test equipment ........... 144
13.3 Endress+Hauser services ............... 144
14 Repair ........................... 145
14.1 General notes ....................... 145
14.2 Spare parts ......................... 145
14.3 Endress+Hauser services ............... 146
14.4 Return ............................. 146
14.5 Disposal ........................... 146
14.5.1 Removing the measuring device .... 146
14.5.2 Disposing of the measuring device .. 146
15 Accessories ...................... 147
15.1 Device-specific accessories .............. 147
15.1.1 For the transmitter ............. 147
15.1.2 For the sensor ................. 147
15.2 Communication-specific accessories ....... 147
15.3 Service-specific accessories .............. 148
15.4 System components ................... 148
Proline Prowirl F 200 PROFIBUS PA Table of contents
Endress+Hauser 5
16 Technical data ................... 149
16.1
Application ......................... 149
16.2 Function and system design ............. 149
16.3 Input .............................. 149
16.4 Output ............................ 151
16.5 Power supply ........................ 155
16.6 Performance characteristics ............. 157
16.7 Installation ......................... 159
16.8 Environment ........................ 159
16.9 Process ............................ 160
16.10 Mechanical construction ............... 161
16.11 Operability ......................... 168
16.12 Certificates and approvals .............. 169
16.13 Application packages .................. 170
16.14 Accessories ......................... 171
16.15 Documentation ...................... 171
17 Appendix ........................ 172
17.1 Overview of the operating menu .......... 172
17.1.1 Main menu ................... 172
17.1.2 "Operation" menu ............... 172
17.1.3 "Setup" menu .................. 172
17.1.4 "Diagnostics" menu .............. 180
17.1.5 "Expert" menu ................. 184
Index ................................. 201
Document information Proline Prowirl F 200 PROFIBUS PA
6 Endress+Hauser
1 Document information
1.1
Document function
These Operating Instructions contain all the information that is required in various phases
of the life cycle of the device: from product identification, incoming acceptance and
storage, to mounting, connection, operation and commissioning through to
troubleshooting, maintenance and disposal.
1.2 Symbols used
1.2.1 Safety symbols
Symbol Meaning
DANGER
A0011189-EN
DANGER!
This symbol alerts you to a dangerous situation. Failure to avoid this situation will result in
serious or fatal injury.
WARNING
A0011190-EN
WARNING!
This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in
serious or fatal injury.
CAUTION
A0011191-EN
CAUTION!
This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in
minor or medium injury.
NOTICE
A0011192-EN
NOTICE!
This symbol contains information on procedures and other facts which do not result in
personal injury.
1.2.2 Electrical symbols
Symbol Meaning
A0011197
Direct current
A terminal to which DC voltage is applied or through which direct current flows.
A0011198
Alternating current
A terminal to which alternating voltage is applied or through which alternating current flows.
A0017381
Direct current and alternating current
A terminal to which alternating voltage or DC voltage is applied.
A terminal through which alternating current or direct current flows.
A0011200
Ground connection
A grounded terminal which, as far as the operator is concerned, is grounded via a grounding
system.
A0011199
Protective ground connection
A terminal which must be connected to ground prior to establishing any other connections.
A0011201
Equipotential connection
A connection that has to be connected to the plant grounding system: This may be a potential
equalization line or a star grounding system depending on national or company codes of practice.
Proline Prowirl F 200 PROFIBUS PA Document information
Endress+Hauser 7
1.2.3 Tool symbols
Symbol Meaning
A0011220
Flat blade screwdriver
A0011221
Allen key
A0011222
Open-ended wrench
1.2.4 Symbols for certain types of information
Symbol Meaning
A0011182
Allowed
Indicates procedures, processes or actions that are allowed.
A0011183
Preferred
Indicates procedures, processes or actions that are preferred.
A0011184
Forbidden
Indicates procedures, processes or actions that are forbidden.
A0011193
Tip
Indicates additional information.
A0011194
Reference to documentation
Refers to the corresponding device documentation.
A0011195
Reference to page
Refers to the corresponding page number.
A0011196
Reference to graphic
Refers to the corresponding graphic number and page number.
,
,
Series of steps
Result of a sequence of actions
A0013562
Help in the event of a problem
1.2.5 Symbols in graphics
Symbol Meaning
1, 2, 3,... Item numbers
,
,
Series of steps
A, B, C, ... Views
A-A, B-B, C-C, ... Sections
A0013441
Flow direction
-
A0011187
Hazardous area
Indicates a hazardous area.
.
A0011188
Safe area (non-hazardous area)
Indicates a non-hazardous area.
Document information Proline Prowirl F 200 PROFIBUS PA
8 Endress+Hauser
1.3 Documentation
The following document types are available:
On the CD-ROM supplied with the device
In the Download Area of the Endress+Hauser Internet site: www.endress.com →
Download
For a detailed list of the individual documents along with the documentation code
1.3.1
Standard documentation
Document type Purpose and content of the document
Technical Information Planning aid for your device
The document contains all the technical data on the device and provides
an overview of the accessories and other products that can be ordered for
the device.
Brief Operating Instructions Guide that takes you quickly to the 1st measured value
The Brief Operating Instructions contain all the essential information
from incoming acceptance to initial commissioning.
1.3.2 Supplementary device-dependent documentation
Additional documents are supplied depending on the device version ordered: Always
comply strictly with the instructions in the supplementary documentation. The
supplementary documentation is an integral part of the device documentation.
1.4
Registered trademarks
PROFIBUS
®
Registered trademark of the PROFIBUS User Organization, Karlsruhe, Germany
KALREZ
®
, VITON
®
Registered trademarks of DuPont Performance Elastomers L.L.C., Wilmington, DE USA
GYLON
®
Registered trademark of Garlock Sealing Technologies, Palmyar, NY, USA
Applicator
®
, FieldCare
®
, Field Xpert
TM
, HistoROM
®
, Heartbeat Technology
TM
Registered or registration-pending trademarks of the Endress+Hauser Group
Proline Prowirl F 200 PROFIBUS PA Basic safety instructions
Endress+Hauser 9
2 Basic safety instructions
2.1
Requirements for the personnel
The personnel for installation, commissioning, diagnostics and maintenance must fulfill
the following requirements:
Trained, qualified specialists must have a relevant qualification for this specific function
and task
Are authorized by the plant owner/operator
Are familiar with federal/national regulations
Before beginning work, the specialist staff must have read and understood the
instructions in the Operating Instructions and supplementary documentation as well as
in the certificates (depending on the application)
Following instructions and basic conditions
The operating personnel must fulfill the following requirements:
Being instructed and authorized according to the requirements of the task by the
facility's owner-operator
Following the instructions in these Operating Instructions
2.2 Designated use
Application and media
Depending on the version ordered, the measuring device can also measure potentially
explosive, flammable, poisonous and oxidizing media.
Measuring devices for use in hazardous areas, in hygienic applications or in applications
where there is an increased risk due to process pressure, are labeled accordingly on the
nameplate.
To ensure that the measuring device remains in proper condition for the operation time:
Only use the measuring device in full compliance with the data on the nameplate and
the general conditions listed in the Operating Instructions and supplementary
documentation.
Based on the nameplate, check whether the ordered device is permitted for the
intended use in the hazardous area (e.g. explosion protection, pressure vessel safety).
Use the measuring device only for media against which the process-wetted materials
are adequately resistant.
If the measuring device is not operated at atmospheric temperature, compliance with
the relevant basic conditions specified in the device documentation provided (on the
CD-ROM) is absolutely essential.
Incorrect use
Non-designated use can compromise safety. The manufacturer is not liable for damage
caused by improper or non-designated use.
!
WARNING
Danger of breakage of the sensor due to corrosive or abrasive fluids!
Verify the compatibility of the process fluid with the sensor material.
Ensure the resistance of all fluid-wetted materials in the process.
Observe the specified pressure and temperature range.
Verification for borderline cases:
For special fluids and fluids for cleaning, Endress+Hauser is glad to provide assistance
in verifying the corrosion resistance of fluid-wetted materials, but does not accept any
warranty or liability as minute changes in the temperature, concentration or level of
contamination in the process can alter the corrosion resistance properties.
Basic safety instructions Proline Prowirl F 200 PROFIBUS PA
10 Endress+Hauser
Residual risks
Possible burn hazard due to fluid temperatures!
For elevated fluid temperature, ensure protection against contact to prevent burns.
2.3
Workplace safety
For work on and with the device:
Wear the required personal protective equipment according to federal/national
regulations.
For welding work on the piping:
Do not ground the welding unit via the measuring device.
If working on and with the device with wet hands:
It is recommended to wear gloves on account of the higher risk of electric shock.
2.4 Operational safety
Risk of injury.
Operate the device in proper technical condition and fail-safe condition only.
The operator is responsible for interference-free operation of the device.
Conversions to the device
Unauthorized modifications to the device are not permitted and can lead to unforeseeable
dangers.
If, despite this, modifications are required, consult with Endress+Hauser.
Repair
To ensure continued operational safety and reliability,
Carry out repairs on the device only if they are expressly permitted.
Observe federal/national regulations pertaining to repair of an electrical device.
Use original spare parts and accessories from Endress+Hauser only.
2.5 Product safety
This measuring device is designed in accordance with good engineering practice to meet
state-of-the-art safety requirements, has been tested, and left the factory in a condition in
which it is safe to operate.
It meets general safety standards and legal requirements. It also complies with the EC
directives listed in the device-specific EC Declaration of Conformity. Endress+Hauser
confirms this by affixing the CE mark to the device.
2.6 IT security
We only provide a warranty if the device is installed and used as described in the
Operating Instructions. The device is equipped with security mechanisms to protect it
against any inadvertent changes to the device settings.
IT security measures in line with operators' security standards and designed to provide
additional protection for the device and device data transfer must be implemented by the
operators themselves.
Endress+Hauser can be contacted to provide support in performing this task.
Proline Prowirl F 200 PROFIBUS PA Product description
Endress+Hauser 11
3 Product description
3.1
Product design
1 2
3
4
5 6
7
8
9
+
E
A0020649
1 Important components of a measuring device
1 Electronics compartment cover
2 Display module
3 Main electronics module
4 Cable glands
5 Transmitter housing (incl. HistoROM)
6 I/O electronics module
7 Terminals (spring loaded terminals, pluggable)
8 Connection compartment cover
9 Sensor
Incoming acceptance and product identification Proline Prowirl F 200 PROFIBUS PA
12 Endress+Hauser
4 Incoming acceptance and product
identification
4.1
Incoming acceptance
A0015502
A0013843
Is the order code on the delivery note (1) identical to the order code on the product sticker
(2)?
A0013695
A0015502
A0013698
Are the goods undamaged?
A0015502
A0013699
Do the nameplate data match the ordering information on the delivery note?
A0015502
A0013697
Is the CD-ROM with the Technical Documentation and documents present?
Proline Prowirl F 200 PROFIBUS PA Incoming acceptance and product identification
Endress+Hauser 13
If one of the conditions is not satisfied, contact your Endress+Hauser Sales Center.
4.2
Product identification
The following options are available for identification of the measuring device:
Nameplate specifications
Order code with breakdown of the device features on the delivery note
Enter serial numbers from nameplates in W@M Device Viewer
(www.endress.com/deviceviewer): All information about the measuring device is
displayed.
For an overview of the scope of the Technical Documentation provided, refer to the
following:
The "Additional standard documentation on the device" (→  8) and "Supplementary
device-dependent documentation" (→  8) sections
The W@M Device Viewer: Enter the serial number from the nameplate
(www.endress.com/deviceviewer)
4.2.1 Transmitter nameplate
Ordercode:
Ext.ord.cd.:
Ser.no.:
Date:
i
i
Patents
322540-0001
1
2
3 4 5
6
7
8
9
10 11
12
14
15
16
17
13
A0013906
2 Example of a transmitter nameplate
1 Manufacturing location
2 Name of the transmitter
3 Order code
4 Serial number
5 Extended order code
6 Electrical connection data, e.g. available inputs and outputs, supply voltage
7 Type of cable glands
8 Permitted ambient temperature range (T
a
)
9 Firmware version (FW) from the factory
10 CE mark, C-Tick
11 Additional information on version: certificates, approvals
12 Permitted temperature range for cable
13 Manufacturing date: year-month
14 Degree of protection
15 Explosion protection approval information
16 Document number of safety-related supplementary documentation
17 2-D matrix code
Incoming acceptance and product identification Proline Prowirl F 200 PROFIBUS PA
14 Endress+Hauser
4.2.2 Sensor nameplate
Order code for "Housing" option B "GT18 two-chamber, 316L" and option K "GT18
two-chamber, remote, 316L"
Ser. no.:
Ptest:
Size:
Materials:
Gasket:
Tm:
Qmax(G):
Ta:
1
2 6
7
8
3
9
10
13 12
4 5
14 11
A0020760
3 Example of a sensor nameplate
1 Name of the sensor
2 Nominal diameter of the sensor
3 Flange nominal diameter/nominal pressure
4 Serial number (Ser. no.)
5 Measuring tube material
6 Measuring tube material
7 Maximal permitted volume flow (gas/steam)
8 Test pressure of the sensor
9 Seal material
10 Document number of safety-related supplementary documentation (→  171)
11 Ambient temperature range
12 CE mark
13 Medium temperature range
14 Degree of protection
Proline Prowirl F 200 PROFIBUS PA Incoming acceptance and product identification
Endress+Hauser 15
Order code for "Housing" option C "GT20 two-chamber, aluminum coated"
Ser. no.:
Ptest:
Size:
Materials:
Tm:
Qmax(G):
Gasket:
Ta:
1
2
5 6 8
7
9
3
4
10
111213
A0020758
4 Example of a sensor nameplate
1 Nominal diameter of the sensor
2 Flange nominal diameter/nominal pressure
3 Measuring tube material
4 Measuring tube material
5 Serial number (Ser. no.)
6 Maximal permitted volume flow (gas/steam)
7 Test pressure of the sensor
8 Degree of protection
9 Approval information for explosion protection and Pressure Equipment Directive
10 CE mark
11 Seal material
12 Medium temperature range
13 Ambient temperature range
Incoming acceptance and product identification Proline Prowirl F 200 PROFIBUS PA
16 Endress+Hauser
Order code for "Housing" option J "GT20 two-chamber, remote, aluminum coated"
Order code:
Ext. ord. cd.:
Ser. no.:
Ptest:
Size:
Ta:
Materials:
Gasket:
Tm:
Qmax(G):
4
1
5
8
12
2 7
9
10
11
13141516
3 6
A0020759
5 Example of a sensor nameplate
1 Name of the sensor
2 Nominal diameter of the sensor
3 Flange nominal diameter/nominal pressure
4 Order code
5 Serial number (Ser. no.)
6 Extended order code (Ext. ord. cd.)
7 Maximal permitted volume flow (gas/steam)
8 Degree of protection
9 Approval information for explosion protection and Pressure Equipment Directive
10 Ambient temperature range
11 Document number of safety-related supplementary documentation (→  171)
12 Test pressure of the sensor
13 Measuring tube material
14 Measuring tube material
15 Seal material
16 Medium temperature range
Order code
The measuring device is reordered using the order code.
Extended order code
The device type (product root) and basic specifications (mandatory features) are
always listed.
Of the optional specifications (optional features), only the safety and approval-
related specifications are listed (e.g. LA). If other optional specifications are also
ordered, these are indicated collectively using the # placeholder symbol (e.g. #LA#).
If the ordered optional specifications do not include any safety and approval-related
specifications, they are indicated by the + placeholder symbol (e.g. XXXXXX-ABCDE
+).
4.2.3 Symbols on measuring device
Symbol Meaning
WARNING!
This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in serious
or fatal injury.
A0011194
Reference to documentation
Refers to the corresponding device documentation.
A0011199
Protective ground connection
A terminal which must be connected to ground prior to establishing any other connections.
Proline Prowirl F 200 PROFIBUS PA Storage and transport
Endress+Hauser 17
5 Storage and transport
5.1
Storage conditions
Observe the following notes for storage:
Store in the original packaging to ensure protection from shock.
Do not remove protective covers or protective caps installed on process connections.
They prevent mechanical damage to the sealing surfaces and contamination in the
measuring tube.
Protect from direct sunlight to avoid unacceptably high surface temperatures.
Storage temperature:
All components apart from the display modules: –50 to +80 °C (–58 to +176 °F)
Display modules:–40 to +80 °C (–40 to +176 °F)
Store in a dry and dust-free place.
Do not store outdoors.
5.2 Transporting the product
!
WARNING
Center of gravity of the measuring device is higher than the suspension points of the
webbing slings.
Risk of injury if the measuring device slips.
Secure the measuring device from rotating or slipping.
Observe the weight specified on the packaging (stick-on label).
Observe the transport instructions on the stick-on label on the electronics compartment
cover.
A0015606
Observe the following notes during transport:
Transport the measuring device to the measuring point in the original packaging.
Lifting gear
Webbing slings: Do not use chains, as they could damage the housing.
For wood crates, the floor structure enables these to be loaded lengthwise or broadside
using a forklift.
For measuring device >DN 40 (1½): lift the measuring device using the webbing slings
at the process connections; do not lift at the transmitter housing or the connection
housing of the remote version.
Do not remove protective covers or protective caps installed on process connections.
They prevent mechanical damage to the sealing surfaces and contamination in the
measuring tube.
Storage and transport Proline Prowirl F 200 PROFIBUS PA
18 Endress+Hauser
5.3 Packaging disposal
All packaging materials are environmentally friendly and 100% recyclable:
Measuring device secondary packaging: polymer stretch film that conforms to EC
Directive 2002/95/EC (RoHS).
Packaging:
Wood crate, treated in accordance with ISPM 15 standard, which is confirmed by the
affixed IPPC logo.
or
Carton in accordance with European Packaging Directive 94/62EC; recyclability is
confirmed by the affixed RESY symbol.
Seaworthy packaging (optional): Wood crate, treated in accordance with ISPM 15
standard, which is confirmed by the affixed IPPC logo.
Carrying and mounting hardware:
Disposable plastic pallet
Plastic straps
Plastic adhesive strips
Dunnage: Paper cushion
Proline Prowirl F 200 PROFIBUS PA Mounting
Endress+Hauser 19
6 Mounting
6.1
Installation conditions
No special measures such as supports are necessary. External forces are absorbed by the
construction of the device.
6.1.1 Mounting position
Mounting location
A0015543
Orientation
Vortex meters require a fully developed flow profile as a prerequisite for correct volume
flow measurement.
The direction of the arrow on the sensor nameplate helps you to install the sensor
according to the flow direction (direction of medium flow through the piping).
The device can basically be installed in any orientation in the pipe. However, note the
following points:
Orientation Compact version Remote version
A Vertical orientation
A0015545

1)

B Horizontal orientation,
transmitter head up
A0015589

2) 3)

Mounting Proline Prowirl F 200 PROFIBUS PA
20 Endress+Hauser
Orientation Compact version Remote version
C Horizontal orientation,
transmitter head down
A0015590

4) 5)

D Horizontal orientation,
transmitter head at side
A0015592

4)

1) In the case of liquids, there should be upward flow in vertical pipes to avoid partial pipe filling (Fig. A).
Disruption in flow measurement! In the case of vertical orientation and downward flowing liquid, the pipe
always needs to be completely filled to ensure correct liquid flow measurement.
2)
Danger of electronics overheating! If the fluid temperature is ≥ 200 °C (392 °F) orientation B is not
permitted for the wafer version (Prowirl D) with nominal diameters DN 100 (4") and DN 150 (6").
3) In the case of hot media (e.g. steam or fluid temperature (TM) ≥ 200 °C (392 °F): orientation C or D
4) In the case of very cold media (e.g. liquid nitrogen): orientation B or D
5) For "wet steam detection" option: orientation C
Minimum spacing and cable length
The following dimensions must be observed to guarantee problem-free access to the device
for service purposes:
Minimum spacing (A) in all directions = 100 mm (3.94 in)
Necessary cable length (L): L + 150 mm (5.91 in)
A
L
A0019211
A Minimum spacing in all directions
L Required cable length
Rotating the electronics housing and the display
The electronics housing can be rotated continuously by 360° on the housing support. The
display unit can be rotated in
45° stages. This means you can read the display comfortably
from all directions.
Inlet and outlet runs
To attain the specified level of accuracy of the measuring device, the inlet and outlet runs
mentioned below must be maintained at the very minimum. If there are several flow
disturbances present, the longest specified inlet run must be maintained.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124
  • Page 125 125
  • Page 126 126
  • Page 127 127
  • Page 128 128
  • Page 129 129
  • Page 130 130
  • Page 131 131
  • Page 132 132
  • Page 133 133
  • Page 134 134
  • Page 135 135
  • Page 136 136
  • Page 137 137
  • Page 138 138
  • Page 139 139
  • Page 140 140
  • Page 141 141
  • Page 142 142
  • Page 143 143
  • Page 144 144
  • Page 145 145
  • Page 146 146
  • Page 147 147
  • Page 148 148
  • Page 149 149
  • Page 150 150
  • Page 151 151
  • Page 152 152
  • Page 153 153
  • Page 154 154
  • Page 155 155
  • Page 156 156
  • Page 157 157
  • Page 158 158
  • Page 159 159
  • Page 160 160
  • Page 161 161
  • Page 162 162
  • Page 163 163
  • Page 164 164
  • Page 165 165
  • Page 166 166
  • Page 167 167
  • Page 168 168
  • Page 169 169
  • Page 170 170
  • Page 171 171
  • Page 172 172
  • Page 173 173
  • Page 174 174
  • Page 175 175
  • Page 176 176
  • Page 177 177
  • Page 178 178
  • Page 179 179
  • Page 180 180
  • Page 181 181
  • Page 182 182
  • Page 183 183
  • Page 184 184
  • Page 185 185
  • Page 186 186
  • Page 187 187
  • Page 188 188
  • Page 189 189
  • Page 190 190
  • Page 191 191
  • Page 192 192
  • Page 193 193
  • Page 194 194
  • Page 195 195
  • Page 196 196
  • Page 197 197
  • Page 198 198
  • Page 199 199
  • Page 200 200
  • Page 201 201
  • Page 202 202
  • Page 203 203
  • Page 204 204
  • Page 205 205
  • Page 206 206