MS Sedco Privacy Timing Module Installation Instructions Manual

Type
Installation Instructions Manual
Page 1
(82A044) PTMv1017
Section 1
General Description
The PTM is a timing module that allows users to control
an automatic door operator for a room where privacy is a
concern, such as a washroom, restroom, clean room, or
photo development room. From the outside of the room,
users are able to activate the door. Once inside, users
are able to lock the door which prevents access from the
outside “push to open” button. When egress is desired,
the user presses an inside “push to open” button which
deactivates the lock and activates the door. A keyswitch
override is present on the exterior, as well as LEDs to
indicate if the room is occupied. Green indicates
available while red indicates occupied.
The delay time between deactivating the lock and
activating the door, as well as the “on time” for door
activation are fully programmable.
WARNING: Devices to be controlled by the PTM
must be low voltage (12-24V) but can be
inductive loads. Surge suppressors are standard
on the PTM.
OPTIONS:
PTM = Privacy Timing Module
PTM-HDWE = Prewired Harness to Terminal Block &
Magnetic Door Position Switch
PTM-KIT = Turnkey Kit Includes PTM, PTM-HDWE &
Switches (830B-59J-PTM, 59V-PTM)
WET/DRY CONTACT OPTION:
The PTM has the option to supply power to Relay Output
1 contacts. This is known as having a "Wet" contact
instead of the conventional "Dry" contact closure. To use
output 1 as a "Wet" contact, change the jumper setting
(see Figure 1). The voltage supplied to Output 1 will be
the same as the voltage supplied to the input power wires
of the PTM.
WARNING: Changing jumper settings to enable
the “Wet” Contact option will apply a voltage to
the Output 1 relay contact. Please ensure that
any device connected to this output is capable of
accepting voltage. Failure to do so may result in
damage to the device.
WARNING: If the “Wet” Contact Option is to be
used, please ensure that no more than a
maximum of 3A current is to be supplied by the
PTM. Failure to do so may result in damage to
the PTM.
Section 2
Basic Installation
1. Mount the PTM in desired location.
2. With power off, make all necessary wiring
connections to the wiring harnesses (Fig. 1) or
Pre-wired Terminal Block (Fig. 2).
Figure 1: PTM Layout and Wiring Connections
NOTICE: These instructions are provided for your
convenience. Please verify your installation is in
compliance with all applicable standards upon
completing installation of this device.
Section 3
Technical Data
Model.................................... PTM
Input Power........................... 12-24V AC or DC
Power Consumption............. 2W Maximum
Output Contacts................... Form C, Rated at 3 Amps
Relay Contact Rating............ 3A:120V AC; 3A:60V DC
Temperature Rating............. -22°F to 158°F
(-30°C to 70°C)
Weight................................... <0.25 lbs.
Physical Size......................... 4.75"L x 2.125"W x 0.75"H
Section 4
Warranty
MS SEDCO guarantees this product to be free from manufacturing
defects for 1 year from date of installation. Unless MS SEDCO is
notified of the date of installation, the warranty will be in effect for
1 year from the date of shipment from our factory. If, during the
first year, this device fails to operate and has not been tampered
with or abused, the unit can be returned prepaid to factory and it
will be repaired free of charge. After 1 year, the unit will be
repaired for a nominal service charge. This limited warranty is in
lieu of all other warranties expressed or implied, including any
implied warranty of merchantability, and no representative or
person is authorized to assume for MS SEDCO any other liability
in connection with the sale of our products. All warranties are
limited to the duration of this written warranty. In no event
shall MS SEDCO be liable for any special, incidental,
consequential or other damages arising from any claimed
breach of warranty as to its products or services.
Questions? Call us toll-free at 1-317-842-2545 or
visit us online at www.mssedco.com.
!
!
!
!
Privacy Timing Module INSTALLATION INSTRUCTIONS
The
Commander
Series
PTM
7898 Zionsville Road Indianapolis, Indiana 46268
Telephone: (317) 842-2545 www.mssedco.com custsvc@mssedco.com
Wht/Brown
Green
Green
Blue
Wht/Red
Wht/Grn
Wht/Vio
Page 2
(82A044) PTMv1017
Privacy Timing Module INSTALLATION INSTRUCTIONS
The
Commander
Series
PTM
Wet/Dry
Contact Option
Orange
Brown
Ye llow
Violet
Gray
White
PTM
INPUT 1
12-24V AC/DC
INPUT 1
CO M
CO M
N. O.
N. C.
N. C.
N. O.
PROGRAM
MODE BUTTON DISPLAY
ADJUSTMENT
LED DISPLAY KEY
d1 = delay output 1 to 2
d2 = output 2 on time
i1 = input 1 (n.o. / n.c.)
i3 = input 3 (n.o. / n.c.)
i2 = input 2 (n.o. / n.c.)
i4 = input 4 (n.o. / n.c.)
o2 = output 2 (n.o. / n.c.)
o1 = output 1 (n.o. / n.c.)
01= dry
01= wet
Output #1
Output #2
INPUT 4
INPUT 3
INPUT 2
CO M
CO M
Green
Green
Blue
Wht/Blue
Wht/Red
Wht/Grn
Wht/Vio
Wht/Gray
Wht/Brown
FIGURE 1—PTM Layout & Wiring Connections
Input Connections
Wht/Blue
Wht/Gra
Input Power 12-24V
(AC or DC)
Switch Input #1 -
Inside Push to Open Switch
Switch Input #2 -
Outside Key Switch and Latchbolt
or Inside Lever Monitor (if used)
Switch Input # 3 -
Inside Push to Lock Switch
Switch Input #4 -
Outside Push to Open Switch
Output
Connections
Orange
Brown
Yellow
Violet
White
Gray Output
#1
Output
#2
COM
N.O.
N.C.
COM
N.O.
N.C.
Input Actions
Input 1—Deactivates Output 1, then activates Output 2.
Input 2—Deactivates Output 1.
Input 3—Activates Output 1. Locks out Input 4.
Input 4—Activates Output 2.
(Factory Setting = Dry Contact)
LED Connections
In series with electric lock
Output #1
GREEN LED
Output #1
RED LED &
Electric Lock
COM
N.O.
N.C.
COM
N.O.
N.C.
7898 Zionsville Road Indianapolis, Indiana 46268
Telephone: (317) 842-2545 www.mssedco.com custsvc@mssedco.com
Page 3
(82A044) PTMv1017
Privacy Timing Module INSTALLATION INSTRUCTIONS
The
Commander
Series
PTM
FIGURE 2—PTM Kit Wiring Diagram
PTM
INPUT 1
12-24V AC/DC
INPUT 1
CO M
CO M
N. O.
N. C.
N. C.
N. O.
PROGRAM
MODE BUTTON DISPLAY
ADJUSTMENT
LED DISPLAY KEY
d1 = delay output 1 to 2
d2 = output 2 on time
i1 = input 1 (n.o. / n.c.)
i3 = input 3 (n.o. / n.c.)
i2 = input 2 (n.o. / n.c.)
i4 = input 4 (n.o. / n.c.)
o2 = output 2 (n.o. / n.c.)
o1 = output 1 (n.o. / n.c.)
01= dry
01= wet
Output #1
Output #2
INPUT 4
INPUT 3
INPUT 2
CO M
CO M
PTM Wire Harness is Prewired to Terminal Block
Wht/Brn
Wht/Gray
Wht/Vio
Wht/Grn
Wht/Red
Wht/Blue
Blue
Green
Green
Auto
Door
Control
Activation
Circuit
!
NOTE:
1. All LEDs provided have
built-in resistors.
2. Strike shown is wired
fail-safe. Door can be
opened if power fails.
3. Strike and power voltages
must match.
Green
LED Strike Red
LED
Vcc
24V +
-
7898 Zionsville Road Indianapolis, Indiana 46268
Telephone: (317) 842-2545 www.mssedco.com custsvc@mssedco.com
Page 4
(82A044) PTMv1017
Privacy Timing Module INSTALLATION INSTRUCTIONS
The
Commander
Series
PTM
FIGURE 3—LOCK AND RUN DETERRANT DIAGRAM
Unlock & Open
12-24V AC or DC
1
2
3
4
5
6
7
8
9
Green
LED Strike Red
LED
Vcc
24V +
-
Door
Activation
O
P
E
N
O
P
E
N
L
O
C
K
U
N
L
O
C
K
NOTE: Additional Red LED’s are
connected in parallel with
the one shown.
Key
Red Green
Unlock
Open
Outside
Inside
Lock
NC
NO
COM
Guard
Magnetic
Switch on Door
Bypass Switch
7898 Zionsville Road Indianapolis, Indiana 46268
Telephone: (317) 842-2545 www.mssedco.com custsvc@mssedco.com