System Sensor FAAST Modbus Schema 2 User guide

Category
Fire protection
Type
User guide

System Sensor FAAST Modbus Schema 2 is an advanced particulate matter detection system with early warning and very early warning fire detection capabilities. It can monitor and detect particulate levels, airflow, and faults remotely. You can also use it to modify device settings and configurations, and read logs and events. Here are some of its key features:

  • Early warning and very early warning fire detection: System Sensor FAAST Modbus Schema 2 uses aspirating smoke detection technology to detect smoke particulates in the air. This allows it to detect fires at a very early stage, providing you with valuable time to respond.

System Sensor FAAST Modbus Schema 2 is an advanced particulate matter detection system with early warning and very early warning fire detection capabilities. It can monitor and detect particulate levels, airflow, and faults remotely. You can also use it to modify device settings and configurations, and read logs and events. Here are some of its key features:

  • Early warning and very early warning fire detection: System Sensor FAAST Modbus Schema 2 uses aspirating smoke detection technology to detect smoke particulates in the air. This allows it to detect fires at a very early stage, providing you with valuable time to respond.
FAAST Fire Alarm Aspiration Sensing
Technology
®
Modbus Protocol Schema 2
USER GUIDE
User Guide: FAAST Fire Alarm Aspiration Sensing Technology® Modbus Protocol Schema 2
22
Table of Contents
Product Description .........................................................................................................................3
Communication Interface ................................................................................................................3
Client Interface ..................................................................................................................................3
Accessible Registers .........................................................................................................................................................................3
Data Format ........................................................................................................................................................................................3
Device Sensor Status and Control Operations ..............................................................................4
Modbus Administrator Password .....................................................................................................................................................4
Device Identier .................................................................................................................................................................................4
Device Read ........................................................................................................................................................................................4
Device Output and Operating Mode Control ...................................................................................................................................5
Device Conguration .........................................................................................................................................................................5
Device Time ........................................................................................................................................................................................6
Device Smoke Reference ..................................................................................................................................................................6
Reading Logs .....................................................................................................................................................................................7
Event Log Read ..................................................................................................................................................................................7
Trend Log Read ..................................................................................................................................................................................7
Message Log Read ............................................................................................................................................................................7
Modbus Conguration .....................................................................................................................8
Input Registers..................................................................................................................................8
Holding Registers .............................................................................................................................9
Device Status .....................................................................................................................................................................................9
Sensor Status ................................................................................................................................................................................... 11
Device Logs ......................................................................................................................................................................................13
Factory Conguration ......................................................................................................................................................................14
Device Conguration .......................................................................................................................................................................15
Network Conguration ....................................................................................................................................................................17
Appendix A. Congurable options on FAAST .............................................................................. 18
A.1. Alarm Conguration Variables .................................................................................................................................................18
A.2. Device Conguration Variables ...............................................................................................................................................19
Revision Table
Revision Description of Change Author Date
A Initial Release for Review ZK 05/06/2013
B Implemented Modbus Slave ID ZK 10/21/14
User Guide: FAAST Fire Alarm Aspiration Sensing Technology® Modbus Protocol Schema 2
3
Rev B
Product Description
The FAAST - Fire Alarm Aspiration Sensing Technology® aspirating smoke detector is an advanced particulate detection system
designed for use in early warning and very early warning fire detection applications. FAAST draws air from the environment through
sampling holes in a pipe network and monitors for smoke particulates. FAAST includes a local display which provides a clear
indication of the devices status. Smoke particulate level, alarm level, air flow, and faults can all be discerned with a glance at the
user interface.
FAAST is also enabled by built-in Modbus communications capabilities. The Modbus Protocol utilizes the TCP server. They physical
connection is Ethernet.
Modbus is a communications protocol allowing for connectivity with several building management solutions. Using Modbus, a
FAAST device can be monitored remotely and various device configuration actions and device interactions are facilitated.
PLEASE NOTE: WHILE Modbus CAN BE USED TO SET DEVICE CONFIGURATIONS, THE DESIGN OF ANY NEW FAAST
DEVICE MUST BE VERIFIED USING PipeIQ
®
TO ENSURE THAT SITE SPECIFIC REQUIREMENTS ARE MET. IF Modbus IS USED
TO MODIFY AN INSTALLED UNIT, ANY CHANGES TO SENSITIVITY SETTING SHOULD ALSO BE VERIFIED IN PipeIQ
®
TO
ENSURE CONTINUED SYSTEM PERFORMANCE.
Client Interface
When a client is connected through Port 502, the FAAST device will act as a Modbus/TCP “server”. This section defines the format of
data in Modbus/TCP registers. More information about Modbus/TCP can be obtained from www.Modbus.org.
The entire Modbus map is related to a single device, and the Slave ID parameter is unused by the FAAST device.
Accessible Registers
Input registers for registers listed in Table 1.
Holding registers in Tables 2 to 8.
Data Format
To properly transfer data to and from the Modbus registers, the following descriptions specify how data is organized when more than
one register is required to read or write a specific piece of data.
1. Long Integer, floating point:
Value = 0xaabbccdd
Holding Reg1 = 0xaabb
Holding Reg2 = 0xccdd
2. String:
Value = “test”
Holding Reg1 = “et”
Holding Reg2 = “ts”
Communication Interface
Modbus protocol stack is an application that runs over TCP. The device requires a 10 or 100Mbps Ethernet connection to an existing
IP network and a valid network configuration in order to enable Modbus Communications. The FAAST device’s TCP server will listen
for Modbus protocol packets on Port 502.
Separate TCP ports allow Modbus, e-mail, PipeIQ and web communications simultaneously. Finally, to transmit and receive data over
Modbus, the user requires a client that can generate Modbus packets over TCP.
3. IP Address:
Value = a.b.c.d
Holding Reg1 = dc
Holding Reg2 = ba
4. MAC Address:
Value = 0x (aa-bb-cc-dd-ee-ff)
Holding Reg1 = 0xbbaa
Holding Reg2 = 0xddcc
Holding Reg3 = 0xffee
User Guide: FAAST Fire Alarm Aspiration Sensing Technology® Modbus Protocol Schema 2
4
Device Sensor Status and Control Operations
Modbus Administrator Password
The Modbus Administrator Password grants the user the privilege of writing to the Holding Registers. This password is the same as
the User Interface Button Lockout Code. It is not readable through the Modbus Interface. It is set to ‘1111’ as the default. The values
may range from 1111 to 9999. The user may change the password by performing a Device Configuration Change as described
earlier.
A failure to gain administrator privileges due to a forgotten or lost password is a recoverable event by using the PipeIQ software,
connecting to the device and updating the device configuration with a known password.
Device Identier
The Modbus Slave Identifier is set in PipeIQ. The device will respond to Modbus commands at the device’s configured Device
Identifier. The valid range is 1-247.
Conventional
The Device Identifier is set in PipieIQ. The valid range is 1-255. The device will only respond to Modbus commands if the
Device Identifier is set within the valid Modbus range.
Intelligent Eclipse
The Device Identifier is set through the FACP protocol commands. The valid range is 1-255. The device will only respond to
Modbus commands if the Device Identifier is set within the valid Modbus range.
Intelligent Flashscan
The Device Identifier is set through PipeIQ. The valid range is 1-159. When set outside this range, the device will respond to
FACP Flashscan protocol commands at Address 0 only, but the Modbus server may respond to commands at the identifier
value set so long as it is within 1-247.
Intelligent CLIP
The Device Identifier is set through PipeIQ. The valid range is 1-99. When set outside this range, the device will respond to
FACP CLIP protocol commands at Address 0 only, but the Modbus server may respond to commands at the identifier value
set so long as it is within 1-247.
Device Read
The Modbus client is able to read the device status data directly via input and holding register reads.
User Guide: FAAST Fire Alarm Aspiration Sensing Technology® Modbus Protocol Schema 2
5
Rev B
Device Output and Operating Mode Control
The Modbus client is able to initiate different operating modes through the Sensor Input Holding Register.
1. Write the Administrator Password in the Administrator Password holding register (this is the same as the Button
Activation Passcode configured through PipeIQ).
2. Read the Sensor API status holding register and verify that the ADMIN_UNLOCK bit is set.
3. Write the value to the Sensor Input Holding Register (40035) that initiates the desired action or mode change:
a. 0x0001 to Isolate
b. 0x0002 to Disable
c. 0x0004 to initiate Test Mode
d. 0x0008 to Silence a Fault or Alarm (when equipped with an audible indicator)
e. 0x0010 to Reset the Device
f. 0x0020 to Reset the Airflow Baseline
g. 0x0040 to Clear the Event Log
h. 0x0080 to Clear the Trend Log
i. 0x0100 to Clear the Message Log
4. Write 0x0 to the Administrator Password in the Administrator Password holding register if no further changes are desired.
Device Conguration
In order to write a new configuration, the following steps must be followed:
1. Write the Administrator Password in the Administrator Password holding register (this is the same as the Button
Activation Passcode configured through PipeIQ).
2. Read the Sensor API status holding register and verify that the ADMIN_UNLOCK bit is set. If it is set, the Sensor API
Command Register is enabled and will process commands issued.
3. The device must be placed in Disable Mode by setting disable bit in Sensor Input Holding register Holding register.
4. Read the Operating Mode holding register.
5. The Modbus client writes the new values for the respective configuration holding registers through Write Multiple
Register Command(s).
6. Write the Save Configuration Command value, 0xAA11 in the Modbus Specific configuration Command holding register
in order to save any configuration changes.
7. The device stores new configuration.
8. Read the Modbus Specific configuration Command holding register. The value will be 0x0000 when the Command
completes successfully.
9. Remove the device from Disable Mode by clearing the disable bit Sensor Input Holding register.
10. The device will reset and the new configuration will be applied.
User Guide: FAAST Fire Alarm Aspiration Sensing Technology® Modbus Protocol Schema 2
6
Device Sensor Status and Control Operations (Contd)
Device Time
In order to set the time, the following steps must be followed:
1. Write the Administrator Password in the Administrator Password holding register.
2. Read the Sensor API status holding register and verify that the ADMIN_UNLOCK bit is set. If it is set, the Sensor API
Command Register is enabled and will process commands issued.
3. The Modbus client writes the new time value using Epoch/UNIX timestamp formate to the time holding registers through
Write Multiple Register Command(s).
4. Write the Save Time Command value, 0xEE22 in the Modbus Specific configuration Command holding register in order
to save the new time.
5. The device stores and applies the new device time.
6. Read the Modbus Specific configuration Command holding register. The value will be 0x0000 when the Command
completes successfully.
7. Write 0x0 to the Administrator Password in the Administrator Password holding register if no further changes are
desired.
Device Smoke Reference
The device may be programmed with a reference in order to compensate for a period of high particulate due to a change in ambient
environmental conditions. Use the following steps to modify the Device Reference:
1. Write the Administrator Password in the Administrator Password holding register.
2. Read the Sensor API status holding register and verify that the ADMIN_UNLOCK bit is set. If it is set, the Sensor API
Command Register is enabled and will process commands issued.
3. The Modbus client writes the new Reference Value in 32-bit Float format to the Smoke Reference Value register through
Write Multiple Register Command.
4. The device applies the new Reference.
5. Read the Sensor Smoke Reference Value to verify it stored correctly.
6. Write 0x0 to the Administrator Password in the Administrator Password holding register if no further changes are
desired.
User Guide: FAAST Fire Alarm Aspiration Sensing Technology® Modbus Protocol Schema 2
7
Rev B
Reading Logs
In order to read the device logs, the following steps must be followed.
Event Log Read
1. Write the Administrator Password in the Administrator Password holding register.
2. Read the Sensor API status holding register and verify that the ADMIN_UNLOCK bit is set.
3. Write the Event log index value into corresponding holding register using Write Single Holding Register Command
(0x06). The default shall be 1 which reads the latest 40 events.
4. Read Event Logs.
Examples:
a. Total no. of events = 50, Index = 2, then the Event log read command will read last 10 events.
b. Total no. of events = 80, Index = 2, then the Event log read command will read last 40 events.
c. Total no. of events <= 80, Index = 3, then the client shall show Device read failure because there are no events present
in the memory corresponding to given Index value.
Trend Log Read
1. Write the Administrator Password in the Administrator Password holding register.
2. Read the Sensor API status holding register and verify that the ADMIN_UNLOCK bit is set.
3. Write the Trend log index value into corresponding holding register using Write Single Holding Register Command
(0x06). The default shall be 1 which reads the latest one trend log.
4. Read the Trend Log.
Examples:
a. Total no. of trends = 50, Index = 2, then the Trend log read command will read recent but one trend log.
b. Total no. of trends = 80, Index = 80, then the Trend log read command will read last trend log.
c. Total no. of trends = 30, Index >30, then the client shall show Device read failure because there are no trends present
in the memory corresponding to given Index value.
Message Log Read
1. Write the Administrator Password in the Administrator Password holding register.
2. Read the Sensor API status holding register and verify that the ADMIN_UNLOCK bit is set.
3. Write the Message log index value into corresponding holding register using Write Single Holding Register Command
(0x06). The default shall be 1 which reads the latest one message log.
4. Read the Message Log.
Examples:
a. Total no. of messages = 50, Index = 2, then the Message log read command will read recent but one message log.
b. Total no. of messages = 20, Index = 20, then the Message log read command will read last message log.
c. Total no. of messages = 30, Index >30, then the client shall show Device read failure because there are no messages
present in the memory corresponding to given Index value.
User Guide: FAAST Fire Alarm Aspiration Sensing Technology® Modbus Protocol Schema 2
8
Modbus Conguration
The device’s Modbus Configuration Structure is READ/WRITE and mapped directly to a set of holding registers. The structure in the
Firmware is defined as follows:
Address Size
(16-bit
words)
Parameter Name Type Description
40326 1 Administrator Password U16 Password to enable Commands through the Command
holding register.
Enter as an Unsigned Decimal number.
327 1 Sensor Command Register U16 Command Register:
0xAA11 – Save Configuration
0xEE22 – Save Time
328 1 Event Log Index U16 Starting Index of Event Log Entry which to read
329 1 Trend Log Index U16 Starting Index of Trend Log to read
330 1 Message Log Index U16 Starting Index of Message Log to read
Table 1. Modbus Specific configuration Holding Registers
Information - Registers 326-330 can be configured by using Function code 6(single write) or Function 16 (multiple write).
Input Registers
The Modbus Holding Register addresses are indexed for a Honeywell Building Solutions Enterprise Building Integrator
TM
client. Other
clients may need to subtract 1 from each address in order to access the desired register.
Address Size
(16-bit
words)
Parameter Name Type Description
30001 1 Schema U16 Modbus Firmware Schema for client to determine version of
register mapping.
Table 2. Modbus Input Registers
User Guide: FAAST Fire Alarm Aspiration Sensing Technology® Modbus Protocol Schema 2
9
Rev B
Holding Registers
Note: The Modbus Holding Register addresses are indexed for a Honeywell Building Solutions Enterprise Building Integrator
TM
client.
Other clients may need to subtract 1 from each address in order to access the desired register.
Device Status
The device’s Device Status Structure is READ ONLY and mapped directly to a set of holding registers. The structure in the Firmware
is defined as follows:
Address Size
(16-bit
words)
Parameter Name Type Description
40001-2 2 Universal Time Stamp U32 Read Only - Universal Time Stamp corresponding to the
real-time clock value in UNIX seconds epoch format
3 1 Startup Flags U16 Startup flags
For internal use only.
4 1 System Faults U16 System Faults.
Bit 0: Low Voltage
Bit 1: Low Flow
Bit 2: Configuration
Bit 3: Sensor
Bit 4: External Monitor
Bit 5: Time
Bit 6: Communication
Bit 7: Aspirator
Bit 8: Filter
Bit 9: Isolation
Bit 10: High Flow
Bits 11-15 unused
5 1 Minor Faults U16 Minor Faults.
Bit 0: Low Flow
Bit 1: Configuration
Bit 2: External Monitor Open
Bit 3: External Monitor Short
Bit 4: Time
Bit 5: Filter
Bit 6: High Flow
Bits 7-15 unused
6 1 Urgent Faults U16 Urgent Faults.
Bit 0: Low Flow
Bit 1: Configuration
Bit 2: Communication
Bit 3: Sensor
Bit 4: Aspirator
Bit 5: Filter
Bit 6: High Flow
Bit 7: Low Voltage
Bits 8-15 unused
7 1 Operating Mode U16 Device Operating Mode Enumeration:
CONFIGURATION_MODE 0,
INITIALIZATION_MODE 1,
TEST_MODE 2,
NORMAL_MODE 3,
DISABLE_MODE 4,
RESET_MODE 5,
FACTORY_MODE 6,
SERVICE_MODE 7,
ISOLATE_NEW_MODE 8,
RESET_NETWORK_MODE 9
User Guide: FAAST Fire Alarm Aspiration Sensing Technology® Modbus Protocol Schema 2
10
Holding Registers (Contd)
Device Status
Address Size
(16-bit
words)
Parameter Name Type Description
8 ½ Relay Status U8 Relay Status.
Bit 0: Alert
Bit 1: Action1
Bit 2: Action2
Bit 3: Fire1
Bit 4: Fire2
Bit 5: Minor (if equipped)
Bit 6: Urgent/Fault
Bit7: Isolate (if equipped)
Bits 8-15 unused
9 1 Internal Error Flags – HW Comm U16 Internal Comm Error.
For internal use only.
10 1 Internal Error Flags – HW U16 Internal HW Error.
For internal use only.
11 1 Internal Error Flags – SW U16 Internal SW Error.
For internal use only.
12 1 Fan Speed in RPMs U16 Speed of fan in RPMs
13 ½ Alarm Level U8 Alarm Status.
Bit 0: Alert
Bit 1: Action1
Bit 2: Action2
Bit 3: Fire1
Bit 4: Fire2
Bits 5-15 unused.
14 1 Lifetime Count in Days U16 Days of operation during lifetime
15 ½ Filter Cover State U8 Filter Cover State.
Not zero = open
0 = closed
16 1 Factory Configuration Status U16 Factory Configuration State.
CONFIG_STATE_PRIMARY 0,
CONFIG_STATE_BACKUP 1,
CONFIG_STATE_UNCONFIGURED 2
17 1 Device Configuration Status U16 Device Configuration State.
See Factory Configuration State.
18 1 Network Configuration Status U16 Network Configuration State.
See Factory Configuration State.
19-30 12 Password Recovery Code U16 Code for recovering the device PipeIQ password.
Uses the format to store a string.
Table 3. Device Status Modbus Holding Registers
User Guide: FAAST Fire Alarm Aspiration Sensing Technology® Modbus Protocol Schema 2
11
Rev B
Sensor Status
The device’s Sensor Status Structure is READ ONLY with the exception of the Smoke Reference Value and mapped directly to a set
of holding registers. The structure in the Firmware is defined as follows:
Address Size
(16-bit
words)
Parameter Name Type Description
40031-32 2 System Time U32 Device Time in UNIX seconds epoch format, use Universal
Time Stamp instead.
33-34 2 Smoke Reference Value F32 Smoke reference value used to increase noise floor of
detector.
US Standard Units Max: 0.10 (%/ft)
Metric Units Max: 0.328 (%/m)
35 1 Sensor Action Inputs U16 All bits are self-clearing and will read ‘0’ after bit has been
read and processed
Bit 0: 1 Isolate – Toggles Isolate Mode
Bit1: 1 Disable – Toggles Disable Mode
Bit2: 1 Test – Place the device in Test Mode
Bit3: 1 Silence Sounder (if enabled / equipped)
Note: Sounder Silence is effective for a single alarm or fault
occurrence. If an alarm recurs, another alarm is initiated or
another fault occurs, the sounder will re-energize.
Bit4: Reset Device
Bit5: Reset Airflow Baselines
Current baseline cleared, and device will set a new
baseline. New baseline established within 15 minutes.
Bit6: Clear Event Log Note: Allow this action up to 10
seconds to complete. Erases all Event Log entries
Bit7: Clear Trend Log Note: Allow this action up to 5
seconds to complete. Erases all Trend Log entries
Bit8: Clear Message Log Note: Allow this action up to 5
seconds to complete. Erases all Message Log entries
Bit9-15: Unused
36 ½ Ch 1 Air Temperature S8 Real-time sampled air temperature in Channel 1
37 ½ Ch 1 Air Velocity Change S8 Percentage change from baseline air velocity in Channel 1
38-39 2 Ch 1 Air Velocity Baseline F32 Average velocity during baselining in Channel 1
40-41 2 Ch 1 Air Velocity Daily Min F32 Daily minimum air velocity realized on Channel 1
42-43 2 Ch 1 Air Velocity Daily Max F32 Daily maximum air velocity realized on Channel 1
44 ½ Ch 2 Air Temperature S8 Real-time sampled air temperature in Channel 2
(multichannel device only)
45 ½ Ch 2 Air Velocity Change S8 Percentage change from baseline air velocity in Channel 2
(multichannel device only)
46-47 2 Ch 2 Air Velocity Baseline F32 Average velocity during baselining in Channel 2
(multichannel device only)
48-49 2 Ch 2 Air Velocity Daily Min F32 Daily minimum air velocity realized on Channel 2
(multichannel device only)
50-51 2 Ch 2 Air Velocity Daily Max F32 Daily maximum air velocity realized on Channel 2
(multichannel device only)
User Guide: FAAST Fire Alarm Aspiration Sensing Technology® Modbus Protocol Schema 2
12
Sensor Status (Cont’d)
Address Size
(16-bit
words)
Parameter Name Type Description
52 ½ Ch 3 Air Temperature S8 Real-time sampled air temperature in Channel 3
(multichannel device only)
53 ½ Ch 3 Air Velocity Change S8 Percentage change from baseline air velocity in Channel 3
(multichannel device only)
54-55 2 Ch 3 Air Velocity Baseline F32 Average velocity during baselining in Channel 3
(multichannel device only)
56-57 2 Ch 3 Air Velocity Daily Min F32 Daily minimum air velocity realized on Channel 3
(multichannel device only)
58-59 2 Ch 3 Air Velocity Daily Max F32 Daily maximum air velocity realized on Channel 3
(multichannel device only)
60 ½ Ch 4 Air Temperature S8 Real-time sampled air temperature in Channel 4
(multichannel device only)
61 ½ Ch 4 Air Velocity Change S8 Percentage change from baseline air velocity in Channel 4
(multichannel device only)
62-63 2 Ch 4 Air Velocity Baseline F32 Average velocity during baselining in Channel 4
(multichannel device only)
64-65 2 Ch 4 Air Velocity Daily Min F32 Daily minimum air velocity realized on Channel 4
(multichannel device only)
66-67 2 Ch 4 Air Velocity Daily Max F32 Daily maximum air velocity realized on Channel 4
(multichannel device only)
68 ½ Smoke Particulate Display U8 Front panel particulate level (0-10)
69-70 2 Smoke Current Obs F32 Current Obscuration Level the Smoke Sensor is Detecting
71-72 2 Smoke Daily Max Obs F32 Maximum Obscuration Level the Smoke Sensor Detected
since 12am
73-74 2 Smoke Daily Min Obs F32 Minimum Obscuration Level the Smoke Sensor Detected
since 12am
75-76 2 Alert Threshold F32 Current Active Alert Threshold ( %/ft if US Standard or %/m
if metric)
77-78 2 Action1 Threshold F32 Current Active Action1 Threshold ( %/ft if US Standard or
%/m if metric)
79-80 2 Action2 Threshold F32 Current Active Action2 Threshold ( %/ft if US Standard or
%/m if metric)
81-82 2 Fire1 Threshold F32 Current Active Fire1 Threshold ( %/ft if US Standard or %/m
if metric)
83-84 2 Fire2 Threshold F32 Current Active Fire2 Threshold ( %/ft if US Standard or %/m
if metric)
85 1 Sensor Status U16 Bit 0 – Admin Unlock
1 = Unlocked, 0 = Locked
Bit 1 –Baselining
1 = set (configured from sensor action inputs)
Table 4. Sensor Status Modbus Holding Registers
Information - Registers 35 can be configured by using Function code 6(single write) or Function 16 (multiple write).
Warning!! Device threshold configuration variables should be set by the user to values scaled based on the Units configuration
setting. The detector will interpret the value differently for different Units settings. E.g. The device will interpret a 0.01 threshold
setting as 0.01 %/ft when Units setting is US Standard. The device will interpret a 0.01 threshold setting as 0.01 %/m when Units
setting is Metric.
User Guide: FAAST Fire Alarm Aspiration Sensing Technology® Modbus Protocol Schema 2
13
Rev B
Device Logs
The device’s Log Structure is READ ONLY and mapped directly to a set of holding registers. The structure in the Firmware is defined
as follows:
Address Size
(16-bit
words)
Parameter Name Type Description
40086 1 Event Log Entries U16 Number of Event Log Entries
87 1 Trend Log Entries U16 Number of Trend Log Entries
88 1 Message Log Entries U16 Number of Message Log Entries
89-208 3 x 40 Read Event Log U32
U16
Reads 40 log entries starting with the entry in the Index register.
Each entry contains a 32-bit Epoch time stamp and 16-bit Event number
The events numbers represent the following events:
Test 0
Normal 1
Isolate 2
POR 3
Reset 4
UI Passcode Entry Failure 5
UI Passcode Entry Success 6
UI Button Autolock 7
Filter Cover Open 8
Filter Cover Closed 9
Configuration Change Success 10
User Login 11
User Logout 12
Flow Fault High 13
Flow Fault Low 14
Configuration Fault 15
Configuration Fault Urgent 16
Sensor Fault 17
External Device Fault 18
External Device Fault Clear 19
Communication Fault 20
Aspiration Fault 21
Aspiration Fault Urgent 22
Filter Fault 23
Filter Fault Urgent 24
Time Fault 25
Low Voltage Fault 26
Low Voltage Fault Clear 27
Alarm Alert 28
Alarm Action1 29
Alarm Action2 30
Alarm Fire1 31
Alarm Fire2 32
Operating Mode Disable 33
209-232 24 Read Trend Log U32
F32 [11]
Reads log entry specified by the Index register.
Each entry contains a 32-bit time stamp and daily air velocity and smoke
detection logs including:
Float : Daily Alert Threshold
Float : Daily Action1 Threshold
Float : Daily Action2 Threshold
Float : Daily Fire1 Threshold
Float : Daily Fire2 Threshold
Float : Trend Max
Float : Trend Min
Float : Trend Avg
Float : Air Velocity Max
Float : Air Velocity Min
Float : Air Velocity Avg
233-298 66 Message Log U32
U16 [64]
Reads the log entry specified by the Index register.
Each entry contains a 32-bit time stamp and a UTF-16 64 character string.
Table 5. Device Log Modbus Holding Registers
User Guide: FAAST Fire Alarm Aspiration Sensing Technology® Modbus Protocol Schema 2
14
Factory Conguration
Address Size
(16-bit
words)
Parameter Name Type Description
40299 ½ SLC Interface Present bool Designates the presence of an SLC interface
(ie Eclipse, Flashscan, etc)
300 1 SLC_PROTOCOL_TYPE U16 Defines the supported SLC protocol.
CONVENTIONAL 0
CLIP 1
FLASHSCAN 2
ECLIPSE 3
ADVANCED 4
PROTOCOL_OTHER 5
301 1 OEMID_TYPE U16 Defines Device OEM.
For internal use only.
302-304 3 MAC Addr U8[6] Device’s MAC Address
Stored in the format described for MAC address storage.
305 ½ Sensor Type U8 Smoke 1
306 ½ Firmware Main Board Rev U8 Main Board Microcontroller Firmware Image Revision
307 ½ Firmware Photo 1 Rev U8 Chamber Microcontroller Firmware Image Revision
308 ½ Firmware Photo 2 Rev U8 Not used, set to zero
309 ½ Hardware Main Board Rev U8 Revision of Main Board Hardware
310 ½ Hardware Photo1 Rev U8 Revision of Photodetector Hardware
311 ½ Hardware Photo 2 Rev U8 Not used, set to zero
312 ½ Hardware Blue Rev U8 Revision of Blue LED Driver Hardware
313 ½ Hardware Laser Rev U8 Revision of Laser Driver Hardware
314 ½ Hardware UI Rev U8 Revision of User Interface Hardware
315 ½ Hardware Ultrasonics Rev U8 Revision of Ultrasonics Board Hardware
316 ½ Hardware SLC Rev U8 Revision of SLC Interface Hardware
317 ½ Photo Cal1 U8 For internal use only.
318 ½ Photo Cal2 U8 For internal use only.
319 ½ Photo Cal3 U8 For internal use only.
320 1 Blue Cal U16 For internal use only.
321 1 IR Cal U16 For internal use only.
322 ½ Airflow Boundary U8 For internal use only.
323 ½ Airflow Timer U8 For internal use only.
324-325 2 Mfg Time Stamp U32 Manufacturing Time Stamp –
UNIX seconds since epoch format
Table 6. Factory Configuration Modbus Holding Registers
User Guide: FAAST Fire Alarm Aspiration Sensing Technology® Modbus Protocol Schema 2
15
Rev B
Device Conguration
Address Size
(16-bit
words)
Parameter Name Type Description
40331 1 Device Config Counter U16 Configuration Counter
332-333 2 Config Timestamp U32 Time of last configuration
334 1 Units U16 Units of Measure for Alarm Threshold Obscuration Values
Metric 0
US Standard 1
335 ½ Relays Latching U8 Set latching behavior of minor fault and alarms.
Non-latching 0
Latching 1
Bit 0: Alert
Bit1: Action1
Bit2: Action2
Bit3: Fire1
Bit4: Fire2
Bit5: Minor
336 ½ Alert Delay U8 Alert Alarm Delay in Seconds
337 ½ Action1 Delay U8 Action1 Alarm Delay in Seconds
338 ½ Action2 Delay U8 Action2 Alarm Delay in Seconds
339 ½ Fire1 Delay U8 Fire1 Alarm Delay in Seconds
340 ½ Fire2 Delay U8 Fire2 Alarm Delay in Seconds
341 ½ Acclimate Enable U8 Enable Acclimate Mode (use Acclimate Alarm Thresholds)
Disable 0
Enable Not Zero
342-343 2 Day Time Start U32 Epoch Local Time Stamp to mark the time in which to use
the day alarm thresholds.
344-345 2 Night Time Start U32 Epoch Local Time Stamp to mark the time in which to use
the night alarm thresholds.
346-347 2 Alert Day Threshold F32 Alert Alarm Day Obscuration Threshold
348-349 2 Alert Night Threshold F32 Alert Alarm Night Obscuration Threshold
350-351 2 Alert Weekend Threshold F32 Alert Alarm Weekend Obscuration Threshold
352-353 2 Action1 Day Threshold F32 Action1 Alarm Day Obscuration Threshold
354-355 2 Action1 Night Threshold F32 Action1 Alarm Night Obscuration Threshold
356-357 2 Action1 Weekend Threshold F32 Action1 Alarm Weekend Obscuration Threshold
358-359 2 Action2 Day Threshold F32 Action2 Alarm Day Obscuration Threshold
360-361 2 Action2 Night Threshold F32 Action2 Alarm Night Obscuration Threshold
362-363 2 Action2 Weekend Threshold F32 Action2 Alarm Weekend Obscuration Threshold
364-365 2 Fire1 Day Threshold F32 Fire1 Alarm Day Obscuration Threshold
366-367 2 Fire1 Night Threshold F32 Fire1 Alarm Night Obscuration Threshold
368-369 2 Fire1 Weekend Threshold F32 Fire1 Alarm Weekend Obscuration Threshold
370-371 2 Fire2 Day Threshold F32 Fire2 Alarm Day Obscuration Threshold
User Guide: FAAST Fire Alarm Aspiration Sensing Technology® Modbus Protocol Schema 2
16
Device Conguration (Contd)
Address Size
(16-bit
words)
Parameter Name Type Description
372-373 2 Fire2 Night Threshold F32 Fire2 Alarm Night Obscuration Threshold
374-375 2 Fire2 Weekend Threshold F32 Fire2 Alarm Weekend Obscuration Threshold
376-377 2 Alert Acclimate Threshold Max F32 Maximum Alert Alarm Threshold when operating in
Acclimate
®
Mode
378-379 2 Alert Acclimate Threshold Min F32 Minimum Alert Alarm Threshold when operating in
Acclimate Mode
380-381 2 Action1 Acclimate Threshold Max F32 Maximum Action1 Alarm Threshold when operating in
Acclimate Mode
382-383 2 Action1 Acclimate Threshold Min F32 Minimum Action1 Alarm Threshold when operating in
Acclimate Mode
384-385 2 Action2 Acclimate Threshold Max F32 Maximum Action2 Alarm Threshold when operating in
Acclimate Mode
386-387 2 Action2 Acclimate Threshold Min F32 Minimum Action2 Alarm Threshold when operating in
Acclimate Mode
388-389 2 Fire1 Acclimate Threshold Max F32 Maximum Fire1 Alarm Threshold when operating in
Acclimate Mode
390-391 2 Fire1 Acclimate Threshold Min F32 Minimum Fire1 Alarm Threshold when operating in
Acclimate Mode
392-393 2 Fire2 Acclimate Threshold Max F32 Maximum Fire2 Alarm Threshold when operating in
Acclimate Mode
394-395 2 Fire2 Acclimate Threshold Min F32 Minimum Fire2 Alarm Threshold when operating in
Acclimate Mode
396 ½ ID Number U8 Can be used for the SLC address or an identification
number on a loop
Flashscan 1-Address: 1-159
Flashscan 5-Address: 1-155
CLIP: 1-99
397-428 32 Contact U8[64] UTF-16 Contact Name string buffer
431-460 32 Facility U8[64] UTF-16 Facility Name string buffer
461-492 32 Facility Location U8[64] UTF-16 Facility Location string buffer
493-524 32 Device Location U8[64] UTF-16 Device Location string buffer
525-527 3 Button Lock U8[3] User Interface Lockout
Unlocked 0
Locked 1
Bit 0: Isolate
Bit 1: Reset/Mode
Bit 2: Test
528-529 2 Passcode U32 Passcode for unlocking the buttons from the front panel.
Unsigned Long Value: 1111-9999
Table 7. Device Configuration Modbus Holding Registers
Warning!! Device threshold configuration variables should be set by the user to values scaled based on the Units configuration
setting. The detector will interpret the value differently for different Units settings. E.g. The device will interpret a 0.01 threshold
setting as 0.01 %/ft when Units setting is US Standard. The device will interpret a 0.01 threshold setting as 0.01 %/m when Units
setting is Metric.
User Guide: FAAST Fire Alarm Aspiration Sensing Technology® Modbus Protocol Schema 2
17
Rev B
Network Conguration
Address Size
(16-bit
words)
Parameter Name Type Description
40530 1 Network Config Counter U16 Configuration Counter
531-546 16 Password U8
[32]
547-570 24 E-mail Sender U8
[48]
UTF-8 E-mail sender account name string buffer
571-594 24 E-mail Server U8
[48]
UTF-8 E-mail outgoing SMTP server name string buffer
595-618 24 E-mail Recipient #1 U8
48]
UTF-8 E-mail address of recipient #1
619 ½ E-mail Recipient #1 Notifications U8 Enables for notifications based on type of event. See
NET_CONFIG_STR for bit definitions
620-643 24 E-mail Recipient #2 U8
[48]
UTF-8 E-mail address of recipient #2
644 ½ E-mail Recipient #2 Notifications U8 Enables for notifications based on type of event
645-668 24 E-mail Recipient #3 U8
[48]
UTF-8 E-mail address of recipient #3
669 ½ E-mail Recipient #3 Notifications U8 Enables for notifications based on type of event
670-693 24 E-mail Recipient #4 U8
[48]
UTF-8 E-mail address of recipient #4
694 ½ E-mail Recipient #4 Notifications U8 Enables for notifications based on type of event
695-718 24 E-mail Recipient #5 U8
[48]
UTF-8 E-mail address of recipient #5
719 ½ E-mail Recipient #5 Notifications U8 Enables for notifications based on type of event
720-743 24 E-mail Recipient #6 U8
[48]
UTF-8 E-mail address of recipient #6
744 ½ E-mail Recipient #6 Notifications U8 Enables for notifications based on type of event
745 ½ Static IP Enable U8 Enable/Disable for Static IP. Disabled state enables
DHCP-based IP address assignment. 0 =Disabled,
Not zero = Enabled
746-747 2 Static IP Address U8
[4]
Static IP Address
748-749 2 Static IP Subnet U8[
4]
Static IP Subnet Mask
750-751 2 Static IP Gateway U8
[4]
Static IP Gateway
752-753 2 Static IP Pref DNS U8
[4]
Static IP Preferred DNS Address
754-755 2 Static IP Alt DNS U8
[4]
Static IP Alternate DNS Address
Table 8. Network Configuration Modbus Holding Registers
User Guide: FAAST Fire Alarm Aspiration Sensing Technology® Modbus Protocol Schema 2
18
Appendix A. Congurable options on FAAST
A.1. Alarm Conguration Variables
Name Description Range Default Value Units
AlertThresholdDay The sensitivity where the Alert Alarm will occur during the daytime. 0.00046 – 6.25
0.0015 – 20.5
0.012
0.0396
%/ft %/m
Action1ThresholdDay The sensitivity where the Action1 Alarm will occur during the
daytime.
0.00046 – 6.25
0.0015 – 20.5
0.05
0.165
%/ft %/m
Action2ThresholdDay The sensitivity where the Action2 Alarm will occur during the
daytime.
0.00046 – 6.25
0.0015 – 20.5
0.1
0.33
%/ft %/m
Fire1ThresholdDay The sensitivity where the Fire1 Alarm will occur during the daytime. 0.00046 – 6.25
0.0015 – 20.5
0.25
0.825
%/ft %/m
Fire2ThrehsoldDay The sensitivity where the Fire2 Alarm will occur during the daytime. 0.00046 – 6.25
0.0015 – 20.5
0.5
1.65
%/ft %/m
AlertThresholdNight The sensitivity where the Alert Alarm will occur during the nighttime. 0.00046 – 6.25
0.0015 – 20.5
0.012
0.0396
%/ft %/m
Action1ThresholdNight The sensitivity where the Action1 Alarm will occur during the
nighttime.
0.00046 – 6.25
0.0015 – 20.5
0.05
0.165
%/ft %/m
Action2ThresholdNight The sensitivity where the Action2 Alarm will occur during the
nighttime.
0.00046 – 6.25
0.0015 – 20.5
0.1
0.33
%/ft %/m
Fire1ThresholdNight The sensitivity where the Fire1 Alarm will occur during the
nighttime.
0.00046 – 6.25
0.0015 – 20.5
0.25
0.825
%/ft %/m
Fire2ThrehsoldNight The sensitivity where the Fire2 Alarm will occur during the
nighttime.
0.00046 – 6.25
0.0015 – 20.5
0.5
1.65
%/ft %/m
NightTimeEnter Time at which to switch to nighttime thresholds. 10:00pm Time
NightTimeExit Time at which to switch to daytime thresholds. 5:00am Time
AlertHigh Sensitive limit for Alert when acclimate mode is active 0.00046 – 6.25
0.0015 – 20.5
0.00138
0.00455
%/ft %/m
Action1High Sensitive limit for Action1 when acclimate mode is active 0.00046 – 6.25
0.0015 – 20.5
0.0028
0.00924
%/ft %/m
Action2High Sensitive limit for Action2 when acclimate mode is active 0.00046 – 6.25
0.0015 – 20.5
0.0075
0.02475
%/ft %/m
Fire1High Sensitive limit for Fire1 when acclimate mode is active 0.00046 – 6.25
0.0015 – 20.5
0.01
0.033
%/ft %/m
Fire2High Sensitive limit for Fire2 when acclimate mode is active 0.00046 – 6.25
0.0015 – 20.5
0.1
0.33
%/ft %/m
AlertLow Insensitive limit for Alert when acclimate mode is active 0.00046 – 6.25
0.0015 – 20.5
0.012
0.0396
%/ft %/m
Action1Low Insensitive limit for Action1 when acclimate mode is active 0.00046 – 6.25
0.0015 – 20.5
0.05
.165
%/ft %/m
Action2Low Insensitive limit for Action2 when acclimate mode is active 0.00046 – 6.25
0.0015 – 20.5
0.1
0.33
%/ft %/m
Fire1Low Insensitive limit for Fire1 when acclimate mode is active 0.00046 – 6.25
0.0015 – 20.5
0.25
0.825
%/ft %/m
Fire2Low Insensitive limit for Fire2 when acclimate mode is active 0.00046 – 6.25
0.0015 – 20.5
0.5
1.65
%/ft %/m
AcclimateAlertLevel Current Sensitivity for Alert Alarm when in acclimate mode. AlertHigh –
AlertLow
AlertLow %/ft %/m
AcclimateAction1Level Current Sensitivity for Action1 Alarm when in acclimate mode. Action1High –
Action1Low
Action1Low %/ft %/m
AcclimateAction2Level Current Sensitivity for Action2 Alarm when in acclimate mode. Action2High –
Action2Low
Action2Low %/f %/m
AcclimateFire1Level Current Sensitivity for Fire1 Alarm when in acclimate mode. Fire1High –
Fire1Low
Fire1Low %/ft %/m
AcclimateFire2Level Current Sensitivity for Fire2 Alarm when in acclimate mode. Fire2High –
Fire2Low
Fire2Low %/ft %/m
Table 9. Alarm Configuration Variable Ranges
User Guide: FAAST Fire Alarm Aspiration Sensing Technology® Modbus Protocol Schema 2
19
Rev B
A.2. Device Conguration Variables
Name Description Range Default Value
Acclimate Mode Enable Set to activate acclimate mode operation Enable / Disable Disabled
Alert Alarm Latch Set to latch Alert alarm. Requires a RESET to clear
alarm. This setting is only valid for conventional
product.
Latching/Non-Latching Latching
Action1 Alarm Latch Set to latch Action1 alarm. Requires a RESET to
clear alarm. This setting is only valid for conventional
product.
Latching/Non-Latching Latching
Action2 Alarm Latch Set to latch Action2 alarm. Requires a RESET to
clear alarm. This setting is only valid for conventional
product.
Latching/Non-Latching Latching
Fire1 Alarm Latch Set to latch Fire1 alarm. Requires a RESET to clear
alarm. This setting is only valid for conventional
product.
Latching/Non-Latching Latching
Fire2 Alarm Latch Set to latch Fire2 alarm. Requires a RESET to clear
alarm. This setting is only valid for conventional
product.
Latching/Non-Latching Latching
Alert Delay Programmable delay before activating Alert Alarm.
This setting is only valid for conventional product.
0 - 60 seconds 0
Action1 Delay Programmable delay before activating Action1
Alarm. This setting is only valid for conventional
product.
0 - 60 seconds 0
Action2 Delay Programmable delay before activating Action2
Alarm. This setting is only valid for conventional
product.
0 - 60 seconds 0
Fire1 Delay Programmable delay before activating Fire1 Alarm.
This setting is only valid for conventional product.
0 - 60 seconds 0
Fire2 Delay Programmable delay before activating Fire2 Alarm.
This setting is only valid for conventional product.
0 - 60 seconds 0
PassCodeButtonLockout Allows lockout feature of buttons. 0000 - 9999 1111
TEST Lockout Setting for locking and unlocking of TEST button.
This setting is only valid for conventional product.
Locked / Unlocked For the lock
function to work the passcode
must be any value other than
0000
Locked
RESET Lockout Setting for locking and unlocking of RESET button.
This setting is only valid for conventional product.
Locked
DISABLE Lockout Setting for locking and unlocking of DISABLE button.
This setting is only valid for conventional product.
Locked
IP Address IP address of the device 192.168.1.10
Subnet Mask 255.255.255.0
Gateway 192.168.1.1
Address Device local address range
CLIP enabled product
Flashscan enabled product
Eclipse enabled product
1-247
1-99
1-159
1-255
1
Time Real time clock time in hours/minutes/seconds Midnight
Date Real time clock date Current date
Year Real time clock year Current year
Log Setting Configures the method of Event logging for either
FIFO (first in first out) or LIFO (last in first out) setting
FIFO / LIFO FIFO
Password User Password for Web Access User entry Monitor
Table 10. Device Configuration Variable Ranges.
User Guide: FAAST Fire Alarm Aspiration Sensing Technology® Modbus Protocol Schema 1
Technical Support
System Sensor strives to provide our customers with outstanding support for the FAAST Fire Alarm Aspiration Sensing Technology
®
and all our products. For more information, contact us using one of the methods below:
Web: E-mail: Phone:
systemsensor.com/faast systemsensor.com/contact 800.736.7672 (press 2) Mon-Fri, 7:30 a.m. – 5:00 p.m. CST
©2014 System Sensor. ASUG27802 • 10/14
User Guide: FAAST Fire Alarm Aspiration Sensing Technology
®
with Modbus
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20

System Sensor FAAST Modbus Schema 2 User guide

Category
Fire protection
Type
User guide

System Sensor FAAST Modbus Schema 2 is an advanced particulate matter detection system with early warning and very early warning fire detection capabilities. It can monitor and detect particulate levels, airflow, and faults remotely. You can also use it to modify device settings and configurations, and read logs and events. Here are some of its key features:

  • Early warning and very early warning fire detection: System Sensor FAAST Modbus Schema 2 uses aspirating smoke detection technology to detect smoke particulates in the air. This allows it to detect fires at a very early stage, providing you with valuable time to respond.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI