User Guide: FAAST Fire Alarm Aspiration Sensing Technology® Modbus Protocol Schema 2
19
Rev B
A.2. Device Conguration Variables
Name Description Range Default Value
Acclimate Mode Enable Set to activate acclimate mode operation Enable / Disable Disabled
Alert Alarm Latch Set to latch Alert alarm. Requires a RESET to clear
alarm. This setting is only valid for conventional
product.
Latching/Non-Latching Latching
Action1 Alarm Latch Set to latch Action1 alarm. Requires a RESET to
clear alarm. This setting is only valid for conventional
product.
Latching/Non-Latching Latching
Action2 Alarm Latch Set to latch Action2 alarm. Requires a RESET to
clear alarm. This setting is only valid for conventional
product.
Latching/Non-Latching Latching
Fire1 Alarm Latch Set to latch Fire1 alarm. Requires a RESET to clear
alarm. This setting is only valid for conventional
product.
Latching/Non-Latching Latching
Fire2 Alarm Latch Set to latch Fire2 alarm. Requires a RESET to clear
alarm. This setting is only valid for conventional
product.
Latching/Non-Latching Latching
Alert Delay Programmable delay before activating Alert Alarm.
This setting is only valid for conventional product.
0 - 60 seconds 0
Action1 Delay Programmable delay before activating Action1
Alarm. This setting is only valid for conventional
product.
0 - 60 seconds 0
Action2 Delay Programmable delay before activating Action2
Alarm. This setting is only valid for conventional
product.
0 - 60 seconds 0
Fire1 Delay Programmable delay before activating Fire1 Alarm.
This setting is only valid for conventional product.
0 - 60 seconds 0
Fire2 Delay Programmable delay before activating Fire2 Alarm.
This setting is only valid for conventional product.
0 - 60 seconds 0
PassCodeButtonLockout Allows lockout feature of buttons. 0000 - 9999 1111
TEST Lockout Setting for locking and unlocking of TEST button.
This setting is only valid for conventional product.
Locked / Unlocked For the lock
function to work the passcode
must be any value other than
0000
Locked
RESET Lockout Setting for locking and unlocking of RESET button.
This setting is only valid for conventional product.
Locked
DISABLE Lockout Setting for locking and unlocking of DISABLE button.
This setting is only valid for conventional product.
Locked
IP Address IP address of the device 192.168.1.10
Subnet Mask 255.255.255.0
Gateway 192.168.1.1
Address Device local address range
CLIP enabled product
Flashscan enabled product
Eclipse enabled product
1-247
1-99
1-159
1-255
1
Time Real time clock time in hours/minutes/seconds Midnight
Date Real time clock date Current date
Year Real time clock year Current year
Log Setting Configures the method of Event logging for either
FIFO (first in first out) or LIFO (last in first out) setting
FIFO / LIFO FIFO
Password User Password for Web Access User entry Monitor
Table 10. Device Configuration Variable Ranges.