Lennox V8DRNP-04 (12A57) Water Pump Kit Installation guide

Type
Installation guide
Page 1
OPTIONAL WATER PUMP KIT V8DRNP-04 (12A57) USED WITH LENNOX VRF INDOOR UNITS
Litho U.S.A
.
507516-01
11/2014 Water Pump Kit
VRF KITS & ACCESSORIES
©2014 Lennox Industries Inc.
Dallas, Texas, USA
WARNING
As with any mechanical equipment, personal injury can
result from contact with sharp metal edges. Be careful
when handling equipment.
Shipping & Packing List
Package 1 of 1 contains the following:
1 - Assembled drain pump
1 - Flexible drain hose
3 - Screws
Application
Optional water pump V8DRNP-04 (12A57) is used with
Lennox VRF indoor units to provide vertical lift to ensure
proper condensate draining. Refer to product specifica
tions bulletin for unit usage.
Installation
1 - Install the indoor unit per the installation instructions
provided in the unit.
2 - Use the provided screws to secure the water pump
to the outside of the cabinet. Make sure that screws
are tightly fastened. See figures 1 and 2.
3 - Use hose clamps to connect the provided flexible
hose to the pump inlet and the main condensate
drain connection on the indoor unit. See figure 2.
NOTE - All joints must be leak-free as these will all
be installed above finished spaces.
4 - Connect the water pump power wiring plug and wa
ter level sensor plug to the appropriate jacks on the
unit control. Refer to the specific unit wiring diagram
on the indoor unit. Connect the green ground wire to
an earth ground. See figures 1 and 3 and wiring dia
gram on unit.
5 - Install field-provided 1-inch drain pipe at pump outlet.
Again, connection to pump must be leak-free to
avoid damage to finished spaces in the building. See
figure 4.
Take care to apply the following rules when installing
the drain line:
● The drain must include a U-shaped backflow pre
venter as shown in figure 4.
● The drain line must maintain a constant slope of ¼”
per foot to ensure proper drainage. See figure 4.
● The drain line and all connections must be insulat
ed to avoid condensation on the line. See figure 4.
● The drain line must be supported approximately
every 3 feet to prevent sagging. See figure 4.
There must be a 2-inch space between the end
of the condensate drain and the final termination
point (ground, open drain, etc.) to ensure that the
line will drain freely.
IMPORTANT !
Drain should have a slope of at least ¼ inch per foot
and should be fabricated using an approved corro
sion-resistant pipe.
6 - After system installation is complete, the con
densate drain line must be checked for leaks and
the condensate pump(s) must be checked to en
sure proper operation. This check is part of the
commissioning sequence. Funnel enough water to
engage the pump (if used) into the drain pan through
a flexible tube.
IMPORTANT !
You must confirm operation of every drain and
pump in the system as part of the commissioning
procedure.
PUMP HOUSING
FIGURE 1. Parts Arrangement
USE THREE PROVIDED
SCREWS TO SECURE
PUMP TO OUTSIDE OF
UNIT CABINET
PUMP TOP COVER
(Remove for installation)
PUMP OUTLET
PUMP INLET
PUMP INLET
PUMP OUTLET
(to drain)
PUMP
WATER LEVEL
SENSOR
FLEXIBLE
DRAIN HOSE
TO MAIN CONDENSATE
DRAIN ON INDOOR UNIT
Page 2
FIGURE 2. Pump Installation
SECURE PUMP
TO UNIT USING
PROVIDED
SCREWS
USE HOSE CLAMPS TO
SECURE PROVIDED HOSE TO
PUMP AND INDOOR UNIT
FIGURE 3. Pump Installation (Continued)
INDOOR UNIT
AUXILIARY
DRAIN
PUMP COVER
(Replace after
installation)
CONNECT PUMP POWER PLUG,
GROUND WIRE AND WATER LEVEL
SENSOR WIRE PER STEP 4.
PUMP OUTLET
(to drain)
FIGURE 4. Condensate Drain
≤ 6 in. ≤ 4 in. BACKFLOW
PREVENTER
WRAP DRAIN PIPE AND ALL
CONNECTIONS TO PRE
VENT CONDENSATION
SUPPORT
STRAPS
INSULATION
DOWNWARD SLOPE OF ¼
INCH PER FOOT
APPROXIMATELY
3 FEET
  • Page 1 1
  • Page 2 2

Lennox V8DRNP-04 (12A57) Water Pump Kit Installation guide

Type
Installation guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI