District heating substation for direct heating with
mixing loop for single-family, semi-detached and
terraced houses as well as flats. With one heating
circuit and with connection pipes for cylinder on
primary side. Designed for wall-mounting.
The heating temperature is controlled by an elec-
tronic temperature controller Danfoss ECL with
an outdoor temperature sensor.
The substation is supplied with mixing ciruit and
is thereby especially suitable for systems with
floor heating. The task of the mixing circuit is to
ensure a correct supply temperature for the heat-
ing circuit (to protect the heating circuit against
too high temperatures) and to ensure, that the
return water is cooled down to the required
temperature, before it flows back to the district
heating plant. The mixing circuit temperature is
controlled by an electronic temperature control-
ler Danfoss ECL.
Description
General PLEASE NOTE, that other variants may be supplied.
The control function, however, is basically as de-
scribed below, and the control of the substation
should be done in accordance with the enclosed pro-
ducer instructions for the mounted controller.
2-way valve + electrical actua-
tor.
The S-Solo is supplied with a 2-way valve VS 2,
which in combination with an electrical actuator
Danfoss AMV 150 controls the heating circuit. The
electrical actuator is preset from factory. In case of
operating disturbances the actuator can be closed
manually.
Please see enclosed instructions,
Electrical actuator AMV 150
2-way valve VS 2
Close actuator by turning the manual override
knob on top of actuator counterclockwise.
Manual override
Note: Press and hold the button on the bottom side of
the actuator during manual override.
7369267-9 SIBC R&D
EI.97.Q2.00 © Danfoss 12/01 1
INSTRUCTIONS
VS2 2-way
065R9075
065R9075
DN L (m m)
15 65
20 70
25 75
DN L
1
(mm)
15 131
20 142
25 159
DN L
2
(mm)
15 139
20 154
25 159
DN L
3
(mm)
15 69
20 74
25 79
Ins truc tion s
AMV 150
73691180 DH-SMT/SI
VI.KU.N2.1J
© Danfoss 01/2008
1
ENGLISH
Actuators for three point control AMV 150 www.danfoss.com Page 2
D A N SK
Motorer til 3-punkts styring AMV 150 www.danfoss.dk Side 3
DEUT SCH
Stellantriebe für 3-Pkt.- Eingangssignal AMV 150 www.danfoss.de Seite 3
SVENSKA
Motor för 3-punktsreglering AMV 150 varme.danfoss.se Sida 4
NEDERLANDS
Servomotor met 3-puntssturing AMV 150 www.danfoss.nl Pagina 4
LIETUVIŲ K.
Pavaros trijų padėčių valdymui AMV 150 www.danfoss.lt 5 puslapis
L A T V I SKI
Motori trīs punktu kontrolei AMV 150 www.danfoss.com Lpp. 5
MAGY A R
Szelepmozgatók hárompontos szabályozáshoz AMV 150 www.danfoss.com 6. oldal
ČESKY
Servopohony s tříbodovým regulačn ím signálem AMV 150 www.danfoss.cz Strana 6
POLSKI
Siłowniki sterowane sygnałem 3-punktow ym AMV 150 www.danfoss.pl Strona 7
Р У С С К И Й
Электроприводы для тре хпозиционного регулир ования AMV 150
www.danfoss.ru Страница 7
AMV 150 + AMV 150 + AMV 150 +
VS2 (DN 15) VMV AVQM (DN 15)
Heating circuit
Temperature control
The temperature for the heating circuit is con-
trolled by the Danfoss ECL controller. The supply
temperature is calculated by the controller on ba-
sis of the outdoor temperature.
The room temperature is controlled by radiator
thermostats. It is recommended that all radiators
are opened a little in each room.
The factory-setting of the controller ensures that
heating is automatically switched off in the sum-
mer period.
In periods with higher heat demand the controller
settings can be changed in accordance with the
enclosed producer instructions for the mounted
controller.
Please see enclosed user guide,
Installation & Maintenance
Danfoss ECL
DH-SMT/DK
VI.KT.F2.02
© Danfoss 06/2008
Instru ctions
ECL Comfort 1 1 0
Application 1 1 6
Constant temperature control
of domestic ho t-wa ter s ys te ms (D H W )
Us er g uide,
Instal lation & Main tenance
5
Produced by Danfoss Redan A/S · 01.2010
Instructions S-Solo