50kW RD05034JDAE

Generac 50kW RD05034JDAE User manual

  • Hello! I am an AI chatbot trained to assist you with the Generac 50kW RD05034JDAE User manual. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
4 3 2 1
4 3 1
A
B
A
B
998 [39.3]
CENTER OF GRAVITY
SEE NOTE 5
618.3 [24.3]
EXHAUST OUTLET
172.6 [6.8]
EXHAUST OUTLET
897 [35.3]
DOOR WIDTH
TYP
1452.9 [57.2]
OVERALL
HEIGHT
888.1 [35.0]
OVERALL WIDTH
343 [13.5]
TYP
181.9 [7.2]
TYP
1625 [64.0]
TYP
2423.9 [95.4]
OVERALL LENGTH
WEIGHT DATA WITH EMPTY BASETANK
(SEE NOTE 5)
GENERATOR AS SHOWN
997 [2197]
WITH WOODEN SHIPPING SKID
1042 [2297]
SERVICE ITEM 3.4L
OIL FILL CAP RIGHT SIDE
OIL DIP STICK RIGHT SIDE
OIL FILTER RIGHT SIDE
OIL DRAIN HOSE
RIGHT SIDE
RADIATOR DRAIN HOSE LEFT SIDE
AIR CLEANER ELEMENT RIGHT SIDE
MUFFLER FRONT
FAN BELT EITHER SIDE
BATTERY LEFT SIDE
TITLE
INSTALL PROTECTOR D3.4L G16 EXT
ISSUE DATE: 08/2018
SIZE CAGE NO DWG NO
10000042807
REV
B
N/A
A
SCALE
0.050
WT-KG SEE ABOVE SHEET
1 of 2
GENERAC POWER SYSTEMS OWNS THE COPYRIGHT OF THIS DRAWING
WHICH IS SUPPLIED IN CONFIDENCE AND MUST NOT BE USED FOR
ANY PURPOSE OTHER THAN FOR WHICH IT IS SUPPLIED WITHOUT
THE EXPRESS WRITTEN CONSENT OF GENERAC POWER SYSTEMS.
c GENERAC POWER SYSTEMS 2013
ELECTRONICALLY APPROVED
INSIDE WINDCHILL
DRAWING CREATED FROM PRO/ENGINEER
3D FILE. ECO MODIFICATION TO BE
APPLIED TO SOLID MODEL ONLY.
SH
1/2
REV
A
WINDCHILL VERSION
A.2
NOTES:
1. MINIMUM RECOMMENDED CONCRETE PAD SIZE: 1194 (47") WIDE X 2718
(107") LONG. REFERENCE INSTALLATION GUIDE SUPPLIED WITH UNIT
FOR CONCRETE PAD GUIDELINES
2. ALLOW SUFFICIENT ROOM ON ALL SIDES OF THE GENERATOR FOR MAINTENANCE
AND SERVICING. THIS UNIT MUST BE INSTALLED IN ACCORDANCE WITH CURRENT
APPLICABLE NFPA 37 AND NFPA 70 STANDARDS AS WELL AS ANY OTHER FEDERAL,
STATE AND LOCAL CODES.
3. CONTROL PANEL / CIRCUIT BREAKER INFORMATION:
- SEE SPECIFICATION SHEET OR OWNERS MANUAL
- ACCESSIBLE THROUGH CUSTOMER ACCESS ASSEMBLY DOOR ON REAR OF
GENERATOR
4. REMOVE THE REAR TANK AND REAR ENCLOSURE COVER PANEL TO ACCESS
THE STUB-UP AREAS AS FOLLOWS:
- HIGH VOLTAGE CONNECTION INCLUDING AC LOAD LEAD CONDUIT CONNECTION,
NEUTRAL CONNECTION, BATTERY CHARGER 120 VOLT AC (0.5 AMP MAX) CONNECTION.
- LOW VOLTAGE CONNECTIONS INCLUDING TRANSFER SWITCH CONTROL WIRES
5. CENTER OF GRAVITY AND WEIGHT MAY CHANGE DUE TO UNIT OPTIONS.
6. ENGINE SERVICE CONNECTIONS
OIL DRAIN: 3/8" NPT
EXHAUST OUTLET: 2" O.D.
7. BOTTOM OF GENERATOR SET MUST BE ENCLOSED TO PREVENT PEST INTRUSION AND
RECIRCULATION OF DISCHARGE AIR AND/OR IMPROPER COOLING AIR FLOW.
8. REFERENCE OWNERS MANUAL FOR LIFTING WARNINGS.
9. MOUNTING BOLTS OR STUDS TO CONCRETE PAD SHALL BE 5/8-11 GRADE 5
(USE STANDARD SAE TORQUE SPECS)
WEIGHT: KG [LBS]
DIMENSIONS: MM [INCH]
REFERENCE OWNERS MANUAL FOR
PERIODIC REPLACEMENT PART LISTINGS
CIRCUIT BREAKER
SEE NOTE 3
REAR ENCLOSURE
COVER PANEL
SEE NOTE 4
CUSTOMER ACCESS
ASSEMBLY, CONTROL
PANEL ACCESS AND
BATTERY CHARGER
LOCATED WITHIN
SEE NOTE 4
REAR TANK
COVER PANEL
SEE NOTE 4
REAR VIEW
ALARM ASSEMBLY AND OPTIONAL 5 GALLON SPILL BOX
VENT, OUTER TANK EMERGENCY VENT, OPTIONAL 90%
LEVEL GAUGE, NORMAL VENT, INNER TANK EMERGENCY
LIFT-OFF DOOR PROVIDES ACCESS TO: FUEL FILL, FUEL
VISE ACTION LATCH, ONE PER
DOOR AND ONE LIFT-OFF DOOR
PER SIDE OF GENERATOR
RIGHT SIDE VIEW
RADIATOR/EXHAUST
DISCHARGE AIR
VENTILATION DUCT
FUEL TANK
VENTILATION
CROSS-FLOW OF AIR
PROVIDE ADEQUATE
VENTILATION DUCT TO
OF FUEL TANK
TYPICAL ON BOTH SIDES
OPEN PUNCHED LOUVERS
WITHIN GENERATOR ENCLOSURE
EXHAUST MUFFLER ENCLOSED
LIFTING PROVISIONS, SEE NOTE 5, 8
AND CENTER OF GRAVITY DIMENSION
(4 PLACES)
LEFT SIDE VIEW
APPLICABILITY)
AND STATE CODE FOR
ENCLOSURE (CHECK LOCAL
OUTSIDE OF THE GENERATOR
TANK VENTS TO TERMINATE
REMOVE PANEL TO ALLOW
RADIATOR/EXHAUST
DISCHARGE AIR
(BOTH SIDES)
BATTERY 12 VOLT
NEGATIVE GROUND
REMOVE COVER FOR ACCESS
TO RADIATOR FILL CAP
AND EXHAUST SYSTEM
THE ENGINE, ALTERNATOR
VENTILATION DUCT FROM
SEPARATES FUEL TANK
INTERNAL DIVIDER PANEL
AIR INTAKE
(BOTH SIDES)
TOP VIEW
4 3 2 1
4 3 1
A
B
A
B
18.5 [.7]
TYP
851.1 [33.5]
MOUNTING CENTERS
TYP
SEE NOTE 9
888.1 [35.0]
394 [15.5]
110 [4.3]
TYP
690 [27.2]
TYP
1216 [47.9]
TYP
1769 [69.6]
TYP
2322 [91.4]
TYP
100.5 [4.0]
225.5 [8.9]
313.8 [12.4]
350.5 [13.8]
213.5 [8.4]
282.1 [11.1]
487.1 [19.2]
660.1 [26.0]
TYP
266.1 [10.5]
TYP
1314.4 [51.8]
1386.1 [54.6]
169.1 [6.7]
717.1 [28.2]
2088.4 [82.2]
TYP
786 [30.9]
125 [4.9]
*STUB-UP
AREA
38 [1.5]
51.1 [2.0]
2159.6 [85.0]
62.4 [2.5]
125 [4.9]
*STUB-UP
AREA
253.3 [10.0]
2423.9 [95.4]
291.3 [11.5]
FUEL TANK
HEIGHT
850.1 [33.5]
FUEL TANK
TOTAL CAPACITY 233 [61]
USABLE CAPACITY 209 [55]
TITLE
INSTALL PROTECTOR D3.4L G16 EXT
ISSUE DATE: 08/2018
SIZE CAGE NO DWG NO
10000042807
REV
B
N/A
A
SCALE
0.050
WT-KG SEE ABOVE SHEET
2 of 2
GENERAC POWER SYSTEMS OWNS THE COPYRIGHT OF THIS DRAWING
WHICH IS SUPPLIED IN CONFIDENCE AND MUST NOT BE USED FOR
ANY PURPOSE OTHER THAN FOR WHICH IT IS SUPPLIED WITHOUT
THE EXPRESS WRITTEN CONSENT OF GENERAC POWER SYSTEMS.
c GENERAC POWER SYSTEMS 2013
ELECTRONICALLY APPROVED
INSIDE WINDCHILL
DRAWING CREATED FROM PRO/ENGINEER
3D FILE. ECO MODIFICATION TO BE
APPLIED TO SOLID MODEL ONLY.
SH
2/2
REV
A
WINDCHILL VERSION
A.2
CAPACITY: LITER [GALLONS]
DIMENSIONS: MM [INCH]
*NOTE: STUB-UP AREA FOR HIGH AND LOW
VOLTAGE CONNECTIONS, CIRCUIT BREAKER,
NEUTRAL AND CUSTOMER CONNECTION OPENING.
THIS TANK IS LISTED TO UL142 AND ULC5601
16.7 [.66] MOUNTING HOLES
(10 PLACES)
REAR TANK
COVER PANEL
SEE NOTE 4
REAR VIEW
LEFT SIDE VIEW
OUTER TANK EMERGENCY VENT
(2" NPT FEMALE)
FUEL FILL
(2" NPT FEMALE)
FUEL RETURN
FUEL SUPPLY
CUSTOMER OPTION
(2" NPT FEMALE)
OUTER TANK
LEAK DETECTOR
INNER TANK NORMAL VENT
(2" NPT FEMALE)
INNER TANK EMERGENCY VENT
(2" NPT FEMALE)
FUEL LEVEL
GAUGE/SENDER
HIGH AND
LOW VOLTAGE
STUB-UP AREA
TOP VIEW
/