ABB RELION REF610 Technical Reference Manual

Type
Technical Reference Manual
REF 610
Feeder Protection Relay
Technical Reference Manual - ANSI Version
Feeder Protection Relay
Technical Reference Manual - ANSI Version
REF 610
Issued: January 30, 2005
Version: A
©Copyright 2004 ABB, Distribution Automation, Allentown, PA 3
Content
1. Introduction ...............................................................................6
1.1. About this manual .........................................................................6
1.2. The use of the relay ......................................................................6
1.3. Features ........................................................................................6
1.4. Warranty ........................................................................................8
1.5. Revision history .............................................................................8
2. Safety information .....................................................................9
3. Instructions ..............................................................................10
3.1. Application ...................................................................................10
3.2. Requirements ..............................................................................10
3.3. Configuration ...............................................................................10
4. Technical description .............................................................13
4.1. Functional description .................................................................13
4.1.1. Product functions .............................................................13
4.1.1.1. Protection functions ............................................13
4.1.1.2. Inputs .................................................................13
4.1.1.3. Outputs ...............................................................14
4.1.1.4. Disturbance recorder ..........................................14
4.1.1.5. HMI .....................................................................14
4.1.1.6. Non-volatile memory ..........................................14
4.1.1.7. Self-supervision ..................................................14
4.1.1.8. Time synchronization .........................................15
4.1.2. Measurements .................................................................16
4.1.3. Configuration ....................................................................16
4.1.4. Protection .........................................................................18
4.1.4.1. Block diagram ....................................................18
4.1.4.2. Overcurrent protection .......................................19
4.1.4.3. Ground-fault protection ......................................20
4.1.4.4. Thermal protection for cables .............................21
4.1.4.5. Phase discontinuity protection ...........................26
4.1.4.6. Circuit-breaker failure protection ........................26
4.1.4.7. Arc protection .....................................................27
4.1.4.8. Auto-reclose function .........................................28
4.1.4.9. Inverse definite minimum time characteristics ...34
4.1.4.10.Settings ..............................................................46
4.1.4.11.Technical data on protection functions ..............58
4.1.5. Trip-circuit supervision .....................................................63
1MRS 755535
4
1MRS 755535
Feeder Protection Relay
Technical Reference Manual - ANSI Version
REF 610
4.1.6. Trip lockout function ........................................................64
4.1.7. Trip counters for circuit-breaker condition monitoring ......65
4.1.8. Indicator LEDs and operation target messages ...............65
4.1.9. Demand values ................................................................65
4.1.10.Commissioning tests ........................................................66
4.1.11.Disturbance recorder .......................................................66
4.1.11.1.Function .............................................................66
4.1.11.2.Disturbance recorder data .................................66
4.1.11.3.Control and target of disturbance
recorder status ...................................................67
4.1.11.4.Triggering ..........................................................68
4.1.11.5.Settings and unloading.......................................68
4.1.11.6.Event code of the disturbance recorder .............68
4.1.12.Recorded data of the last events .....................................68
4.1.13.Communication ports .......................................................70
4.1.14.IEC 60870-5-103 remote communication protocol ..........71
4.1.15.Modbus remote communication protocol .........................75
4.1.15.1.Protocol overview ..............................................75
4.1.15.2.Profile of Modbus REF 610 ...............................76
4.1.16.DNP 3.0 remote communication protocol ........................89
4.1.16.1.Protocol overview ..............................................89
4.1.16.2.Protocol parameters of REF 610 .......................89
4.1.16.3.DNP 3.0 point list of REF 610 ............................89
4.1.16.4.DNP 3.0 device profile of REF 610 ....................93
4.1.16.5.REF 610-specific DNP features .......................100
4.1.17.SPA bus communication protocol parameters ...............103
4.1.17.1.Event codes .....................................................118
4.1.18.Self-supervision (IRF) system ........................................122
4.1.19.Relay parameterization ..................................................123
4.2. Design description ....................................................................124
4.2.1. Input/output connections ...............................................124
4.2.2. Light sensor input connections ......................................129
4.2.3. Serial communication connections ................................129
4.2.4. Technical data ...............................................................134
5. Application examples .......................................................... 139
5.1. Auto-reclose function ................................................................139
5.1.1. Fast tripping and initiation of shot 1 using two
protection stages ..........................................................139
5.1.2. Fast tripping and initiation of shot 1 using pickup signals 140
5.1.3. Selecting adaptive sequence length ..............................141
5.2. Arc protection ............................................................................142
5.2.1. Arc protection with one REF 610 relay ..........................142
1MRS 755535
Feeder Protection Relay
Technical Reference Manual - ANSI Version
REF 610
5
5.2.2. Arc protection with several REF 610 relays ...................144
5.2.3. Arc protection with several REF 610 relays and
one REA 101 ..................................................................145
6. Ordering information ............................................................146
7. Revision History of REF 610.................................................148
7.1. Revision identification ................................................................148
7.2. Changes and additions to earlier released revision A................148
8. References .............................................................................149
9. Abbreviations ........................................................................150
10.Check lists ............................................................................152
6
1MRS 755535
Feeder Protection Relay
Technical Reference Manual - ANSI Version
REF 610
1. Introduction
1.1. About this manual
This manual provides thorough information on the protection relay REF 610
Revision B
and its applications. For more information about the earlier revisions,
refer to section "Revision history of the REF 610".
Refer to the Operator’s Manual for instructions on how to use the
Human-Machine Interface (HMI) of the relay, also known as the Man-Machine
Interface (MMI), and to the Installation Manual for installation of the relay.
1.2. The use of the relay
The feeder protection relay REF 610 is a versatile multifunction protection relay
mainly designed to protect incoming and outgoing feeders in a wide range of feeder
applications.
REF 610 is based on a microprocessor environment. A self-supervision system
continuously monitors the operation of the relay.
The HMI includes a Liquid Crystal Display (LCD) which makes the local use of the
relay safe and easy.
Local control of the relay via serial communication can be carried out with a
computer connected to the front communication port. Remote control can be carried
out via the rear connector connected to the control and monitoring system through
the serial communication bus.
1.3. Features
Three-phase non-directional overcurrent protection with definite-time or IDMT
(mode) characteristic, low-set element
Three-phase non-directional overcurrent protection, high-set element
Three-phase non-directional overcurrent protection, instantaneous element
Non-directional ground-fault protection with definite-time or IDMT (mode)
characteristic, low-set element
Non-directional ground-fault protection, high-set element
Phase discontinuity protection
Three-phase thermal overload protection for cables
Arc protection
two lens sensors for arc detection (optional)
automatic reference level adjustment based on backlight intensity
arc detection via a remote light signal
Automatic reclosing 1...3 shots
Circuit-breaker failure protection
Trip counters for circuit-breaker condition monitoring
Trip-circuit supervision with possibility to route the warning signal to a non-trip
output
1MRS 755535
Feeder Protection Relay
Technical Reference Manual - ANSI Version
REF 610
7
Trip lockout function
Four accurate current inputs
User-selectable rated frequency 50/60 Hz
Three normally open trip output contacts
Two change-over (Form C) non-trip output contacts and three additional change
over (Form C) non-trip output contacts on the optional I/O module
Output contact functions freely configurable for desired operation
Two galvanically isolated digital inputs and three additional galvanically isolated
digital inputs on the optional I/O module
Disturbance recorder
recording time up to 80 seconds
triggering by one or several internal or digital input signals
records four analogue channels and up to eight user-selectable digital channels
adjustable sampling rate
Non-volatile memory for
up to 100 event codes with time stamp
setting values
disturbance recorder data
recorded data of the five last events with time stamp
number of AR shots and pickups/trips for protection elements
operation target messages and LEDs showing the status at the moment of
power failure
HMI with an alphanumeric LCD and
maneuvering buttons
eight programmable LEDs
Operation target messages displayed in ANSI mode
Multi-language support
User-selectable password protection for the HMI
Display of primary current values
Demand values
All settings can be modified with a PC
Optical front communication connection: wirelessly or via cable
Optional rear communication module with plastic fibre-optic, combined
fibre-optic (plastic and glass) or RS-485 connection for system communication
using the SPA-bus, IEC 60870-5-103 or Modbus (RTU and ASCII)
communication protocol
Optional DNP 3.0 rear communication module with RS-485 connection for
system communication using the DNP 3.0 communication protocol.
Battery back-up for real-time clock
8
1MRS 755535
Feeder Protection Relay
Technical Reference Manual - ANSI Version
REF 610
Battery charge supervision
Continuous self-supervision of electronics and software.
Detachable plug-in unit
1.4. Warranty
Please inquire about the terms of warranty from your nearest ABB representative.
1.5. Revision history
Version Date Remarks
A
Jan. 30 2005 Modified for ANSI compliance from the original manual
version 1MRS755310 version A
1MRS 755535
Feeder Protection Relay
Technical Reference Manual - ANSI Version
REF 610
9
2. Safety information
Dangerous voltages can occur on the connectors, even though the
auxiliary voltage has been disconnected.
National and local electrical safety regulations must always be
followed.
The device contains components which are sensitive to electrostatic
discharge. Unnecessary touching of electronic components must
therefore be avoided.
The frame of the device has to be carefully grounded.
Only a competent electrician is allowed to carry out the electrical
installation.
Non-observance can result in death, personal injury or substantial
property damage.
Breaking the sealing tape on the upper handle of the device will result
in loss of warranty and proper operation will no longer be guaranteed.
When the plug-in unit has been detached from the case, do not touch
the inside of the case. The relay case internals may contain high voltage
potential and touching these may cause personal injury.
!
10
1MRS 755535
Feeder Protection Relay
Technical Reference Manual - ANSI Version
REF 610
3. Instructions
3.1. Application
REF 610 is a versatile multifunction protection relay mainly designed for protection
of incoming and outgoing feeders in MV distribution substations. REF 610 can also
be used as back-up protection for motors, transformers and generators, in industrial
as well as in utility applications.
The large number of integrated protection functions, including three overcurrent
protection elements, non-directional ground-fault protection elements as well as
thermal protection, makes REF 610 a complete protection against overcurrent and
ground faults.
The optional arc protection for detection of arc situations in air insulated metal-clad
switchgears and the auto-reclose function for automatic clearing of overhead line
faults increase the range of applications further.
The large number of digital inputs and output contacts allows a wide range of
applications.
3.2. Requirements
To secure correct and safe operation of the relay, preventive maintenance is
recommended to be performed every five years when REF 610 is operating under
the specified conditions; see below and section Technical data.
When being used for real-time clock or recorded data functions, the battery should
be changed every five years.
Environmental conditions
3.3. Configuration
Setting and connection examples
The appropriate configuration of the output contact matrix enables the use of the
signals from the protection elements as contact functions. The pickup signals can be
used for blocking co-operating protection relays and signalling.
Fig. 3.3.-1 and Fig. 3.3.-2 represent REF 610 with the default configuration: all trip
signals are routed to trip the circuit breaker. In Fig. 3.3.-1, the residual current is
measured via a core-balance current transformer and the output contacts are
connected to enable the use of the auto-reclose function. In Fig. 3.3.-2, the residual
current is measured via a summation connection of the phase current transformers
and the output contacts are connected to enable the use of the trip lockout function.
• Recommended temperature range (continuous) -10...+55°C
• Limit temperature range (short-term) -40...+70°C
• Temperature influence on the operation accuracy of the
protection relay within the specified service temperature range
0.1%/°C
• Transport and storage temperature range -40...+85°C
1MRS 755535
Feeder Protection Relay
Technical Reference Manual - ANSI Version
REF 610
11
Fig. 3.3.-1 Connection diagram, example 1
U
aux
X2.1 7 8 1 2 3 4 5 6 X3.1 6 5 4 3 2 1
D15 D14 D13 D12 D11
21 22 23 24 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
16 17 18 19 20 21 22 23 24 X3.1
IRF SO1 SO4 PO3 PO2 PO1 SO5 SO4 SO3
Optional
Optional
SGB5 SGB4 SGB3 SGB2 SGB1
11 11 11 11 11
12 12 12 12 12
13 13 13 13 13
14 14 14 14 14
15 15 15 15 15
999 99
18 18 18 18 18
19 19 19 19 19
16 16 16 16 16
17 17 17 17 17
20 20 20 20 20
888 88
10 10 10 10 10
666 66
777 77
111 11
222 22
333 33
444 44
555 55
1111 1 111
2222 2 222
3333 3 333
4444 4 444
5555 5 555
6666 6 666
7777 7 777
8888 8 888
9999 9 999
10 10 10 10 10 10 10 10
11 11 11 11 11 11 11 11
12 12 12 12 12 12 12 12
13 13 13 13 13 13 13 13
14 14 14 14 14 14 14 14
23 23 23 23 23 23 23 23
22 22 22 22 22 22 22 22
16 16 16 16 16 16 16 16
17 17 17 17 17 17 17 17
19 19 19 19 19 19 19 19
20 20 20 20 20 20 20 20
18 18 18 18 18 18 18 18
21 21 21 21 21 21 21 21
15 15 15 15 15 15 15 15
Self-supervision IRF
Warning
51P Pickup
Blocking Trip
50P-1 Pickup
Blocking Trip
50P-2 Pickup
Trip
51N Pickup
Blocking Trip
50N Pickup
Blocking Trip
46 Pickup
Blocking Trip
49 Alarm
Trip
Arc 51P/51N Arc light output
External Arc Trip
79
CB Position Open
CB Position Closed
AR Disable
CB Close Disable
External AR Initiation
Trip Lockout
External Triggering
Reset
External Trip
CB FAIL
External Triggering
Indications Cleared
Output contacts unlatched
Memorized values cleared
Setting group selection
Time sync
SGF1...SGF5
SGL1...SGL8
Open CB Command
Close CB Command
CB Reclosing Failed
Shot Due
Definite Trip Alarm
Trip Lockout
External Trip
Trip
X5.1
X5.2
Light Sensor 1
Light Sensor 2
Optional
ConnDiagr1REF610_a
-
52b
52a
A
B
C
+
CS
C
+
-
52
CLOSE
52
TC
+
CS
T
52a 52b
+
-
-
+
(dc/ac)
(dc/ac)
12
1MRS 755535
Feeder Protection Relay
Technical Reference Manual - ANSI Version
REF 610
Fig. 3.3.-2 Connection diagram, example 2
SGB5 SGB4 SGB3 SGB2 SGB1
11 11 11 11 11
12 12 12 12 12
13 13 13 13 13
14 14 14 14 14
15 15 15 15 15
999 99
18 18 18 18 18
19 19 19 19 19
16 16 16 16 16
17 17 17 17 17
20 20 20 20 20
888 88
10 10 10 10 10
666 66
777 77
111 11
222 22
333 33
444 44
555 55
1111 1 111
2222 2 222
3333 3 333
4444 4 444
5555 5 555
6666 6 666
7777 7 777
8888 8 888
9999 9 999
10 10 10 10 10 10 10 10
11 11 11 11 11 11 11 11
12 12 12 12 12 12 12 12
13 13 13 13 13 13 13 13
14 14 14 14 14 14 14 14
23 23 23 23 23 23 23 23
22 22 22 22 22 22 22 22
16 16 16 16 16 16 16 16
17 17 17 17 17 17 17 17
19 19 19 19 19 19 19 19
20 20 20 20 20 20 20 20
18 18 18 18 18 18 18 18
21 21 21 21 21 21 21 21
15 15 15 15 15 15 15 15
51P Pickup
Blocking Trip
50P-1 Pickup
Blocking Trip
50P-2 Pickup
Trip
51N Pickup
Blocking Trip
50N Pickup
Blocking Trip
46 Pickup
Blocking Trip
49 Alarm
Trip
Arc 51P/51N Arc light output
External Arc Trip
79
CB Position Open
CB Position Closed
AR Disable
CB Close Disable
External AR Initiation
Trip Lockout
External Triggering
Reset
External Trip
CB FAIL
External Triggering
Indications Cleared
Output contacts unlatched
Memorized values cleared
Setting group selection
Time sync
SGF1 ...SGF5
SFL1 ...SGL8
Open CB Command
Close CB Command
CB Reclosing Failed
Shot Due
Definite Trip Alarm
AR Lockout
Trip Lockout
External Trip
Trip
Self-supervision IRF
Warning
X2.1 7 8 1 2 3 4 5 6 X3.1 6 5 4 3 2 1
D15 D14 D13 D12 D11
21 22 23 24 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
16 17 18 19 20 21 22 23 24 X3.1
IRF SO2 SO1 PO3 PO2 PO1 SO5 SO4 SO3
Optional
Optional
SGR5 SGR4 SGR3 SGR2 SGR1 SGR8 SGR7 SGR6
X5.1
X5.2
L
ight Sensor 1
L
ight Sensor 2
Optional
ConnDiagr2 REF610_a
U
aux
L1
L2
L3
-
52b
52a
+
CS
C
+
-
52
CLOSE
52
TC
+
CS
T
+
(dc/ac)
(dc/ac)
1MRS 755535
Feeder Protection Relay
Technical Reference Manual - ANSI Version
REF 610
13
4. Technical description
4.1. Functional description
4.1.1. Product functions
4.1.1.1. Protection functions
The protection functions of REF 610 with their IEC symbols and IEEE device
numbers are presented in the table below:
For descriptions of the protection functions, refer to sections:
4.1.4.2. Overcurrent protection
4.1.4.3. Ground-fault protection
4.1.4.4. Thermal protection for cables
4.1.4.5. Phase discontinuity protection
4.1.4.6. Circuit-breaker failure protection
4.1.4.7. Arc protection
4.1.4.8. Auto-reclose function
4.1.1.2. Inputs
REF 610 is provided with four energizing inputs, two optional light sensor inputs,
two digital inputs and three optional digital inputs controlled by an external voltage.
Three of the energizing inputs are for the phase currents and one for the ground-fault
current. For details, refer to section Input/output connections and tables 4.1.4.10-7,
4.2.1-1 and 4.2.1-5. The functions of the digital inputs are determined with the
SGB switches.
Table 4.1.1.1-1 IEC symbols and IEEE device numbers
Function description IEC symbol
IEEE Device
No.
Three-phase non-directional overcurrent protection,
low-set element
I> 51P
Three-phase non-directional overcurrent protection,
high-set element
I>> 50P-1
Three-phase non-directional overcurrent protection,
instantaneous element
I>>> 50P-2
Phase discontinuity protection ΔI> 46
Three-phase thermal overload protection for cables θ>49
Non-directional ground-fault protection, low-set element I
0
>51N
Non-directional ground-fault protection, high-set
element
I
0
>> 50N
Arc protection ARC ARC
Circuit-breaker failure protection CBFP CBFAIL
Automatic reclosing 0179
Lockout relay 86
14
1MRS 755535
Feeder Protection Relay
Technical Reference Manual - ANSI Version
REF 610
4.1.1.3. Outputs
REF 610 is provided with three trip outputs (PO1, PO2 and PO3), two non-trip
outputs (SO1 and SO2) and three optional non-trip outputs (SO3, SO4 and SO5).
Switchgroups SGR1...8 are used for routing internal signals from the protection
elements, the external trip signal and signals from the auto-reclose function to the
desired non-trip or trip output. The minimum pulse length can be configured to be
40 or 80 ms and the trip outputs can all be configured to be latched.
4.1.1.4. Disturbance recorder
REF 610 includes an internal disturbance recorder which records the instantaneous
measured values, or the RMS curves of the measured signals, and up to eight
user-selectable digital signals: the digital input signals and the internal signals from
the protection elements. Any digital signal can be set to trigger the recorder on either
the falling or rising edge.
4.1.1.5. HMI
The HMI of REF 610 is equipped with six push-buttons, an alphanumeric
2x16 characters’ LCD, eight programmable target LEDs, three target LEDs with
fixed functionality, and an target LED for front communication. The
push-buttons are used for navigating in the menu structure and for adjusting setting
values.
An HMI password can be set to protect all user-changeable values from being
changed by an unauthorized person. The HMI password will remain inactive and
will thus not be required for altering parameter values until the default HMI
password has been replaced. Entering the HMI password successfully can be
selected to generate an event code. This feature can be used to indicate interaction
activities via the local HMI. For further information on the HMI, refer to the
Operator’s Manual.
4.1.1.6. Non-volatile memory
REF 610 can be configured to store various data in a non-volatile memory, which
will retain its data also in case of loss of auxiliary voltage (provided that the battery
has been inserted and is charged). Operation target messages and LEDs, disturbance
recorder data, event codes and recorded data can all be configured to be stored in the
non-volatile memory whereas setting values will always be stored in the EEPROM.
4.1.1.7. Self-supervision
The self-supervision system of REF 610 manages run-time fault situations and
informs the user about an existing fault. There are two types of fault targets: internal
relay fault (IRF) targets and warnings.
When the self-supervision system detects a permanent internal relay fault, which
will prevent relay operation, the green target LED (ready) will begin to blink. At the
same time, the IRF contact, which is normally picked up, will drop off and a fault
code will appear on the LCD. The fault code is numerical and identifies the fault
type.
1MRS 755535
Feeder Protection Relay
Technical Reference Manual - ANSI Version
REF 610
15
Fig. 4.1.1.7.-1 Permanent IRF
In case of a warning, the relay will continue to operate with full or reduced
functionality and the green target LED (ready) will remain lit as during normal
operation. A fault target message (see Fig. 4.1.1.7.-2), with a possible fault code (see
Fig. 4.1.1.7.-3), will appear on the LCD indicating the type of fault. In case of a
warning due to an external fault in the trip circuit detected by the trip-circuit
supervision, or due to continuous light on the light sensor inputs, SO2 will be
activated (if SGF1/8=1).
Fig. 4.1.1.7.-2 Warning with text message
Fig. 4.1.1.7.-3 Warning with numeric code
For fault codes, refer to section Self-supervision (IRF) system.
4.1.1.8. Time synchronization
Time synchronization of the relay’s real-time clock can be realized in two different
ways: via serial communication using a communication protocol or via a digital
input.
Any digital input can be configured for time synchronization and used for either
minute-pulse or second-pulse synchronization. The synchronization pulse is
automatically selected and depends on the time range within which the pulse occurs.
The time must be set once, either via serial communication or manually via the HMI.
If the synchronization pulse differs more than +/- 0.05 seconds for second-pulse or
+/- 2 seconds for minute-pulse synchronization from the relay’s real-time clock, the
synchronization pulse will be rejected.
IntFault_a
INTERNAL FAULT
FAULT CODE :30
Warning_a
WARNING
BATTERY LOW
WarnREF610_a
WARNING
FAULT CODE: 33
16
1MRS 755535
Feeder Protection Relay
Technical Reference Manual - ANSI Version
REF 610
Time synchronization is always triggered on the rising edge of the digital input
signal. The time is adjusted in steps of five milliseconds per synchronization pulse.
The typical accuracy achievable with time synchronization via a digital input is
+2.5...-2.5 milliseconds for second-pulse and +5...-5 milliseconds for minute-pulse
synchronization.
Note!
The pulse length of the digital input signal does not affect time synchronization.
4.1.2. Measurements
The table below presents the measured values which can be accessed through the
HMI:
4.1.3. Configuration
Fig. 4.1.3.-1 illustrates how the internal and digital input signals can be configured
to obtain the required protection functionality.
Table 4.1.2-1 Measured values
Indicator Description
l
a
Current measured on phase l
a
l
b
Current measured on phase l
b
l
c
Current measured on phase l
c
ln Measured ground-fault current
l(unbal) Calculated phase unbalance
TH LEVEL Calculated thermal level
I
1_
min
One-minute demand value
I
n_
min
Demand value during the specified time range
Max I Maximum one-minute demand value during
the specified time range
1MRS 755535
Feeder Protection Relay
Technical Reference Manual - ANSI Version
REF 610
17
Fig. 4.1.3.-1 Signal diagram
Ia
Ib
Icı ı
In
X5.1
X5.2
Light Sensor 1
Light Sensor 2
Optional
Optional
D15 D14 D13 D12 D11
IRF SO2 SO1 PO3 PO2 PO1 SO5 SO4 SO3
X3.1 6 5 4 3 2 1 X4.1 21 22 23 24
3 4 5 6 7 8 9 1011 1213 1415 161718 19
16 17 18 19 20 21 22 23 24
X3.1
SGB5 SGB4 SGB3 SGB2 SGB1
11 11 11 11 11
12 12 12 12 12
13 13 13 13 13
14 14 14 14 14
18 18 18 18 18
19 19 19 19 19
16 16 16 16 16
17 17 17 17 17
20 20 20 20 20
888 88
10 10 10 10 10
666 66
777 77
111 11
222 22
333 33
444 44
555 55
999 99
15 15 15 15 15
1111 1 111
2222 2 222
3333 3 333
4444 4 444
5555 5 555
6666 6 666
7777 7 777
8888 8 888
9999 9 999
10 10 10 10 10 10 10 10
11 11 11 11 11 11 11 11
12 12 12 12 12 12 12 12
13 13 13 13 13 13 13 13
14 14 14 14 14 14 14 14
23 23 23 23 23 23 23 23
22 22 22 22 22 22 22 22
16 16 16 16 16 16 16 16
17 17 17 17 17 17 17 17
19 19 19 19 19 19 19 19
20 20 20 20 20 20 20 20
18 18 18 18 18 18 18 18
21 21 21 21 21 21 21 21
15 15 15 15 15 15 15 15
51P
Blocking
50P-1
Blocking
50P-2
51N
Blocking
50N
Blocking
46
Blocking
49
Trip
Arc 51P/51N Arc light output
External Arc Trip
79
CB Position Open
CB Position Closed
AR Disable
CB Close Disable
External AR Initiation
Trip Lockout
External Triggering
Reset
External Trip
CBFAIL
External Triggering
Indications Cleared
Output contacts unlatched
Memorized values cleared
Setting group selection
Time sync
SGF1 ...SGF5
SFL1 ...SGL8
Arc light output
Open CB Command
Close CB Command
CB Reclosing Failed
Shot Due
Definite Trip Alarm
AR Lockout
Trip Lockout
External Trip
Trip
Self-supervision IRF
Warning
SignDiagrREF610_a
Pickup
Trip
Pickup
Trip
Pickup
Trip
Pickup
Trip
Pickup
Trip
Pickup
Trip
Pickup
Trip
18
1MRS 755535
Feeder Protection Relay
Technical Reference Manual - ANSI Version
REF 610
The functions of the relay are selected with the switches of switchgroups SGF, SGB,
SGR and SGL. The checksums of the switchgroups are found under SETTINGS in
the HMI menu. The functions of the switches are explained in detail in the
corresponding SG_ tables.
4.1.4. Protection
4.1.4.1. Block diagram
Fig. 4.1.4.1.-1 Block diagram
LED1
LED2
LED3
LED4
LED5
LED6
LED7
LED8
PO1
PO2
PO3
SO1
SO2
SO3
SO4
SO5
IRF
SGB1...5
SGL1...8
ıˇ
ııııı ˇ
ı
Programmable
LEDs
Disturbance recorder
(4 analogue + up to 8 digital channels)
Digital outputs
(Output contacts)
IRF INDICATION
START/ALARM INDICATION
TRIP INDICATION
IRF indication LED (green)
Start/Alarm (yellow) and
trip (red) indication LEDs
The dashed line indicates optional functionality.
1) Clear indications by the digital input signal
2) Clear indications and unlatch output contacts by the
digital input signal
3) Reset indications and memorized values; unlatch output
contacts by the digital input signal
Optional digital
inputs
(I/O module)
Digital inputs
DI1
DI2
DI3
DI4
DI5
Switchgroups for
digital inputs
Protection relay functions
Analogue inputs
Switchgroups for
programmable LEDs
Switchgroups for
output contacts
Trip lockout
ı
ı
Warning
BlockDiagrREF610_a
SGR1...5
SGB1...5 SGL1...8
Disturbance recorder
(4 analogue + up to 8 digital channels)
Reset 1
Reset 2
Reset 3
Setting group
Time sync
Ext Trip
Ex Trig CBFAIL
Ext Trig Trip lockout
Ext Arc
Trip lockout reset
Block 51P
Block 50P-1
Block 51N
Block 50N
Block 46
AR Disable
CB Close Disable
CB Pos Open
CB Pos Close
Ext AR Initiation
1)
2)
3)
Ia
Ib
Ic
In
Optional arc detector inputs
(Communication module)
Light sensor input1
Light sensor input 2
51P 51N
Block Block
Pickup
Trip
Pickup
Trip
50N
Pickup
Trip
50P-1
Double
Block
Double
Block
Pickup
Trip
50P-2
Pickup
Trip
46
Block
Pickup
Trip
49
CBFAIL
Block
Pickup
Trip
I
In
Trip lockout
Trip lockout
Light Output
Trip
Arc 50, Arc 50N
In
Ia
Ib
Ic
Pickup
Trip
PO1
EXT TRIG
Ext Trig
Reset
PO3
PO2
Light1
Light2
Ext Arc
79, AR
Autoreclose
CB Pos Open
CB Pos Closed
AR Disable
CB Close Disable
Ext AR Initiation
51P Pickup
51P Trip
50P-1 Trip
50P-2 Trip
51N Pickup
51N Trip
50N Pickup
46 Trip
49 Alarm
49 Trip
Arc Trip
CBFAIL
Open CB Cmd
Close CB Cmd
CB Reclose Failed
Shot DUe
Definite Trip Alarm
AR Lockout
Block 51P
Block 50P-1
Block 50P-2
Block 51N
Block 50N
Ia
Ib
Ic
In
DI1
DI2
DI3
DI4
DI5
51P Pickup
51P Trip
50P-1 Pickup
50P-1 Trip
50P-2 Pickup
50P-2 Trip
51N Pickup
51N Trip
50N Pickup
50N Trip
46 Pickup
46 Trip
49 Pickup
49 Trip
51P Trip
50P-1 Trip
50P-2 Trip
51N Trip
50N Trip
46 Trip
49 Alarm
49 Trip
Trip Lockout
Definate Trip Alarm
Shot Due
AR Lockout
CB Pos Open
CB Pos CLosed
DI1
DI2
DI3
DI4
DI5
Arc Trip
Arc light output
51P Pickup
51P Trip
50P-1 Pickup
50P-1 Trip
50P-2 Pickup
50P-2 Trip
51N Pickup
51N Trip
50N Pickup
50N Trip
46 Pickup
6Trip
49 Alarm
49 Trip
Ext Trip
Open CB Cmd
Close CB Cmd
Definate Trip Alarm
CB Reclose Failed
Shot Due
AR Lockout
Arc Trip
Arc light output
Optional digital
outputs
(I/O module)
SGF1...SGF5
1MRS 755535
Feeder Protection Relay
Technical Reference Manual - ANSI Version
REF 610
19
4.1.4.2. Overcurrent protection
The non-directional overcurrent protection detects overcurrent caused by phase-to-
phase and phase-to-ground short circuits.
When one or several phase currents exceed the set pickup value of the low-set
element, 51P, the element will generate a pickup signal after a ~ 55 ms. When the
set operate time at definite-time characteristic or the calculated operate time at
IDMT (mode) characteristic elapses, the element will generate a trip signal. Element
51P has a settable resetting time (both at definite-time and IDMT (mode)
characteristics), RSET, for reset coordination with existing electromechanical relays
or for reducing fault clearance times of recurring, transient faults. If element 51P has
picked up and the phase currents fall below the set pickup value of the element, the
pickup of the element will remain active for the set resetting time. If the phase
currents exceed the set pickup value again, while the timer is being reset, the pickup
of the element will remain active. Consequently, the set resetting time ensures that
when the element picks up because of current spikes, it will not be immediately
reset. However, if element 51P has already tripped, the element will be reset in 50
ms after all three phase currents have fallen below 0.5 times the set pickup value of
the element.
The inverse-time function of element 51P can be set to be disabled when element
50P-1 and/or 50P-2 picks up. In this case, the operate time will be determined by
element 50P-1 and/or 50P-2. The selection is made in SGF4. It is possible to block
the tripping of the low-set overcurrent element by applying a digital input signal to
the relay.
When one or several phase currents exceed the set pickup value of the high-set
element, 50P-1, the element will generate a pickup signal after a ~ 30 ms’ pickup
time. When the set operate time at definite-time characteristic elapses, the element
will generate a trip signal. Element 50P-1 can be given an instantaneous
characteristic by setting the operate time to the minimum, i.e. 0.04 s.The set pickup
value of element 50P-1 can be set to be automatically doubled in a pickup situation,
i.e. when the object to be protected is being connected to a network. Consequently,
a set pickup value below the connection inrush current level can be selected for
element 50P-1. A pickup situation is defined as a situation where the maximum
phase current rises from a value below 0.12 x 51P to a value above 1.5 x 51P within
less than 60 ms. The pickup situation ends when all phase currents fall below 1.25 x
51P and remain below for at least 200 ms. The selection is made in SGF4.
It is possible to block the tripping of the high-set overcurrent element by applying a
digital input signal to the relay.
Element 50P-1 can be set out of operation in SGF3. This state will be indicated by
dashes on the LCD and by “999” when the set pickup value is read via serial
communication.
When one or several phase currents exceed the set pickup value of the instantaneous
element, 50P-2, the element will generate a pickup signal after a ~ 30 ms’ pickup
time. When the set operate time at definite-time characteristic elapses, the element
will generate a trip signal. Element 50P-2 can be given an instantaneous
characteristic by setting the operate time to the minimum, i.e. 0.04 s.
20
1MRS 755535
Feeder Protection Relay
Technical Reference Manual - ANSI Version
REF 610
Element 50P-2 can be set out of operation in SGF3. This state will be indicated by
dashes on the LCD and by “999” when the set pickup value is read via serial
communication. Elements 50P-1 and 50P-2 will be reset in 50 ms after all three
phase currents have fallen below the set pickup value of the element.
Note!
Elements 51P and 50P-1 can be set to be blocked by the auto-reclose function.
4.1.4.3. Ground-fault protection
The non-directional ground-fault current protection detects phase-to-ground
currents, caused by insulation failure due to ageing and thermal cycling, for instance.
When the ground-fault current exceeds the set pickup value of the low-set element,
51N, the element will generate a pickup signal after a ~ 60 ms’ pickup time. When
the set operate time at definite-time characteristic or the calculated operate time at
IDMT (mode) characteristic elapses, the element will generate a trip signal. The
low-set element can be given an instantaneous characteristic by setting the operate
time to the minimum, i.e. 0.05 s.
Element 51N has a settable resetting time (both at definite-time and IDMT (mode)
characteristics),RSET, for reset coordination with existing electromechanical relays
or for reducing fault clearance times of recurring, transient faults. If element 51N has
picked up and the ground-fault current falls below the set pickup value of the
element, the pickup of the element will remain active for the set resetting time. If the
ground-fault current exceeds the set pickup value again, while the timer is being
reset, the pickup of the element will remain active. Consequently, the set resetting
time ensures that when the element picks up because of current spikes, it will not be
immediately reset. However, if element 51N has already tripped, the element will be
reset in 50 ms after the ground-fault current has fallen below 0.5 times the set pickup
value of the element.
The inverse-time function of element 51N can be set to be disabled when element
50N picks up. In this case, the operate time will be determined by element 50N. The
selection is made in SGF4.
When the ground-fault current exceeds the set pickup value of the high-set element,
50N, the element will generate a pickup signal after a ~ 40 ms’ pickup time. When
the set operate time at definite-time characteristic elapses, the element will generate
a trip signal. The high-set element can be given an instantaneous characteristic by
setting the operate time to the minimum, i.e. 0.05 s. The element will be reset in 50
ms after the ground-fault current has fallen below the set pickup value of the
element.
The set pickup value of element 50N can be set to be automatically doubled in a
pickup situation, i.e. when the object to be protected is being connected to a network.
Consequently, a set pickup value below the connection inrush current level can be
selected for the element. A pickup situation is defined as a situation where the
ground-fault current rises from a value below 0.12 x 51N to a value above 1.5 x 51N
within less than 60 ms. The pickup situation ends when the current falls below 1.25
x 51N and remain below for at least 200 ms. The selection is made in SGF4.
Element 50N can be set out of operation in SGF3. This state will be indicated by
dashes on the LCD and by “999” when the set pickup value is read via serial
communication.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124
  • Page 125 125
  • Page 126 126
  • Page 127 127
  • Page 128 128
  • Page 129 129
  • Page 130 130
  • Page 131 131
  • Page 132 132
  • Page 133 133
  • Page 134 134
  • Page 135 135
  • Page 136 136
  • Page 137 137
  • Page 138 138
  • Page 139 139
  • Page 140 140
  • Page 141 141
  • Page 142 142
  • Page 143 143
  • Page 144 144
  • Page 145 145
  • Page 146 146
  • Page 147 147
  • Page 148 148
  • Page 149 149
  • Page 150 150
  • Page 151 151
  • Page 152 152
  • Page 153 153
  • Page 154 154
  • Page 155 155
  • Page 156 156
  • Page 157 157
  • Page 158 158

ABB RELION REF610 Technical Reference Manual

Type
Technical Reference Manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI