VENTS-US VKP 150 Specification

Type
Specification
VKP SERIES
The external rotor motor on ball bearings and the backward
curved, balanced impeller is suitable for high pressure
application, prevent vibration and assure quiet operation.
The fan’s housing is made of galvanized steel.
VKP 125/125*2 and VKP 150/150*2 models are available
with two inlets.
VKP
fans are specially designed for extract and input
ventilation and are perfect air movement solution for areas
with tight spaces. It provides small to medium airflow.
From 104 cfm to 360 cfm.
VKP
series is suitable for a wide
range of residential and light commercial applications. The
fans offer a variety of choices of extract and input ventilation
options and enables ducting from multiple sources.
Suitable for low ceilings and tight spaces.
Hinges provide quick and fast access to the motor.
Easy, two step, one hand installation.
Excellent aerodynamics & Low noise
Housing
Installation benefits
Installation example
CENTRIFUGAL IN-LINE FANS
Tel: 888-640-0925
513-348-3853
Fax: 513-268-4597
VentsUS.com
11013 Kenwood Road,
Cincinnati, Ohio 45242
Performance
Specification
Voltage: 120 V, 60 Hz
Motor: Single-phase asynchronous motor
Duct compatibility:
Ø 4”, 5”, 6”
Airflow capacity: up to 290 CFM
Power consumption: 105 – 117 W
Suitable for working airstreams up to 13-140 °F
IPX4 protection
Thermal overload protection
Five year warranty
Flow Chart Graphs can be viewed at VentsUS.com/ /cat/507/
D
D1
D
B
B
H
H
L
L
D1
2013/03
Contacts
Tel: 888-640-0925 Tel: 513-348-3853
Fax: 513-268-4597
VentsUS.com
11013 Kenwood Road Cincinnati, Ohio 45242
VENTS – US reserves the rights to modify any of its products features,
designs, components, and specifications at any time and without notice to
maintain the development and qualit
y of manufactured goods.
Pic. 2 Twin intake fan
Pic. 1 One Intake
Performance certified is for installation type D – Ducted inlet, Ducted outlet. Speed (RPM) shown is nominal. Performance is based on actual speed of test. Use this statement only when nominal speed is catalogued. Performance
ratings do not include the effects of appurtenances (accessories).
Model Measurements [in.]
Picture
Ø D Ø D1 L B H
VKP 100
3
15/16
15/16
3 13
7/8
7/8
9
3/8
6
1
VKP 125
4
7/8
7/8
4 16
3/16
12
3/16
1/2
7
1
VKP 150
5
7/8
7/8
5 18
3/16
15
7/16
1/2
7
1
VKP 125/125*2
4
7/8
7/8
4 16
3/16
12
3/16
1/2
7
2
VKP 150/150*2
5
7/8
7/8
5 18
3/16
15
7/16
1/2
7
2
Dimensions
Model
Duct
dia
Watts*
Amps*
CFM vs. Static Pressure (Ps) in WG
Max.
Ps
Volts /
Hz
0” 0.1” 0.2” 0.3” 0.4” 0.5” 0.6” 0.7” 0.8” 0.9” 1”
VKP 100
4” 30
0.27
104 98 94 89 84 77 69 61 52 43 33
1.2 120 / 60
VKP 125
5” 67
0.56
212 208 201 192 182 172 162 152 142 132 120
1.6 120 / 60
VKP 125/125*2
5” / 5” 74
0.61
244 234 223 213 204 194 183 170 160 150 140
1.9 120 / 60
VKP 150
6” 102 0.85 295 287 278 270 260 251 242 233 225 215 206 3.0
120 / 60
VKP 150/150*2
6” /
6”
119 1 360 348 332 316 302 289 272 259 245 323 220 3.0
120 / 60
* Indicated at 0.2 in.W.G.