Royal Sovereign ARP-1200M User manual

Category
Mobile air conditioners
Type
User manual

This manual is also suitable for

Royal Sovereign ARP-1200M is a portable air conditioner that can cool, dehumidify, and circulate air in rooms up to 400 square feet. It features two fan speeds, adjustable louvers for directing airflow, a 24-hour timer, and a remote control for added convenience. The ARP-1200M also has an energy-saving mode that automatically adjusts its cooling power based on the ambient temperature, and a washable and reusable air filter to help keep the air clean.

Royal Sovereign ARP-1200M is a portable air conditioner that can cool, dehumidify, and circulate air in rooms up to 400 square feet. It features two fan speeds, adjustable louvers for directing airflow, a 24-hour timer, and a remote control for added convenience. The ARP-1200M also has an energy-saving mode that automatically adjusts its cooling power based on the ambient temperature, and a washable and reusable air filter to help keep the air clean.

Royal Centurian Inc.
ARP-1200M / ARP-1200DM / ARP-1200E / ARP-1200DE
OWNER’S MANUAL
MANUAL DEL PROPIETARIO
PORTABLE AIR CONDITIONER
ACONDICIONADOR DE AIRE PORTÁTIL
Read and retain these instructions for future reference
Lea y tenga presente estas instrucciones para futuras consultas
PORTABLE AIR CONDITIONER
Model ARP-1200M / ARP-1200DM / ARP-1200E / ARP-1200DE
BEFORE USE
GENERAL SAFETY
Only use in the upright position on a flat, level surface at least 20”/50cm from any object (fig 1 & 4).
Do not place objects on the unit or restrict air inlet / outlet (fig. 2).
Closely supervise children and pets while unit is in use.
ELECTRICAL SAFETY
For indoor use only.
Turn off and unplug the unit when it is not in use.
Do not use in wet environments (fig 3).
Do not pull the unit by the cord.
If the supply cord is damaged, it must be replaced by an
electrician or qualified person, to avoid hazard or injury.
FOR MAXIMUM EFFICENCY
Do not exceed the recommended room size 400 sq. feet.
Close doors and windows.
Keep curtains or blinds closed during the sunniest
part of the day.
Keep filters clean.
Once room has reached the desired conditions, reduce
temperature and ventilation settings.
3
FIG.3
FIG.1 FIG.2
FIG.4
ARP-1200M / ARP-1200DM
ARP-1200E / ARP-1200DE
4
Front
1. Control Panel
2. Air outlet
3. Carrying handle
4. Caster
Back
5. Air filter
6. Air inlet
7. Exhaust air outlet
8. Cord storage &
power cord with
LCDI breaker plug
and reset buttons.
9. Water stopper /
drainage point
PARTS
Accessories
10. Air Conditioner adaptor - for insertion over hose and into back of the air conditioner.
11. Window adaptor - for insertion over hose and into window spacer.
12. Exhaust hose
13. Extendable window spacer.
14. Drain tube for continuous drainage
15. Water tray
16. Remote control (for electronic type only)
14
12
11
10
15
13
5
1
2
3
4
6
7
8
9
16
5
ARP-1200M / ARP-1200DM
ARP-1200E / ARP-1200DE
INSTALLATION
Installation of the exhaust pipe
The unit is a portable air conditioner that may be moved from room to room.
Please follow the steps for installation:
1. Feed the outward adapter through the extendable window spacer.
2. Screw the exhaust hose into the outward adapter.
3. Insert the window spacer into window gaps as shown.
Adjust its length if necessary.
4. Slide window across so that the spacer is held securely.
NOTE: Take care to maintain protection against intruders
NOTE: Install window vent vertically or horizontally depending on window style.
Window Spacer may be cut to fit. If window spacer does not fill opening
completely a custom made spacer from your local home improvement store
can be made.
Extendable
window
spacer
FIG.5
FIG.6
FIG.7
Outward Adapter
Mounting of the exhaust pipe
Using only the hose provided, screw unit adapter to exhaust hose then clip the unit adaptor to the back of the air conditioner.
Avoid kinks and bends in the exhaust hose as this will cause expelled moist air to build up causing the
unit to overheat and shut down. (Fig 8 & 9 show correct position).
NOTE: For best results do not exceed a 45º angle.( Fig 10)
The hose may be extended from 1-5 ft /300mm -1500mm but for maximum efficiency use the shortest straightest length possible.
It is not recommended to exceed 5 feet for this will diminish the efficiency of the unit. See WARNING Figure 11
6
WARNING
The length of the exhaust pipe is specially designed according to the
specification of this product. Do not replace or lengthen it with your own
hose as this will cause the unit to malfunction.
FIG.8 FIG.9 FIG.10
FIG.11
Installation of the carbon filter
1. Remove the filter frame from the unit.
2. Separate the filter fixer from the filter frame.
3. Remove the active carbon filter from its plastic bag.
4. Insert the active carbon filter into the filter frame.
5. Fix the filter by reassembling the fixer to the filter frame.
6. Re-fit the filter frame inside the unit.
7
1. Power indicator
2. Fan operating indicator
3. Cooling operating indicator
4. 'Full water' indicator
5. Heating operating indicator (ARP-1200DM only)
6. Timer (1-8 hours) as well as ON/OFF Switch
7. Speed switch with options for - FAN, LOW COOL, HIGH COOL, LOW HEAT, HIGH HEAT.
8. Thermostat
OPERATION for mechanical unit
ARP-1200M/ ARP-1200DM
FIG.12
ARP-1200M / ARP-1200DM
ARP-1200E / ARP-1200DE
8
Turning ON/OFF
Set the TIMER to ON position for continuous operation (the unit will operate as long as it is not turned off).
Power indicator comes on.
To turn off the unit, turn the TIMER to the OFF position.
Setting function / ventilation speed
Cooling only models (ARP-1200M and ARP-1200E)
Turn the speed switch to select required setting: LOW FAN, HIGH FAN, LOW COOL, HIGH COOL
Cooling & heating models (ARP-1200DM and ARP-1200DE)
Turn the speed switch to select required setting: FAN, LOW COOL, HIGH COOL, LOW HEAT, HIGH HEAT
Setting temperature
Turn the THERMOSTAT to regulate the temperature desired: The cooling intensity increases clockwise..
Set timer
Set the TIMER to the desired operating time (1 to 8 hours). When the set time has been reached, the machine will shut off automatically.
Regulating air flow direction
Turn the roller on the air vent to control the air flow direction of the vertical louvers.
Move the air vent directly to adjust the air flow direction of the horizontal louvers.
NOTE: 1. To lengthen the compressor's life, when the unit is turned off wait at least 3 minutes before turning it back on.
2. The cooling system will turn off if the ambient temperature is lower than the set one. The ventilation, however,
keeps working on the set level. If the ambient temperature rises above the selected level, the cooling function will resume.
3. On the contrary, the heat will turn off if the ambient temperature is higher than the set one (still, the ventilation keeps working on
the set level). As the ambient temperature drops below the selected level, the heating function will resume.
4. This machine is equipped with an ANTI-FROST function. While using the heating function in low temperatures, sometimes the
heat will stop for a while in order to melt the frost. As this occurs, just wait for the heating function to resume.
FIG.13
FIG.14
FIG.15
9
Turning ON/OFF
Press ON/OFF button, the unit will start automatically. If the ambient temperature is
- Higher than 75
o
F / 24
o
C, the unit will work in cooling mode.
- Higher than 68
o
F / 20
o
C, but below or equal to 75
o
F / 24
o
C, the unit will work in ventilation mode.
- Below 68
o
F / 20
o
C, the unit will work in heating mode (Only for units ARP-1200 DM/DE)
Indicators of the functions in progress will be lit. *NOTE: The COMPRESSOR indicator will only light up when the compressor is in operation.
The display window shows the ambient room temperature.
To turn the unit off, press the ON/OFF button again.
Setting mode/function
Press MODE button to select required working mode: automatic, cooling, fan or heating,
(heating is only available for units ARP-900DE and ARP-900DM). The indicator of your selected mode will be lit.
Auto mode is factory preset at 75 degrees. When in auto mode(auto and cool light illuminated) the temp up and temp down buttons are
disabled and you cannot set a desired temperature. If you want a desired temperature above or below 75 run unit in cool mode and set your
desired temperature by pressing the temp up or temp down buttons.
OPERATION for electronic unit
Control panel
1. 'Heating operation indicator (For ARP-DM, ARP-DE)
2. Fan operation indicator
3. Cooling operation indicator
4. Automatic mode indicator
5. ' Set temperature' indicator
6. 'Room temperature' indicator
7. High ventilation indicator
8. Low ventilation indicator
9. Timer operation indicator
10. Sleep function indicator
11. Compressor operation indicator
12. Mode (function) option button
13. 'Temperature up' button
14. 'Temperature down' button
15. Speed (ventilation) button
16. Sleep button
17. Timer button (1~12 hours)
18. ON/OFF(power) button
19. Receiver
20. Display window
FIG.16
ARP-1200M / ARP-1200DM
ARP-1200E / ARP-1200DE
Setting temperature
Press the 'Temperature up' or 'Temperature down' button to regulate the temperature desired.
The display window will show the temperature which you have set as you press the 'Temperature up' or 'Temperature down' button.
Otherwise, it will always show the ambient temperature.
The preset temperature of this machine is: 75
o
F / 24
o
C / for cooling, 68
o
F / 20
o
C for heating.
Setting ventilation speed
1. Press the SPEED button to choose the ventilation speed needed, high or low. The indicator of high or low
ventilation will light up at the same time.
2. If the unit is in AUTO mode, it will choose the ventilation speed automatically according to the ambient temperature (the related
indicators will light up: at this time, the speed switch is invalid).
Setting timer
1. Press the TIMER button to set the operating hours desired (1 to 12 hours, the timer indicator will light on).
When the set time has been reached, the machine will turn off automatically.
The display window will show the hour(s) you set as you press the TIMER button. If the timer button is not pressed,
the unit will work continuously.
2. By pressing the timer but without turning on the other functions, you can PRESET the time for the machine to start.
For example, if you press the timer to '2', the unit will start automatically after 2 hours.
Sleep function
1. By pressing the SLEEP button, the set temperature will increase 2
o
F /1
o
C / in the 1st hour, another 2
o
F / 1
o
C in the second hour,
then remains at that temperature.
2. By pressing the SLEEP button again, the temperature setting will return to the pre-selected one.
3. The unit will automatically turn off after the SLEEP function runs for 12 hours.
All the above functions can also be performed with the supplied remote control.
The remote control requires 2 AAA batteries to operate.
10
FIG.17
Regulating air flow direction
Turn the roller on the air vent to control the air flow direction of the vertical louvers.
Move the air vent directly to adjust the air flow direction of the horizontal louvers.
NOTE: 1. To lenghten the compressor's life, after turning off the unit, please wait at
least 3 minutes before turning it back on.
2. The cooling system will switch off if the ambient temperature is lower than the set one. The ventilation, however, keeps working at the
set level. If the ambient temperature rises above the selected level, the cooling function will resume.
3. On the contrary, the heat will switch off if the ambient temperature is HIGHER than the set one (still, the ventilation keeps working at
the set level). As the ambient temperature drops below the selected level, the heating fu nction will reume.
4. This machine is equipped with ANTI-FROST function. While using the heating function in low temperatures, sometimes the heat will
stop for a while in order to melt the frost. As this occurs, just wait for the heating function to resume.
DRAINAGE
Although the unit is self evaporating, during high humidity levels excess water may fill the internal water tray. Depending on how high the humidity
and the duration of high humidity levels will depend on how often the unit needs to be drained. When the reservoir full :
a. For the mechanical model, the compressor will stop, only the fan ill continue to circulate the air. The 'FULL WATER' indicator will light up.
b. For the electronic model, both of the compressor and motor will stop. The COMP. indicator light will flash.
To resume the cooling function, empty the water by the following steps:
1. Turn off the air conditioner and avoid moving it when full.
2. Position the water tray underneath the drain hole.
3. Remove the drain knob & rubber plug from the drain hole and allow the water to drain out.
4. When the water tray is almost full, replace the rubber plug in the drain hole and empty
the water tray.
5. Repeat until the unit is emptied.
6. Replace the rubber plug and tighten the drain knob firmly.
7. Turn on the unit - the comp light should not be flashing.
11
FIG.18
FIG.19
ARP-1200M / ARP-1200DM
ARP-1200E / ARP-1200DE
Drain hole
Rubber plug
Drain knob
12
If you wish to operate the unit without the need to empty the water tank, please:
Remove the drain knob and rubber plug and retain for future use.
Connect the drain tube supplied to the water outlet as shown and locate
the other end into a drain.
The drain tube may be extended by adding an extension tube and using a
suitable connector.
Please note
1. The drain must be at or below the outlet level.
2. Flashing comp / 'full water' indicator will not function in this mode of drainage.
3. If you want to extend the water tube, you can connect it with another tube
(OD: .7" / 18mm)
Caution for heating function:
While using the heating function, please note:
1. In heat mode the exhaust MUST be exhausted to the outside just as in air conditioning
mode. The unit works in reverse of air conditioning mode with the warm air out the front
and cold air is exhausted out the back.
2. Fix the drainage to be a continuous one (i.e. drain the water by water tube).
3. Working range for heating function is 41
o
- 80.6
o
F (5
o
- 27
o
C) and for the cooling
function, it is 64
o
- 89
o
F (18
o
- 32
o
C). For temperatures outside of this range, the
unit will not work properly.
rubber plug
drain knob
drain tube
original water tube
FIG.20
FIG.21
FIG.22
13
MAINTENANCE
Always unplug the air conditioner from the outlet before cleaning.
To maximize the efficiency of the air conditioner clean regularly.
Cleaning the housing
Use a soft, damp cloth to wipe the body clean.
Never use chemicals, gasoline, detergents, chemically treated cloths, or other cleansing solutions, as such could possibly damage the cabinet.
Cleaning the filter
Use a vacuum cleaner or tap the filter lightly to remove loose dust and dirt, then rinse thoroughly under running water (no hotter than 104
o
F/40
o
C).
Dry thoroughly before replacing.
NOTE: Never operate the unit without the filters.
End of season storage
Drain any water from the unit. Operate the unit in fan mode only for a few hours to thoroughly dry the inside.
Clean or change the filter.
Unplug and store the power cord as shown
Replace in the original carton or cover for storage..
Always maintain the unit in an upright position.
FIG.23
ARP-1200M / ARP-1200DM
ARP-1200E / ARP-1200DE
Cord
14
TROUBLE SHOOTING
* Never try to repair or dismantle the unit yourself
The compressor doesn't run:
Too noisy:
The machine seems to do nothing:
The machine seems to do little:
The air conditioner does not run:
It is possible that the overheat protection of the compressor is on. Just wait for the
temperature to drop.
Is the machine positioned unevenly Creating Vibration?
Is the floor underneath the machine uneven?
Is the filter dusty or contaminated?
Is the air intake or output blocked up?
Is the room temperature below your selected temperature?
Is there direct light? (Please pull down the curtain.)
Are too many windows or doors open?
Are there too many people in the room?
Is there something in the room producing heat?
Is the air conditioner plugged in?
Reset plug breaker by pressing reset buttons until green light is illuminated on plug.
Is there a power failure?
Is the comp / 'full water' indicator flashing?
Is the room temperature below the set temperature?
15
SPECIFICATION FOR ARP-1200 UNITS
MODEL ARP-1200M ARP-1200DM ARP-1200E ARP-1200DE
Voltage/Hz 115V / 60Hz
Cooling (BTU/hr) 12000
Heating (BTU/hr) N/A 12500 BTU’s N/A 12500 BTU’s
Power/Ampere for cooling 950 W / 8.7 A
Power/Ampere for heating N/A 930 W / 8.6 A N/A 930 W / 8.6 A
Refrigerant R22
Control manual manual electronic w/ remote electronic w/ remote
Carton weight 73 (lbs) 33 (kg)
Carton Dimension (W x H x D) 19.7 x 15.7 x 29.5 (in) 500 x 400 x 750 (mm)
Noise Level 54.1 dB(A)
NOTE: 1. Heating capacity is only for the models with the heating function, i.e. model no. ARP-1200 DM & ARP-1200 DE.
2. Measuring condition for above is: Cooling - RT 80.6 °F (27
o
C), RH60%
Heating - RT 68 °F (20
o
C), RH60%
ARP-1200M / ARP-1200DM
ARP-1200E / ARP-1200DE
16
FULL ONE YEAR WARRANTY
Royal Sovereign warrants each Portable Air Conditioner to be free from defects in material and workmanship. Our obligation under this warranty is limited to
the repair or replacement, free of charge, when delivered to an authorized Royal Sovereign service center, of any defective part(s) thereof, other than parts
damaged in transit. This warranty is in effect to the original purchaser, for a period of one year from the date of purchase and is not transferable. This warranty
shall apply only if the air conditioner is used on Alternating Current (AC) circuit, in accordance with the factory provided instructions which accompany it.
LIMITED FIVE YEAR WARRANTY (COMPRESSOR)
For a period of five years from the date of purchase, when this Royal Sovereign Portable Air Conditioner is operated and maintained according to the
instruction manual provided with the product, Royal Sovereign will supply a replacement compressor (part only), free of charge, if the original compressor is
determined to be defective in workmanship or material. If repair becomes necessary, please contact our customer service center. You will be responsible for all
freight, insurance, and any other transportation charges to get the unit to our factory or service center. If shipping is required, be sure to pack the unit properly
to avoid shipping damages, as we will not be responsible for such damages.
THIS WARRANTY IS VALID THROUGHOUT THE UNITED STATES AND PUERTO RICO ONLY
EXCLUSIONS
This warranty excludes and does not cover defects, malfunctions or failures of your Royal Sovereign Portable Air Conditioner, caused by repairs by
unauthorized persons or service centers, mishandling, improper installation, modification or unreasonable use including incorrect voltage, acts of god, or failure
to provide reasonable and necessary maintenance.
This warranty is in lieu of any and all expressed warranties. In no event shall Royal Sovereign be liable for consequential or incidental
damages. Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion
may not apply to you. This warranty gives you specific legal rights and you may also have other rights which vary from state to state.
ROYAL SOVEREIGN INTERNATIONAL, INC.
Royal Centurian Inc.
2 Volvo Drive, Rockleigh, NJ 07647 USA
TEL : +1) 201-750-1020, 800-397-1025 FAX : +1) 201-750-1022
RS International Australia PTY. LTD. Royal Sovereign Canada
30 Prime Drive, Seven Hills, NSW 2147, AUSTRALIA 164 Oakdale Road, Toronto, Ontario M3N 2S5 CANADA
TEL : +61) 2-9674-2127 FAX : +61) 2-9674-2027 TEL: +1) 416-741-8400 FAX: +1) 416-741-8185
www.royalsovereign.com / [email protected]
Royal Centurian Inc.
ARP-1200M / ARP-1200DM / ARP-1200E / ARP-1200DE
MANUAL DEL PROPIETARIO
ACONDICIONADOR DE AIRE PORTÁTIL
Lea y tenga presente estas instrucciones para futuras consultas
AIRE-CONDICIONADO PORTABLE
Model ARP-1200M / ARP-1200DM / ARP-1200E / ARP-1200DE
ANTES DE USAR LA UNIDAD
ANTES DE USAR LA UNIDAD
LA UNIDAD DEBE USARSE SÓLO EN POSICIÓN VERTICAL SOBRE UNA SUPERFICIE HORIZONTAL LISA Y SEPARADA POR
LOS MENOS 20”/50cm DE OTROS OBJETOS (Fig. 1 a 4).
NO COLOQUE OBJETOS SOBRE LA UNIDAD NI RESTRINJA LA ENTRADA/SALIDA DE AIRE (FIG. 2).
VIGILE ATENTAMENTE A LOS NIÑOS Y MASCOTAS MIENTRAS LA UNIDAD ESTÁ FUNCIONANDO.
SEGURIDAD ELÉCTRICA
LA UNIDAD DEBE USARSE SÓLO EN INTERIORES.
APAGUE Y DESENCHUFE LA UNIDAD CUANDO NO SE
USA.
NO LA USE EN AMBIENTES HÚMEDOS (FIG 3).
NO ARRASTRE LA UNIDAD TIRANDO DEL CORDÓN DE
ALIMENTACIÓN ELÉCTRICA.
SI EL CORDÓN DE ALIMENTACIÓN ELÉCTRICA ESTÁ
DAÑADO, DEBE REEMPLAZARLO UN ELECTRICISTA
COMPETENTE PARA EVITAR RIESGOS O LESIONES.
PARA LOGRAR EL RENDIMIENTO MÁXIMO
No exceda el tamaño recomendado de la habitación:
164 pies cúbicos/50m3
(normalmente 66 pies cuadrados/20m2 de área útil).
Cierre puertas y ventanas.
Mantenga ventanas y persianas cerradas durante las
horas más soleadas.
Mantenga limpios los filtros.
Cuando la habitación alcance las condiciones deseadas
reduzca los valores fijados de temperatura y ventilación.
19
FIG.3
FIG.1 FIG.2
FIG.4
ARP-1200M / ARP-1200DM
ARP-1200E / ARP-1200DE
20
Parte delantera
1. Panel de Control (vea en la
página 5 una ilustración
del pane
2. Salida de aire
3. Manija para transporte
4. Rueda giratoria
Parte posterior
5. Filtro de aire
6. Entrada de aire
7. Descarga de la salida
de aire
8. Depósito para el
cordón y Cordón de
alimentación con
enchufe de disyuntor
LCDI y botones de
9. Tapón para el agua /
punto de drenaje
COMPONENTES
Accesorios
10. Adaptador de acondicionador - para conectar a la manguera y a la parte
posterior del acondicionador
11. Adaptador de ventana - para insertar sobre la manguera y en el espaciador de
ventana.
12. Manguera de descarga
13. Espaciador de ventana extensible.
14. Tubo de drenaje para drenaje continuo
15. Bandeja para el agua
16. Control remoto (sólo para el modelo electrónico)
14
12
11
10
15
13
16
5
1
2
3
4
6
7
8
9
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32

Royal Sovereign ARP-1200M User manual

Category
Mobile air conditioners
Type
User manual
This manual is also suitable for

Royal Sovereign ARP-1200M is a portable air conditioner that can cool, dehumidify, and circulate air in rooms up to 400 square feet. It features two fan speeds, adjustable louvers for directing airflow, a 24-hour timer, and a remote control for added convenience. The ARP-1200M also has an energy-saving mode that automatically adjusts its cooling power based on the ambient temperature, and a washable and reusable air filter to help keep the air clean.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI

in other languages