The Mean Well SHP-10K Series is a high-efficiency digital power supply well-suited for various industrial applications, including automation systems, laser processing machines, EV charging stations, and more. It offers a wide 3-phase AC input range (340-530VAC) and provides stable output voltages (55V/115V/230V/380V) with high efficiency up to 97%. The SHP-10K Series supports various cooling methods, including forced-air and water cooling, allowing for operation in ambient temperatures up to 70°C.

The Mean Well SHP-10K Series is a high-efficiency digital power supply well-suited for various industrial applications, including automation systems, laser processing machines, EV charging stations, and more. It offers a wide 3-phase AC input range (340-530VAC) and provides stable output voltages (55V/115V/230V/380V) with high efficiency up to 97%. The SHP-10K Series supports various cooling methods, including forced-air and water cooling, allowing for operation in ambient temperatures up to 70°C.

Model Encoding
Description
Features
3 3-wire / 340~530VAC wide input range ψ
without Neutral
High efficiency up to 97%
Water / forced air cooling selectable
Built-in CANBus/Optional PMBus/MODBus-RTU/RS-485 protocol
Output voltage and constant current level programmable
Active current sharing up to 4 units(40KW)
Built-in remote ON-OFF control / Auxilary power / Alarm signal
Protections: Short circuit / Overload / Over voltage /
Over temperature / Fan fail
5 years warranty
Energy & power system for automation
U.V or laser diode application
Electrolysis system
Laser processing machine
Burn-in facility
RF application
EV charging station
Applications
File Name:SHP-10K-SPEC 2022-07-27
SHP -- 10K 115
Output voltage (55V/115V/230V/380V)
Output wattage
Series name
UL62368-1 TPTC004 IEC62368-1EN62368-1
Bauar
Sicherheit
egel gema
tgepruft
od
be
www.
ID 2000000000
tuv.com
wac g
os
SHP-10K is a 10KW C/DC power supply. This series operates for the wide range three input A33Wψ
phase AC input (3 phase 3 wire / 340~530VAC) and offers the models with DC n eutral is not needed,
outputs (55V/115V/230V/380V) that mostly demanded by various industries. Two types of cooling
methods, forced air and water cooling, that can be working at ambient temperature up to 70 Moreover,
.
SHP-10K provides vast design flexibility by equipping various built-in functions such as output
programming, active current sharing, remote ON-OFF control, auxiliary power, and communication
protocols, that will not only satisfy marker demand, but also enhance automation purpose.
Communication protocol option
L: Water cooling
Blank: Forced air cooling
{
Type Communication Protocol
Blank CANBus
PMBus
MODBus-RTU/RS-485
Note
In Stock
-PM
-MOD
By request
By request
8.3 8.5
Dimension Dimension
L L
460 460
18.1 18.1
W W
211 216
H H
83.5 83.5(2U) (2U)
(2U) (2U)
mm mm
inch inch3.29 3.29
* *
* *
* *
* *
* *
* *
Ordering No.: HS-684
Forced-air cooling: Blank type Water cooling: L type
Front Front
Back Back
User’s Manual
https://www.meanwell.com/serviceGTIN.aspx
MW Search:
GTIN CODE
Video
10KW Power Supply3 3W High Efficiency Digitalψ
SHP-10K series
SPECIFICATION
File Name:SHP-10K-SPEC 2022-07-27
MODEL
DC VOLTAGE (factory default)
CURRENT (factory default)
CURRENT RANGE
RATED POWER (max.)
FULL POWER VOLTAGE RANGE
OUTPUT VOLTAGE ADJ. RANGE
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
VOLTAGE RANGE
Note.4
FREQUENCY RANGE
EFFICIENCY (Typ.)
Note.6
INPUT
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
OVER TEMPERATURE
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
MTBF
DIMENSIONOTHERS
NOTE
PACKING
OVER LOAD
OVER VOLTAGE
AC CURRENT (Typ.)
3000ms, 100ms at full load
25ms / 400VAC at 75% load 20ms / 400VAC at full load
3 3-wire / 340 ~ 530VACψ
47 ~ 63Hz
<6.5mA peak / 530VAC
40A/400VAC 65A/480VAC
100 ~ 105% of rated current
Protection type : Constant current limiting, unit will shutdown after 5 sec. re-power on to recover
Protection type : Shut down o/p voltage, re-power on to recover
-30 ~ +70 (Refer to "Derating Curve")
20 ~ 90% RH non-condensing
-40 ~ +85 , 10 ~ 95% RH non-condensing
±℃ ℃0.03%/ (0 ~ 50 )
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
SHP-10K: 460*211*83.5mm (L*W*H) SHP-10K-L: 460*216*83.5mm (L*W*H)
SHP-10K: SHP-10K-L:
11.9Kg; 1pcs/11.9Kg/1.25CUFT /1.1CUFT11.9Kg; 1pcs/11.9Kg
281.2K hrs min. Telcordia SR-332 (Bellcore) ; 28K hrs min. MIL-HDBK-217F (25 )
96%
15.7A/400VAC 13A/480VAC
94.5%
11.2A/400VAC 9.5A/480VAC
145 ~ 166V60.5 ~ 69.1V
96.5%
273 ~ 312V
96.5%
420 ~ 480V
±0.5%±0.5% ±0.5% ±0.5%
±0.5%±0.5% ±0.5% ±0.5%
±1.0%±1.0% ±1.0% ±1.0%
0.6Vp-p0.3Vp-p 1Vp-p 1Vp-p
90 ~ 138V39 ~ 57.6V 170 ~ 260V 260 ~ 400V
115V55V 230V 380V
87A131A 43.5A 26.3A
0 ~ 87A0 ~ 150A 0 ~ 46.3A 0 ~ 30A
10000W7200W
48 ~ 57.6V 115 ~ 138V 216 ~ 260V 334 ~ 400V
10000W 10000W
SHP-10K-115SHP-10K-55 SHP-10K-230 SHP-10K-380
POWER FACTOR (Typ.) 0.98/400VAC/480VAC at full load
SAFETY STANDARDS UL62368-1, CAN/CSA C22.2 , TUV EN62368-1, EAC TP TC 004 approvedBS EN/No. 62368-1
RIPPLE & NOISE (max.)
Note.2
VOLTAGE TOLERANCE
Note.3
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
I/P-O/P:3.75KVAC I/P-FG:2KVAC O/P-FG:1.25KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH
ENVIRONMENT
SAFETY &
FUNCTION
EMC
(Note 5,7)
PROTECTION
Shut down o/p voltage, recovers automatically after temperature goes down
Parameter
Parameter
ESD
Radiated
EFT / Burst
Surge
Conducted
Magnetic Field
Voltage Dips and Interruptions
Conducted
Radiated
Harmonic Current
Voltage Flicker
EN55024 , EN61204-3, EN61000-6-2
Standard
Standard
BS EN/EN55032 (CISPR32) / EN55011 (CISPR11)
BS EN/EN55032 (CISPR32) / EN55011 (CISPR11)
BS EN/EN61000-3-2
BS EN/EN61000-3-3
BS EN/EN61000-4-2
BS EN/EN61000-4-3
BS EN/EN61000-4-4
BS EN/EN61000-4-5
BS EN/EN61000-4-6
BS EN/EN61000-4-8
BS EN/EN61000-4-11
Test Level / Note
Test Level / Note
Level 3, 8KV air ; Level 2, 4KV contact
Level 3
Level 3
Level 3
Level 4
>95% dip 0.5 periods, 30% dip 25 periods,
>95% interruptions 250 periods
Class B
Class A
-----
-----
EMC IMMUNITY
EMC EMISSION
ALARM SIGNAL OUTPUT
REMOTE ON-OFF CONTROL
AUXILIARY POWER(AUX)
Please refer to the Function Manual.
AC-OK, DC-OK, Fan Fail. Please refer to the Function Manual.
12V@1A tolerance 5%, ripple 150mVp-p±
CURRENT SHARING Up to 4 units. Please refer to the Function Manual
OUTPUT VOLTAGE PROGRAMMABLE
Can be adjusted via built-in potentiometer
Adjustment of output voltage is allowable between 50 ~ 120% of nominal output voltage. Please refer to the PV curve Function Manual
Adjustment of constant current level is allowable between 20 ~ 100% of rated current. Please refer to the PC Function Manualcurve
CONSTANT CURRENT LEVEL PROGRAMMABLE
Level 4, 4KV/Line-Earth ; Level 3, 2KV/Line-Line
10KW Power Supply3 3W High Efficiency Digitalψ
DC-OK SIGNAL The TTL signal output, PSU turn on = -0.5 ~ 0.5V ; PSU turn off = 3.5 ~ 5.5V. Please refer to the Function Manual
1. All parameters NOT specially mentioned are measured at 0VAC input, rated load and 25 of ambient temperature.40
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance :includes set up tolerance, line regulation and load regulation.
4. Derating may be needed under low input voltages. Please check the for more details.derating curve
5. Additional EMI filter is needed to meet regulations of EMC conducted and radiated emission. Characteristics of EMI filter please refer to the table, Minimum
Insertion Loss.
6. The efficiency is measured at 480VAC input.
7. The power supply is considered a component which will be installed into a final equipment. All the EMC tests are been executed by mounting the unit on
a mm* mm metal plate with 1mm of thickness. The final equipment must be re-confirmed that it still meets EMC directives.600 900 For guidance on how to
perform these EMC tests, please refer to EMI testing of component power supplies. (as available on http://www.meanwell.com)
8. The ambient temperature derating of 3.5 /1000m with fanless models and of 5 /1000m with fan models for operating altitude higher than 2000m(6500ft).℃℃
9. If use PV signal to adjust Vo, under certain operations conditions, ripple noise of Vo might slightly go over rating defined in this specification.
10.Under light load condition, output voltage ripple will exceed specification. The behavior can be minimized by increasing the load.
Product Liability Disclaimer For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx
SHP-10K series
File Name:SHP-10K-SPEC 2022-07-27
BLOCK DIAGRAM
10KW Power Supply3 3W High Efficiency Digitalψ
PFC fosc : 60KHz
PWM fosc : 70KHz
I/P RECTIFIERS
&
FILTER
SWITCHING
CONTROL
POWER
PWM
RECTIFIERS
FILTER
EMI
CIRCUIT
DETECTION
POWER
AUX
ISOLATOR
ATOR
ISOL
&
PFC
FILTER
&AUX POWER
(12V/1A)
MCU
MCU
O.V.P.
O.T.P.
MCU
DA/DB
PV/PC
PV/PC ENABLE
DC-OK
(SDA/SCL)
(CANH/CANL)
(DATA+/DATA-)
T-ALARM
AC-OK
REMOTE ON-OFF
RECTIFIERS
TRANSCEIVERS
DATA
ISOLATION
O.L.P.
-V
+V
CIRCUIT
DETECTION
SHP-10K series
FAN
(Fan cooling model only)
DERATING CURVE
AMBIENT TEMPERATURE WITH WATER COOLING SYSTEM ( )
LOAD (%)
AMBIENT TEMPERATURE WITH 85CFM FAN*2
FAN-FAIL
LOAD (%)
Blank Type:
L Type:
20
20 20
40
40 40
25
60
60 60
50
50 50
80
80 80
100
100 100
-30
-30 -30
0
0 0
10
10 10
20
20 20
30
30 30
40
40 40
50
50 50 55
60
60 60
70
70 70
(HORIZONTAL)
(HORIZONTAL) (HORIZONTAL)
AMBIENT TEMPERATURE ( )
for 55V
for other
File Name:SHP-10K-SPEC 2022-07-27
10KW Power Supply3 3W High Efficiency DigitalψSHP-10K series
STATIC CHARACTERISTICS
100
90
80
70
60
50
LOAD (%)
INPUT VOLTAGE (V) 60Hz
340 360 380 400 420 440 460 480 500 525 530
LOAD (%)
20
40
60
80
100
-40 -25 0 20 30 40 50 60
(HORIZONTAL)
Tcase ( )
Fig 1.1
AC Power Connection
Fig 1.2
◎ψ3 3-wire / 340VAC~530VAC
340V~530VAC
340V~530VAC
TSHP-10K
SHP-10K
S
RFG
L1
L2
L3
◎ψ3 3-wire / Y 340VAC~530VAC
T
S
R
FG
L1
L2
L3
340V~530VAC
340V~530VAC
EFFICIENCY (%)
LOAD
EFFICIENCY VS LOAD (380V MODEL)
65
70
75
80
85
90
95
97
100
10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
480VAC & 3 VDC80
400VAC& 3 VDC80
480VAC& 3 VDC34
400VAC& 3 VDC34
for other
for 55V
L Type:
(Main Adjustments)
(Fine adjustments)
DIP SW1
Fig 1.1
LOAD
+V
-V
PIN3,4 PV+
PIN1,2 -V(Signal)
EXTERNAL VOLTAGE (DC)(0~5V)
CN86
CN53
DIP SW
DIP
SW81
Fig 1.2
The rated current should change with the Output Voltage Programming accordingly.
100
40
60
70
80
83.3
20
V
OUTPUT VOLTAGE
103.5
300.6
194.4
57.5 115V
167 380V
108 230V
43.2
115
334
216
48
138
400
260
57.6
24 55V
OUTPUT CURRENT (%)
Function Manual
(a)Have the DIP switch position-3 set as
(a)Have the DIP switch position-3 set as
(b)Output voltage can be trimmed by SVR.
(b)The output voltage can be trimmed to 50~120% by applying EXTERNAL VOLTAGE between and on CN53.PV+ PV-
(1)Default by potentiometer (SVR)
(2)By Output Voltage Programming
1.Output Voltage Programming (or, PV / remote voltage programming / remote adjust / margin programming / dynamic voltage trim)
File Name:SHP-10K-SPEC 2022-07-27
10KW Power Supply3 3W High Efficiency DigitalψSHP-10K series
50
OUTPUT VOLTAGE(%)
EXTERNAL VOLTAGE (DC)
100
120
Vout
014
4.41
4.37
V
OUTPUT VOLTAGE(%)
4.7
4.8
113.7
114.5
106.5 380V(Default)
55V(Default)
230V(Default)
Non-Linear
he 100% output voltage is 48/115/216/334V.T
L type Blank type
ON
ON
OFF
OFF
123
123
Fig 2.2
File Name:SHP-10K-SPEC 2022-07-27
2.Constant Current Programming (or, PC / remote current programming / dynamic current trim)
Non-Linear
(HORIZONTAL)
T1T2
20
40
50
60
80
100
AMBIENT TEMPERATURE ( )
LOAD (%)
20
OUTPUT CURRENT(%)
100
110
Iout
0
EXTERNAL VOLTAGE (DC)
1
4.7
V
4.8
Non-Linear
10KW Power Supply3 3W High Efficiency DigitalψSHP-10K series
T : Maximum ambient temperature of full load.1(Typ.)
T : T1+5 .2(Typ.)
Ac ituto de-rating function overed by over temperature protection, works either in PC mode or under control by communication protocol.
Under PC function at wattage < 4KW, the power supply might enter burst mode and cause output unstable, please increase the load to minimized the effect.
(a)Have the DIP switch position-2 set as
(b)Output current is set default value.
(1)Default Overload Protection(OLP) value
(2)By Constant Current Level Programming
(a)Have the DIP switch position-2 set as
(b)The constant current level can be trimmed to 20~100% of the rated current by applying EXTERNAL VOLTAGE between and on CN53.PC+ PC-
Fig 2.1
DIP SW1
LOAD
+V
-V
PIN1,2 -V(Signal)
EXTERNAL VOLTAGE (DC)(0~5V)
CN86
CN53
PIN5,6 PC+
SVR
DIP
SW81
he 100% output current is 150/87/46.3/30A.T
ON
ON
OFF
OFF
123
123
File Name:SHP-10K-SPEC 2022-07-27
3.DA, DB signal and parallel control function
10KW Power Supply3 3W High Efficiency DigitalψSHP-10K series
(a)set the DIP switch of postion-1 as
(b) .By default, non-parallel operation
(1)Non-parallel operation
(2)Default parallel operation
(a)set the DIP switch of postion-1 as
(b)PSUs are configured in parallel operation.
Fig 3.1
4.Remote ON-OFF Control
The power supply can be turned ON-OFF by using the "Remote ON-OFF" function.
power supply OFF
Between ( ) and 5V-AUX( 2)Remote ON-OFF CN86 pin1 CN86 pin
Output Status
power supply ON
Table 4.1
Switch open (Open)
Switch close (Short)
Fig 4.1
PIN2 +5V-AUX
PIN1 Remote ON-OFF
DIP SW1
CN86
CN53
SVR
DIP
SW81
CN53
SVR
DIP
SW81
CN86
ON
ON
OFF
OFF
123
123
5.Alarm Signal Output
There are 4 alarm signals, DC-OK, T-ALARM, Fan Fail and AC-OK, in TTL signal form, on CN86. These signals are isolated from output.
DC OK might mis-triggered when the voltage difference between PSU and the load, please minimized the unnecessary voltage difference.
File Name:SHP-10K-SPEC 2022-07-27
10KW Power Supply3 3W High Efficiency DigitalψSHP-10K series
DC-OK & T-ALARM & Fan Fail Signal
AC-OK Signal
Power Supply Status
Power Supply Status
“High” >3.5~5.5V
“High” >3.5~5.5V
“Low” <-0.5~0.5V
“Low” <-0.5~0.5V
OFF
ON
ON
OFF
PIN4,6,8,10 GND-AUX
Application
Circuit
Fig 5.1
PIN3 T-ALARM
PIN5 Fan Fail
PIN7 DC-OK
PIN9 AC-OK
CN53
SVR
CN86
DIP
SW
6.Current Sharing
CN53/SW1 Function pin connection
Parallel
CN53 CN53 CN53 CN53SW1 PIN1 SW1 PIN1 SW1 PIN1 SW1 PIN1
PSU1 PSU2 PSU3 PSU4
1 unit X
OFF
OFF OFF
ON
ON
ON
ON
ONV
VV
V
ON
VON
V
V
VV
2 unit
3 unit
4 unit
(V : CN53 connected ; X : CN53 not connected.)
PSU1 PSU2 PSU3 PSU4
File Name:SHP-10K-SPEC 2022-07-27
10KW Power Supply3 3W High Efficiency Digitalψ
LOAD
+V -V
DA,DB are connected mutually in parallel.
Fig 6.1
DA DA DA DADB DB DB DB
If the lines of CN53 are too long, they should
be twisted in pairs to avoid the noise.
PSU1
CN53
PSU2
CN53
PSU3
CN53
PSU4
CN53
888810 10 10 10
DA DA DA DADB DB DB DB
77779999
SHP-10K series
SHP-10K has the built-in active current sharing function and can be connected in parallel, up to 4 units, to provide higher output power as exhibited below :
The power supplies should be paralleled using short and large diameter wiring and then connected to the load.
In parallel connection, power supply with the highest output Voltage will be the master unit and its Vout will be the DC bus voltage.
The total output current must not exceed the value determined by the following equation:
the current shared among units may not be balanced.
※ ×When the total output current is less than 5% of the total rated current, or say (5% of Rated current per unit) (Number of unit)
Under parallel operation ripple of the output voltage may be higher than the SPEC at light load condition. It will go back to normal ripple level once the
output load is more than 5%.
Maximum output current at parallel operation=(Rated current per unit) (Number of unit) 0.95××
Mounting Instruction
Hole No. Recommended Screw Size MAX. Penetration Depth LRecommended mounting torque
15mm
M4 7~1 Kgf-cm0
Mounting Screw
Mounting Surface Chassis of SHP-10K
File Name:SHP-10K-SPEC 2022-07-27
10KW Power Supply3 3W High Efficiency DigitalψSHP-10K series
Mechanical Specification
Case No.223 Unit:mm
Forced-Air Cooling (Blank type)
94.75
4-M4 L=5mm
460
431.75
60
11.8
17
39.25
83.5
1 1
18 max.
-V
+V
13
10
211
1234
SVRLED
CN86
17
18
1
2
1
2
9
10
CN53
SVR
DIP-SW
1 2 3
45.9
45.45
128
383
94.75
4-M4 L=5mm
4-M4 L=5mm
Air flow
direction
60
11.7
1 1
11
11
8
36
54
72
9
1
10 3
85
67
4
10
1
9
2
12
11
14
13
16
15
18
17
CN86
CN53
DIP-SW
1 2 3
4.5
460
451
257.5
244.5
CN86
CN53
SVR
LED
2
18
1
17
SVR
10
91
2
50.5
24
124
115
50.5
115
216
4- 7.5ψ
2- 15ψ
-V
+V
File Name:SHP-10K-SPEC 2022-07-27
10KW Power Supply3 3W High Efficiency DigitalψSHP-10K series
Case No.223D Unit:mm
Water Cooling (L type)
: Max. Case Temperature
tc
83.5
tc
Tcase
265
80
18 max.
8
36
54
72
9
1
10 3
85
67
4
10
1
9
2
12
11
14
13
16
15
18
17
CN86
CN53
13
10
1234
19
102
Control Pin No. Assignment : HRS DF11-10DP-2DS or equivalent(3)CN5
Mating Housing
Terminal
HRS DF11-10DS or equivalent
HRS DF11-**SC or equivalent
Pin No. Function Description
1,2
3,4
5,6
7,8
9,10
-V(Signal)
PV+
PC+
DA
DB
Negative output voltage signal. It is for local sense and certain function reference; it cannot be connected directly to the load.
Connection for output voltage programming. (Note)
Connection for constant current level programming. (Note)
Differential digital signal for parallel control. (Note)
Differential digital signal for parallel control. (Note)
10KW Power Supply3 3W High Efficiency Digitalψ
Note: Non-isolated signal, referenced to [-V(Signal)].
SHP-10K series
File Name:SHP-10K-SPEC 2022-07-27
Pin No.
2
3
Function
+5V-AUX
T-ALARM
Description
Auxiliary voltage output, 4.5~5.5V, referenced to GND-AUX (pin 4,6,8,10,17,18) only for Remote ON/OFF used. This output is not
controlled by the Remote ON/OFF control.
1
Remote
ON-OFF
The unit can turn the output ON/OFF by dry contact between Remote ON/OFF and +5-AUX.(Note)
Short (4.5 ~ 5.5V) : Power ON ; Open(0 ~ 0.5V) : Power OFF ; The maximum input voltage is 5.5V
Note: Isolated signal, referenced to (GND-AUX).
High (3.5 ~ 5.5V) : When the internal temperature exceeds the limit of temperature alarm.
Low (-0.5 ~ 0.5V) : When the internal temperature is normal.
The maximum sourcing current is 10mA and only for output.(Note)
7
DC-OK
High(3.5 ~ 5.5V) : When Vout 80% 6%.≦±
High (3.5 ~ 5.5V): When AC input 335≧±1.5%Vac, PSU works normally.
Low(-0.5 ~ 0.5V) : When Vout 80% 6%.≧±
Low (-0.5 ~ 0.5V): When AC input 3≦±20 1.5%Vac, PSU shut down.
The maximum sourcing current is 10mA and only for output.(Note)
The maximum sourcing current is 10mA and only for output.(Note)
4,6,8,10
15,16
GND-AUX
+12V-AUX
Auxiliary voltage output GND.
Auxiliary voltage output, 11.4~12.6V, referenced to GND-AUX (pin17 & 18).
The signal return is isolated from the output terminals (+V & -V).
The maximum load current is 1A. This output is not controlled by “Remote ON-OFF”.
For PMBus model: Serial Clock used in the PMBus interface.(Note)
For PMBus model: Serial Data used in the PMBus interface.(Note)
For CANBus model: Data line used in CANBus interface.(Note)
For MODBus model: Data line used in MODBus interface.(Note)
For MODBus model: Data line used in MODBus interface.(Note)
For CANBus model: Data line used in CANBus interface.(Note)
11,12
13,14
SCL/CANL/
DATA-
SDA/CANH/
DATA+
9 AC-OK
18 2
117
Control Pin No. Assignment : HRS DF11-18DP-2DS or equivalent()CN86
Mating Housing
Terminal
HRS DF11-18DS or equivalent
HRS DF11-**SC or equivalent
5
17,18
Fan Fail
GND-AUX
High(3.5~5.5V):When the fan fail.
Auxiliary voltage output GND.
Low(-0.5~0.5V):When the fan works normally.
The maximum sourcing current is 10mA and only for output.(Note)
The signal return is isolated from the output terminals(+V & -V).
LED
Green(LED1)
Red(LED2)
LED on when output voltage is OK
Description
LED on when any protection occurs
LED Status Indicators
AC Input Terminal Pin No. Assignment (TB1)
DIP Switch Position Assignment(DIP-SW1): Please refer to the Function Manual.
DIP Switch Position Assignment(DIP-SW81): Please refer to the Function Manual.
Pin No.
1
3
4
2
Assignment Diagram Mxa imum mounting torque
18Kgf-cm
AC/L1
FG
AC/L3
AC/L2
Pin No.
1
3
2
Assignment Diagram
Output Current Programming (PC)
Output Voltage Programming (PV)
DA,DB Signal and paralled control function
ON
OFF
123
DIP-SW PIN2:PC
DIP-SW PIN3:PV
10KW Power Supply3 3W High Efficiency Digitalψ
Pin No.
1
2
3
4
Function
A0
A1
A2
RL
Description
PMBus/CANBus/MODBus interface address switch. (Max. 8 address)
Termination resistors(120 ) for communication.(CANBUS MODBUS)Ω
GUIDANCE OF ADDITIONAL FILTER
SHP-10K series
File Name:SHP-10K-SPEC 2022-07-27
L1 L1'
EMI
FILTER
AC Utility
LOAD
SHP-10K
CORE
AC
I/P
DC
O/P
Cx Cx
Cy
R1
R2
LL
LL
L3
L2
L3'
PE
L2'
PE
LOADLINE
1.Schematic
FREQ. MHz
FREQ. MHz
0.01
10
20
70.5
13
0.05
20
47
93.7
16
0.10
30
61
111
47
0.15
50
66
136
58
0.50
60
100
145
87
1.0
80
83
156
86
5.0
90
62
160
80
10
100
49
166
79
30
120
30
180
65
COM. MODE dB
Z( )Ω
DIF. MODE dB
2.Minimum insertion loss (In dB at 50 system): Filter model FN3288-20-33-C35-R65 or equivalentΩ
3.Minimum Impedance: Core model 4A11 or equivalent
4.Configration
If optional cold plate is in need, please contact MEAN WELL for details.
Ordering No.:HS-684
Ambient temperature: 50
Inlet temperature 5~15:
Flow rate (minimum):4~ 10LPM
Humidity: 20~90% RH non-condensing
Pressure drop 6 psi , pressure inlet 80 psi(minimum) (maximum)
1.Suitable for water cooling (L type)
10KW Power Supply3 3W High Efficiency DigitalψSHP-10K series
File Name:SHP-10K-SPEC 2022-07-27
Apply thermal grease (gap filler) between power supply
and cold plate connection surface.
Thermal grease (gap filler) :
* Thermal conductivity is no less than 1W/mK.
* Thickness is no more than 0.3mm.
505
M6*16
Water Output
Water Input
M6*4
L>7mm
M6*2(combination screw)
L>7mm
478
478
216.7
216.7
233.5
ψ7*4
ψ13*4
27
24
73
142
165.5
147.9
50.5
10KW Power Supply3 3W High Efficiency DigitalψSHP-10K series
Installation Manual
Please refer to : http://www.meanwell.com/manual.html
Air flow
direction
100mm
FAN
85CFM x 2
FAN
File Name:SHP-10K-SPEC 2022-07-27
2.With 85CFM forced air (L type)
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15

Mean Well SHP-10K Series User manual

Type
User manual

The Mean Well SHP-10K Series is a high-efficiency digital power supply well-suited for various industrial applications, including automation systems, laser processing machines, EV charging stations, and more. It offers a wide 3-phase AC input range (340-530VAC) and provides stable output voltages (55V/115V/230V/380V) with high efficiency up to 97%. The SHP-10K Series supports various cooling methods, including forced-air and water cooling, allowing for operation in ambient temperatures up to 70°C.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI