SICK UM18-2xxxxCxxx UM18-2xxxxDxxx UM18-2xxxxExxx Quickstart

Type
Quickstart

SICK UM18-2xxxxCxxx UM18-2xxxxDxxx UM18-2xxxxExxx are ultrasonic sensors used for the non-contact detection of objects, animals, and people. They are ideal for applications such as:

  • Level measurement
  • Object detection
  • Presence detection
  • Collision avoidance

The sensors have a range of up to 1000 mm and a resolution of up to 0.069 mm. They are also highly accurate, with an accuracy of ±1% of the current measured value.

The sensors are easy to install and configure. They can be mounted in any orientation and have a wide range of mounting options. The sensors also have a variety of output options, including analog, digital, and IO-Link.

SICK UM18-2xxxxCxxx UM18-2xxxxDxxx UM18-2xxxxExxx are ultrasonic sensors used for the non-contact detection of objects, animals, and people. They are ideal for applications such as:

  • Level measurement
  • Object detection
  • Presence detection
  • Collision avoidance

The sensors have a range of up to 1000 mm and a resolution of up to 0.069 mm. They are also highly accurate, with an accuracy of ±1% of the current measured value.

The sensors are easy to install and configure. They can be mounted in any orientation and have a wide range of mounting options. The sensors also have a variety of output options, including analog, digital, and IO-Link.

8023458/2018-08/8M_DR
UM18-2xxxxCxxx
UM18-2xxxxDxxx
UM18-2xxxxExxx
Irrtümer und Änderungen vorbehalten
1
31
46
4
M18 x 1
2
3
4
1
58,2
M12 x 1
62
47
16,5
4
M18 x 1
3,4
2
4
1
74,5
M12 x 1
3
1Anschluss
2Befestigungsmuttern, SW 24 mm
3und 4 LED Statusanzeige Versorgungsspannung aktiv (grün),
LED Statusanzeige des Schalt-/Analogausgangs (orange)
2
UM18-21xxxExxx
Stecker
M12, 5-polig
1
2
4
3
5
L+
Q1/Q1/C
1
4
brn
blk
2
wht
3
M
blu
5
MF
gra
1
Q2/Q2
UM18-21xxxCxxx
UM18-21xxxDxxx
Stecker
M12, 5-polig
1
2
4
3
5
L+
1
4
brn
blk
Q
A
2
wht
3
M
blu
5
MF
gra
1
Q1/Q1/C
1Multifunktionseingang/Synchronisations- und Multiplexbetrieb/
Kommunikation Connect+
3
UM18-217
0
50
250
150
200
100
100 10050 500
Erfassungsbereich in mm
Erfassungsbereich in mm
5
3
2
4
1
1Erfassungsbereich abhängig von Reflexionseigenschaften,
Größe und Ausrichtung des Objekts
2Grenzreichweite
3Betriebsreichweite
4Beispielobjekt: Ausgerichtete Platte 500 mm x 500 mm
5Beispielobjekt: Rundstab mit Durchmesser 10 mm
UM18-211
100150 15010050 500
0
50
150
100
200
250
300
350
3
4
5
2
1
Erfassungsbereich in mm
Erfassungsbereich in mm
1Erfassungsbereich abhängig von Reflexionseigenschaften,
Größe und Ausrichtung des Objekts
2Grenzreichweite
3Betriebsreichweite
4Beispielobjekt: Ausgerichtete Platte 500 mm x 500 mm
5Beispielobjekt: Rundstab mit Durchmesser 10 mm
UM18-212
200300 300200100 1000
3
4
5
2
1
0
100
300
200
400
500
600
Erfassungsbereich in mm
Erfassungsbereich in mm
1Erfassungsbereich abhängig von Reflexionseigenschaften,
Größe und Ausrichtung des Objekts
2Grenzreichweite
3Betriebsreichweite
4Beispielobjekt: Ausgerichtete Platte 500 mm x 500 mm
5Beispielobjekt: Rundstab mit Durchmesser 27 mm
UM18-218
500 500250 2500
0
500
250
750
1.000
1.250
1.500
Erfassungsbereich in mm
Erfassungsbereich in mm
3
4
5
2
1
1Erfassungsbereich abhängig von Reflexionseigenschaften,
Größe und Ausrichtung des Objekts
2Grenzreichweite
3Betriebsreichweite
4Beispielobjekt: Ausgerichtete Platte 500 mm x 500 mm
5Beispielobjekt: Rundstab mit Durchmesser 27 mm
A B C
Objekt bei
positionieren
L+ ca. 3 s an MF anlegen,
bis beide LEDs
gleichzeitig blinken
Q2: M an MF anlegen
Schaltpunkt einlernen
IO-Link: Einzelpunkt (DtO)
Beide LEDs: blinken
wechselseitig
L+ ca. 1 s an MF anlegen
Q2: M an MF anlegen
Objekt bei
Schaltpunkt einlernen + 8 %
IO-Link: Einzelpunkt + 8 %
(DtO + 8 %)
Beide LEDs:
L+ ca. 3 s an MF
anlegen, bis beide LEDs
erneut wechselseitig blinken
Q2: M an MF anlegen
Objekt bei
Schaltfenster einlernen
IO-Link: Fenster (Fensterbetrieb)
Beide LEDs:
Objekt bei
positionieren
Beide LEDs:
Hintergrund bei
positionieren
Hintergrund einlernen
IO-Link: Fenster ± 8 % (ObSB)
Beide LEDs:
Öffner/Schließer
einstellen
Q1: LED Q1
Q2: LED Q2
blinkt
an: Schließer
aus: Öffner
ca. 10 s warten
Normalbetrieb
Schaltausgang einlernen
positionieren positionieren
blinken
wechselseitig
blinken
wechselseitig
blinken
wechselseitig
L+ ca. 1 s an MF anlegen
Q2: M an MF anlegen
L+ ca. 10 s an MF
anlegen, bis beide LEDs
aufhören zu blinken
Q2: M an MF anlegen
Zum Ändern der Einstellung
L+ ca. 1 s
an MF anlegen
Q2: M an MF anlegen
111
2
1
L+ ca. 3 s an MF anlegen,
bis beide LEDs
gleichzeitig blinken
Q2: M an MF anlegen
L+ ca. 3 s an MF anlegen,
bis beide LEDs
gleichzeitig blinken
Q2: M an MF anlegen
L+ ca. 3 s an MF anlegen,
bis beide LEDs
gleichzeitig blinken
Q2: M an MF anlegen
L+ ca. 13 s an MF anlegen,
bis beide LEDs
wechselseitig blinken
Q2: M an MF anlegen
Q1: LED Q1
Q2: LED Q2
blinkt nicht mehr
Q1: LED Q2
Q2: LED Q1
Q1: LED Q2
Q2: LED Q1
wechselt Status
blinken
wechselseitig
Werkseinstellung: UM18-2xxxxCxxx/UM18-2xxxxDxxx: Schließer, Schaltpunkt (DtO) bei maximaler Betriebsreichweite;
UM18-2xxxxExxx: Schließer, Schaltpunkt (DtO) bei halber (Q1) und maximaler (Q2) Betriebsreichweite
12
11
+ 8 %
1
– 8 %
+ 8 %
Skalierung Analogausgang
einlernen
Objekt bei
positionieren
M ca. 3 s an MF anlegen,
bis beide LEDs
gleichzeitig blinken
Objekt bei
positionieren
M ca. 1 s an MF anlegen
Steigende / fallende
Ausgangscharakteristik
einstellen
M ca. 13 s an MF
anlegen, bis beide LEDs
wechselseitig blinken
blinkt
an: steigende,
aus: fallende Aus-
gangscharakteristik
LED Qa:
LED Q1:
Zum Ändern der Einstellung M
ca. 1 s an MF anlegen
ca. 10 s warten
Normalbetrieb
1
2
Analogausgang einlernen
LED Q1: wechselt Status
LED Qa: blinkt nicht mehr
blinken
wechselseitig
Beide LEDs:
Werkseinstellung: steigende Ausgangscharakteristik von minimaler bis
maximaler Betriebsreichweite
blinkt
LED Q2:
Teach-in und Synchro-
nisations-/Multiplexbetrieb
aktivieren/deaktivieren
Versorgungsspannung
ausschalten
Versorgungsspannung
einschalten
Zum Ändern der Einstellung
M ca. 1 s an MF anlegen
Auf Werkseinstellung
zurücksetzen
Normalbetrieb
Versorgungsspannung
ausschalten
ca. 10 s warten
ca. 3 s warten, bis
beide LEDs gleichzeitig blinken
ca. 13 s warten, bis
beide LEDs aufhören zu blinken
Weitere Einstellungen
LED Q2:blinkt nicht mehr
LED Q1/Qa: wechselt Status
M an MF anlegen
LED Q1/Qa: an: Teach-in und
Synchronisations-/
Multiplexbetrieb
aktiviert
aus: Teach-in und
Synchronisations-/
Multiplexbetrieb
deaktiviert
Versorgungsspannung
einschalten
M an MF anlegen
Vor dem Ausschalten der
Versorgungsspannung M von
MF trennen, um die Werks-
einstellung zu übernehmen
Sensoren mit Schaltausgang und IO-Link-Funktionalität Sensoren mit Schaltausgang, IO-Link-Funktionalität und Analogausgang
UM18-2 (gerade) UM18-21712E211 UM18-21112E211 UM18-21212E211 UM18-21812E211 4 mA ...20 mA UM18-21712C111 UM18-21112C111 UM18-21212C111
UM18-21812C111
0 V...10 V UM18-21712D111 UM18-21112D111 UM18-21212D111
UM18-21812D111
UM18-2 (gewinkelt) UM18-21712E212 UM18-21112E212 UM18-21212E212 UM18-21812E212 4 mA ...20 mA UM18-21712C112 UM18-21112C112 UM18-21212C112 UM18-21812C112
0 V...10 V UM18-21712D112 UM18-21112D112 UM18-21212D112 UM18-21812D112
Betriebsreichweite 20 ... 150 mm 30 ... 250 mm 65 ... 350 mm 120 ... 1000 mm 20 ... 150 mm 30 ... 250 mm 65 ... 350 mm 120 ... 1000 mm
Grenzreichweite 250 mm 350 mm 600 mm 1300 mm 250 mm 350 mm 600 mm 1300 mm
Ultraschallfrequenz (typisch) 380 kHz 320 kHz 400 kHz 200 kHz 380 kHz 320 kHz 400 kHz 200 kHz
Hysterese (einstellbar über Connect+) 2 mm 3 mm 5 mm 20 mm
Auflösung ≥ 0,069 mm
Reproduzierbarkeit ± 0,15 % bezogen auf den aktuellen Messwert
Genauigkeit
1)
± 1 % bezogen auf den aktuellen Messwert
Versorgungsspannung U
v
2)
DC 10 ... 30 V Spannungsausgang: DC 15 ... 30 V
Stromausgang: DC 10 ... 30 V bei RL ≤ 100 Ωr
DC 20 ... 30 V bei RL > 100 Ω
Leistungsaufnahme (ohne Last) ≤ 1,35 W
Gehäusematerial Messing vernickelt; Ultraschallwandler: Polyurethanschaum, Epoxydharz mit Glasanteilen
Schutzart nach EN 60529 IP 67
Schutzklasse III
Anschlussart Stecker M12, 5-polig
Umgebungstemperatur Betrieb: –25 °C ... +70 °C
Lager : –40 °C ... +85 °C
Gewicht Gerade: 25 g
Gewinkelt: 30 g
Analogausgang 4 mA ... 20 mA nicht verfügbar RL ≤ 500 Ω
0 V ... 10 V nicht verfügbar RL ≥ 100 kΩ
Schaltausgang
3)
2 x Gegentakt: PNP/NPN (100mA); IO-Link V1.1 Gegentakt: PNP/NPN (100mA); IO-Link V1.1
Ausgabezeit 8 ms 8 ms 16 ms 20 ms 8 ms 8 ms 16 ms 20 ms
Schaltfrequenz 25 Hz 25 Hz 12 Hz 10 Hz
Ansprechzeit 32 ms 32 ms 64 ms 80 ms 32 ms
4)
32 ms
4)
64 ms
4)
80 ms
4)
Initialisierungszeit < 300 ms
Max. Anzugsmoment der
Befestigungsmuttern
15 Nm
1) Temperaturkompensation abschaltbar über Connect+, nicht temperaturkompensiert: 0,17 % /K
2) Grenzwerte, verpolsicher, Betrieb in kurzschlussgeschützem Netz, max. 8 A; Class 2
3) Gegentakt: PNP/NPN: HIGH = U
V
– (< 3 V)/LOW = <3 V
4) Die nachgelagerte Glättung des Analogsignals kann die Ansprechzeit applikationsbedingt um bis zu 200 % verlängern
DEUTSCH
Ultraschallsensor - Quickstart
Sicherheitshinweise
> Vor der Inbetriebnahme die Betriebsanleitung lesen.
> A
nschluss, Montage und Einstellung nur durch Fachpersonal.
> Gerät bei Inbetriebnahme vor Feuchte und Verunreinigung schützen.
> Kein Sicherheitsbauteil g
emäß EU-Maschinenrichtlinie.
Bestimmungsgemäße Verwendung
Der UM18-2 Pro ist ein Ultraschallsensor und wird zum
berührungslosen Erfassen von Sachen, Tieren und Personen
eingesetzt.
Hinweise:
Unterhalb der Betriebsreichweite des Ultraschallsensors
UM18-2 Pro ist eine Entfernungsmessung nicht möglich.
Im Betrieb mit der Filtereinstellung F00 (einstellbar über
SOPAS, Connect+ und IO-Link) können bei EMV-Störeinflüssen
systembedingt nachfolgende Störzeiten von bis zu einer
Ausgabezeit auftreten. Der Sensor ist danach wieder voll
funktionsfähig.
Die UM18-2 Pro-Sensoren verfügen über eine interne
Temperaturkompensation. Aufgrund der Eigenerwärmung des
Sensors erreicht die Temperaturkompensation nach ca. 1 min
Betriebszeit ihren optimalen Arbeitspunkt.
Weitere Informationen zur Temperaturkompensation finden Sie in
der Betriebsanleitung unter www.sick.com/UM18.
Im Normalbetrieb signalisiert eine orange leuchtende LED, dass
der Schaltausgang aktiv ist (Sensoren mit Schaltausgang) bzw.
dass sich ein Objekt im Bereich der Skalierung befindet (Sensoren
mit Analogausgang).
Bei aktiviertem Multiplexbetrieb ist die Teach-in-Funktion
deaktiviert.
UM18-2 Pro-Sensoren mit Schaltausgang sind IO-Link-fähig
gemäß Spezifikation V1.1. Die Beschreibung der IO-Link
Funktionalität sowie die aktuelle IODD für diese Sensoren ist
kostenfrei erhältlich unter www.sick.com/UM18.
Inbetriebnahme
Handlungsanweisungen siehe:
Ablaufdiagramm A für Sensoren mit Schaltausgang
Ablaufdiagramm B für Sensoren mit Analogausgang
Sensoren mit Schaltausgang
Für Sensoren mit Schaltausgang gibt es drei Betriebsmodi.
Schaltpunkt (+8 %) einlernen:
Der Schaltausgang ist aktiv, wenn sich das Objekt entweder
unterhalb des eingelernten Schaltpunktes oder unterhalb des
eingelernten Schaltpunktes + 8 % befindet.
Schaltfenster einlernen:
Der Schaltausgang ist inaktiv, wenn sich das Objekt innerhalb des
eingelernten Fensters befindet.
Hintergrund einlernen:
Der Schaltausgang ist aktiv, wenn sich das Objekt unterhalb des
eingelernten Reflektors - 8 % oder oberhalb des eingelernten
Reflektors + 8 % befindet.
Sensoren mit Analogausgang
Siehe Ablaufdiagramm B.
Skalierung einlernen (4 mA ... 20 mA bzw. 0 V ... 10 V):
Wird zuerst die sensorferne Skalierungsgrenze und danach
die sensornahe Skalierungsgrenze eingelernt, werden die Grenzen
intern getauscht. Wird die Skalierung < 1 mm eingelernt, so
blinken beide LEDs für 3 s gleichzeitig schnell als Fehleranzeige.
Die alten Skalierungsgrenzen werden beibehalten.
Zwischen Teach-in und Synchronisations-/Multiplexbetrieb
wechseln
Siehe Ablaufdiagramm C.
Möchten Sie mehrere Ultraschallsensoren betreiben und
wird der in der Tabelle „Montageabstände“ angegebene
Montageabstand unterschritten, empfehlen wir den integrierten
Synchronisations- oder Multiplexbetrieb zu nutzen.
Während die grüne LED blinkt, wird mit jedem Anlegen von
„M“ zwischen Teach-in und Synchronisations-/Multiplexbetrieb
gewechselt. Wird für 10 s „M“ nicht angelegt, ist die eingestellte
Funktion übernommen. Der Sensor ist betriebsbereit.
Synchronisations-/Multiplexbetrieb (nicht verfügbar im IO-Link-
Betrieb)
Synchronisations- und Multiplexbetrieb vermeiden eine gegenseitige
Beeinflussung mehrerer miteinander verschalteter Sensoren.
Der Detektionsbereich vergrößert sich auf die Fläche, die alle via
PIN 5 (MF) miteinander verschalteten Sensoren abdecken. Beim
UM18-2 Pro können max. 20 Sensoren miteinander verschaltet
werden.
Im Synchronisationsbetrieb senden und empfangen alle Sensoren
ihre Ultraschallimpulse gleichzeitig. Der Synchronisationsbetrieb
beginnt automatisch, sobald die Sensoren miteinander via PIN 5
(MF) verschaltet werden.
Im Multiplexbetrieb senden und empfangen alle Sensoren ihre
Ultraschallimpulse nacheinander in einer definierten Reihenfolge.
Dies ermöglicht eine zusätzliche Positionsbestimmung der
erfassten Objekte.
Um in den Multiplexbetrieb zu wechseln, müssen den via PIN 5
(MF) verschalteten Sensoren mittels der Software Connect+
unterschiedliche Adressen zugeordnet werden.
Tabelle Montageabstände ohne Einsatz
von Synchronisations-/Multiplexbetrieb
Parallel Gegenüberliegend
UM18-217x > 250 mm > 1300 mm
UM18-211x > 350 mm > 2500 mm
UM18-212x > 400 mm > 2500 mm
UM18-218x > 700 mm > 4000 mm
Auf Werkseinstellung zurücksetzen
Siehe Ablaufdiagramm C.
Wartung
SICK-Sensoren sind wartungsfrei. Wir empfehlen, in regelmäßigen
Abständen die Grenzflächen zu reinigen und die Verschraubungen
und Steckverbindungen zu überprüfen.
www.sick.com/UM18
- For use in NFPA79 applications only.
- UL-Listed adapters providing field wiring leads
are available.
- Refer to the product information.
BZ int48
Please find detailed addresses and further locations in all major industrial
nations at www.sick.com
Australia
Phone +61 (3) 9457 0600
Austria
Phone +43 (0) 2236 62288-0
Belgium/Luxembourg
Phone +32 (0) 2 466 55 66
Brazil
Phone +55 11 3215-4900
Canada
Phone +1 905.771.1444
Czech Republic
Phone +420 2 57 91 18 50
Chile
Phone +56 (2) 2274 7430
China
Phone +86 20 2882 3600
Denmark
Phone +45 45 82 64 00
Finland
Phone +358-9-25 15 800
France
Phone +33 1 64 62 35 00
Germany
Phone +49 (0) 2 11 53 01
Hong Kong
Phone +852 2153 6300
Hungary
Phone +36 1 371 2680
India
Phone +91-22-6119 8900
Israel
Phone +972-4-6881000
Italy
Phone +39 02 27 43 41
Japan
Phone +81 3 5309 2112
Malaysia
Phone +603-8080 7425
Mexico
Phone +52 (472) 748 9451
Netherlands
Phone +31 (0) 30 229 25 44
New Zealand
Phone +64 9 415 0459
Norway
Phone +47 67 81 50 00
Poland
Phone +48 22 539 41 00
Romania
Phone +40 356-17 11 20
Russia
Phone +7 495 283 09 90
Singapore
Phone +65 6744 3732
Slovakia
Phone +421 482 901 201
Slovenia
Phone +386 591 78849
South Africa
Phone +27 (0)11 472 3733
South Korea
Phone +82 2 786 6321
Spain
Phone +34 93 480 31 00
Sweden
Phone +46 10 110 10 00
Switzerland
Phone +41 41 619 29 39
Taiwan
Phone +886-2-2375-6288
Thailand
Phone +66 2 645 0009
Turkey
Phone +90 (216) 528 50 00
United Arab Emirates
Phone +971 (0) 4 88 65 878
United Kingdom
Phone +44 (0)17278 31121
USA
Phone +1 800.325.7425
Vietnam
Phone +65 6744 3732
8023458/2018-08/8M_DR
UM18-2xxxxCxxx
UM18-2xxxxDxxx
UM18-2xxxxExxx
Subject to change without notice
1
31 (1.22)
46 (1.81)
4
(0.16)
M18 x 1
2
3
4
1
58.2 (2.29)
M12 x 1
62 (2.44)
47 (1.85)
16.5
(0.65)
4
(0.16)
M18 x 1
3.4
(0.13)
2
4
1
74.5 (2.93)
M12 x 1
3
1Connection
2Fixing nuts, width 24 mm
3and 4 LED status display for supply voltage active (green), LED
status display for the switching/analog output (orange)
2
UM18-21xxxExxx
Male connector
M12, 5-pin
1
2
4
3
5
L+
Q1/Q1/C
1
4
brn
blk
2
wht
3
M
blu
5
MF
gra
1
Q2/Q2
UM18-21xxxCxxx
UM18-21xxxDxxx
Male connector
M12, 5-pin
1
2
4
3
5
L+
1
4
brn
blk
Q
A
2
wht
3
M
blu
5
MF
gra
1
Q1/Q1/C
1Multifunctional input / synchronization and multiplex mode /
Connect+ communication
3
UM18-217
0
50
(1.97)
250
(9.84)
150
(5.91)
200
(7.87)
100
(3.94)
100
(3.94)
50
(1.97)
0
Detection area in mm (inch)
Detection area in mm (inch)
50
(1.97)
100
(3.94)
5
3
2
1
4
1Detection range dependent on reflection properties, size,
and alignment of the object
2Limiting range
3Operating range
4Example object: Aligned plate 500 mm x 500 mm
5Example object: Cylindrical bar with diameter of 10 mm
UM18-211
100
(3.94)
150
(5.91)
150
(5.91)
Detection area in mm (inch)
100
(3.94)
50
(1.97)
50
(1.97)
0
Detection ar
ea in mm (inch)
0
50
(1.97)
150
(5.91)
100
(3.94)
200
(7.87)
250
(9.84)
300
(11.81)
350
(13.78)
3
4
5
2
1
1Detection range dependent on reflection properties, size,
and alignment of the object
2Limiting range
3Operating range
4Example object: Aligned plate 500 mm x 500 mm
5Example object: Cylindrical bar with diameter of 10 mm
UM18-212
200
(7.87)
300
(11.81)
300
(11.81)
200
(7.87)
100
(3.94)
100
(3.94)
0
Detection area in mm (inch)
3
4
5
2
1
0
100
(3.94)
300
(11.81)
200
(7.87)
400
(15.75)
500
(19.69)
600
(23.62)
Detection area in mm (inch)
1Detection range dependent on reflection properties, size,
and alignment of the object
2Limiting range
3Operating range
4Example object: Aligned plate 500 mm x 500 mm
5Example object: Cylindrical bar with diameter of 27 mm
UM18-218
500
(19.69)
500
(19.69)
250
(9.84)
250
(9.84)
0
Detection area in mm (inch)
3
4
5
2
1
0
500
(19.69)
250
(9.84)
750
(29.53)
1,000
(39.37)
1,250
(49.21)
1,500
(59.06)
Detection area in mm (inch)
1Detection range dependent on reflection properties, size,
and alignment of the object
2Limiting range
3Operating range
4Example object: Aligned plate 500 mm x 500 mm
5Example object: Cylindrical bar with diameter of 27 mm
A B C
Position object at 1
Apply L+ at MF for approx. 3s
until both LEDs are
flashing simultaneously
Q2: Apply M at MF
Teaching in the switching point
IO-Link: Single point (DtO)
Both LEDs: Flashing
alternately
Apply L+ at MF for approx. 1s
Q2: Apply M at MF
Position object at 1
Teaching in the switching point + 8%
IO-Link: Single point +8%
(DtO + 8 %)
Both LEDs:
Apply L+ at MF for approx. 3s
until both LEDs are
flashing alternately again
Q2: Apply M at MF
Position object at 1
Teaching in the switching point
IO-Link: Window (window mode)
Both LEDs:
Position object at 2
Both LEDs:
Position background at 1
Teach in the background
IO-Link: Window ±8% (ObSB)
Both LEDs:
Set normally closed/
normally open
Q1: LED Q1
Q2: LED Q2
Flashing
ON: Normally open
OFF: Normally
closed
Wait approx. 10s
Normal mode
Teaching in the switching output
Flashing
alternately
Flashing
alternately
Flashing
alternately
Apply L+ at MF for approx. 1s
Q2: Apply M at MF
Apply L+ at MF for approx. 10s
until both LEDs
stop flashing
Q2: Apply M at MF
Apply L+ at MF for
approx. 1s to
change the setting
Q2: Apply M at MF
Apply L+ at MF for approx. 3s
until both LEDs are
flashing simultaneously
Q2: Apply M at MF
Apply L+ at MF for approx. 3s
until both LEDs are
flashing simultaneously
Q2: Apply M at MF
Apply L+ at MF for approx. 3s
until both LEDs are
flashing simultaneously
Q2: Apply M at MF
Apply L+ at MF for approx. 13s
until both LEDs are
flashing alternately
Q2: Apply M at MF
Q1: LED Q1
Q2: LED Q2
No longer flashing
Q1: LED Q2
Q2: LED Q1
Q1: LED Q2
Q2: LED Q1
Changes status
Flashing
alternately
Factory setting: UM18-2xxxxCxxx/UM18-2xxxxDxxx: normally open, switching point (DtO) at maximum operating range;
UM18-2xxxxExxx: normally open, switching point (DtO) at half (Q1) and maximum (Q2) operating range
12
11
+ 8 %
1
– 8 %
+ 8 %
Teach in analog
output scaling
Position object at
Apply M at MF for approx. 3s
until both LEDs are
flashing simultaneously
Position object at
Apply M at MF for approx. 1s
Set rising/falling
output characteristic
Apply M at MF for approx. 13s
until both LEDs are
flashing alternately
Flashing
ON: Rising
OFF: Falling signal
edge
LED Qa:
LED Q1:
Apply M at MF for approx. 1s
to change the setting
Wait approx. 10s
Normal mode
1
2
Teaching in the analog output
LED Q1: Changes status
LED Qa: No longer flashing
Flashing
alternately
Both LEDs:
Factory setting: Rising output characteristic from minimum to
maximum operating range
Flashing
LED Q2:
Activate/deactivate teach-in
and synchronization/
multiplex mode
Switch off the
supply voltage
Switch on the
supply voltage
Apply M at MF for approx. 1s
to change the setting
Reset to
factory settings
Normal mode
Switch off the
supply voltage
Wait approx. 10s
Wait approx. 3s until both LEDs
are flashing simultaneously
Wait approx. 13s until both LEDs
stop flashing
Additional settings
Green LED: No longer flashing
Orange LED: Changes status
Apply M at MF
LED Q1/Qa: ON: Teach-in and
synchronization/
multiplex mode
activated
OFF: Teach-in and
synchronization/
multiplex mode
deactivated
Switch on the
supply voltage
Apply M at MF
Disconnect M from MF
before switching off the
supply voltage to apply
the factory setting
Sensors with switching outputs and IO-Link functionality Sensors with switching outputs, IO-Link functionality, and analog output
UM18-2 (straight) UM18-21712E211 UM18-21112E211 UM18-21212E211 UM18-21812E211 4 mA ...20 mA UM18-21712C111 UM18-21112C111 UM18-21212C111
UM18-21812C111
0 V...10 V UM18-21712D111 UM18-21112D111 UM18-21212D111
UM18-21812D111
UM18-2 (angled) UM18-21712E212 UM18-21112E212 UM18-21212E212 UM18-21812E212 4 mA ...20 mA UM18-21712C112 UM18-21112C112 UM18-21212C112 UM18-21812C112
0 V...10 V UM18-21712D112 UM18-21112D112 UM18-21212D112 UM18-21812D112
Operating range 20 ... 150 mm 30 ... 250 mm 65 ... 350 mm 120 ... 1,000 mm 20 ... 150 mm 30 ... 250 mm 65 ... 350 mm 120 ... 1,000 mm
Limiting range 250 mm 350 mm 600 mm 1,300 mm 250 mm 350 mm 600 mm 1,300 mm
Ultrasonic frequency (typical) 380 kHz 320 kHz 400 kHz 200 kHz 380 kHz 320 kHz 400 kHz 200 kHz
Hysteresis (can be adjusted via Con-
nect+)
2 mm 3 mm 5 mm 20 mm
Resolution ≥ 0.069 mm
Reproducibility ± 0.15% in relation to the current measured value
Accuracy
1)
± 1% in relation to the current measured value
Supply voltage U
V
2)
DC 10 ... 30 V Voltage output: DC 15 ... 30 V
Current output: DC 10 ... 30 V at RL ≤ 100 Ωr
DC 20 ... 30 V at RL > 100 Ω
Power consumption (without load) ≤ 1.35 W
Housing material Nickel plated brass, ultrasonic converter: polyurethane foam, epoxy resin with glass content
Enclosure rating as per EN 60529 IP 67
Protection class III
Connection type Male connector, M12, 5-pin
Ambient temperature Operation: –25 °C ... +70 °C
Storage: –40 °C … +85 °C
Weight Straight: 25 g
Angled: 30 g
Analog output 4 mA ... 20 mA not available RL ≤ 500 Ω
0 V ... 10 V not available RL ≥ 100 kΩ
Switching output
3)
2 x push-pull: PNP/NPN (100 mA); IO-Link V1.1 Push-pull: PNP/NPN (100 mA); IO-Link V1.1
Output time 8 ms 8 ms 16 ms 20 ms 8 ms 8 ms 16 ms 20 ms
Switching frequency 25 Hz 25 Hz 12 Hz 10 Hz
Response time 32 ms 32 ms 64 ms 80 ms 32 ms
4)
32 ms
4)
64 ms
4)
80 ms
4)
Initialization time < 300 ms
Max. tightening torque for fixing nuts 15 Nm
1) Temperature compensation can be switched off via Connect+, without temperature compensation: 0.17% / K
2) Limit values, reverse-polarity protected, operation in short-circuit protected network: max. 8 A; Class 2
3) Push-pull: PNP/NPN: HIGH = U
V
– (< 3 V)/LOW = < 3 V
4) Subsequent smoothing of the analog output may increase the response time by up to 200% in some applications
ENGLISH
Ultrasonic sensorQuickstart
Safety notes
> Read the operating instructions before commissioning.
> Connection, mounting, and configuration may only be performed
by trained specialists.
> When commissioning, protect the device from moisture and contami-
nation.
> Not a safety component in accordance with the EU Machinery
Directive.
Intended use
The UM18-2 Pro is an ultrasonic sensor for non-contact detection of
objects, animals, and persons.
Notes:
Distance measurement is not possible below the operating range
of the UM18-2 Pro ultrasonic sensor.
During operation with the filter setting F00 (can be set via SOPAS,
Connect+, and IO-Link), EMC interference can cause system-
inherent subsequent disruption times of up to one output time.
After this the sensor returns to full working order.
UM18-2 Pro sensors feature internal temperature compensation.
Due to the sensor heating up, the temperature compensation
function will reach its optimal working point after approximately
one minute.
For additional information on temperature compensation,
please refer to the operating instructions which are available at
www.sick.com/UM18.
During normal operation, an orange LED lights up to signal that
the switching output is active (for sensors with a switching output)
or that an object is in the scaling area (for sensors with an analog
output).
The teach-in function is deactivated when multiplex mode is
activated.
UM18-2 Pro sensors with switching outputs are IO-Link-capable
in accordance with the V1.1 specification. A description of IO-Link
functions and the latest IODD for these sensors are available free
of charge at www.sick.com/UM18.
Commissioning
For instructions, see:
Process diagram A for sensors with switching outputs
Process diagram B for sensors with analog outputs
Sensors with switching outputs
There are three operating modes for sensors with switching outputs.
Teach in switching point (+8%):
The switching output is active when the object is located either
below the taught-in switching point or below the taught-in switching
point +8%.
Teach in switching window:
The switching output is inactive when the object is located inside
the taught-in window.
Teach in background:
The switching output is active when the object is located either
below the taught-in reflector -8% or above the taught-in reflector
+8%.
Sensors with analog outputs
See process diagram B.
Teach in scaling (4 mA ... 20 mA or 0 V ... 10 V):
If the distant sensor scaling limit is taught-in first, followed by the
close sensor scaling limit, then the limits are replaced internally. If
scaling < 1 mm is taught-in, then both LEDs flash rapidly together
for 3 seconds as an error indication. The old scaling limits are
retained.
Switching between teach-in and synchronization / multiplex mode
See process diagram C.
If you want to operate several ultrasonic sensors and cannot
comply with the mounting distance specified in the “Mounting
distances” table, we recommend using the integrated
synchronization or multiplex mode.
While the green LED is flashing, every time “M” is applied the
mode switches between teach-in and synchronization/multiplex. If
“M” is not applied for 10 s, the set function is adopted. The sensor
is ready for operation.
Synchronization/Multiplex mode (not available in IO-Link mode)
Synchronization/Multiplex mode prevents mutual interference of
several interconnected sensors.
The detection zone is enlarged to a size which covers all sensors
connected via PIN 5 (MF). A maximum of 20 sensors can be intercon-
nected with the UM18-2 Pro.
In synchronization mode, all sensors send and receive their
ultra sonic pulses simultaneously. Synchronization mode begins
automatically as soon as the sensors are interconnected via PIN 5
(MF).
In multiplex mode, all sensors send and receive their ultrasonic
pulses one after another in a defined sequence. This enables
additional position detection of the recorded objects.
To change to multiplex mode, different addresses must be
assigned to the sensors interconnected via PIN 5 (MF) using the
Connect+ software.
Table listing mounting distances when synchronization/
multiplex mode is not used
Parallel Opposite
UM18-217x > 250 mm > 1,300 mm
UM18-211x > 350 mm > 2,500 mm
UM18-212x > 400 mm > 2,500 mm
UM18-218x > 700 mm > 4,000 mm
Reset to factory settings
See process diagram C.
Maintenance
SICK sensors are maintenance-free. We recommend that the limit
surfaces are cleaned thoroughly with water and that the screwed
connections and plug connectors are checked at regular intervals.
www.sick.com/UM18
- For use in NFPA79 applications only.
- UL-Listed adapters providing field wiring leads
are available.
- Refer to the product information.
BZ int48
Please find detailed addresses and further locations in all major industrial
nations at www.sick.com
Australia
Phone +61 (3) 9457 0600
Austria
Phone +43 (0) 2236 62288-0
Belgium/Luxembourg
Phone +32 (0) 2 466 55 66
Brazil
Phone +55 11 3215-4900
Canada
Phone +1 905.771.1444
Czech Republic
Phone +420 2 57 91 18 50
Chile
Phone +56 (2) 2274 7430
China
Phone +86 20 2882 3600
Denmark
Phone +45 45 82 64 00
Finland
Phone +358-9-25 15 800
France
Phone +33 1 64 62 35 00
Germany
Phone +49 (0) 2 11 53 01
Hong Kong
Phone +852 2153 6300
Hungary
Phone +36 1 371 2680
India
Phone +91-22-6119 8900
Israel
Phone +972-4-6881000
Italy
Phone +39 02 27 43 41
Japan
Phone +81 3 5309 2112
Malaysia
Phone +603-8080 7425
Mexico
Phone +52 (472) 748 9451
Netherlands
Phone +31 (0) 30 229 25 44
New Zealand
Phone +64 9 415 0459
Norway
Phone +47 67 81 50 00
Poland
Phone +48 22 539 41 00
Romania
Phone +40 356-17 11 20
Russia
Phone +7 495 283 09 90
Singapore
Phone +65 6744 3732
Slovakia
Phone +421 482 901 201
Slovenia
Phone +386 591 78849
South Africa
Phone +27 (0)11 472 3733
South Korea
Phone +82 2 786 6321
Spain
Phone +34 93 480 31 00
Sweden
Phone +46 10 110 10 00
Switzerland
Phone +41 41 619 29 39
Taiwan
Phone +886-2-2375-6288
Thailand
Phone +66 2 645 0009
Turkey
Phone +90 (216) 528 50 00
United Arab Emirates
Phone +971 (0) 4 88 65 878
United Kingdom
Phone +44 (0)17278 31121
USA
Phone +1 800.325.7425
Vietnam
Phone +65 6744 3732
  • Page 1 1
  • Page 2 2

SICK UM18-2xxxxCxxx UM18-2xxxxDxxx UM18-2xxxxExxx Quickstart

Type
Quickstart

SICK UM18-2xxxxCxxx UM18-2xxxxDxxx UM18-2xxxxExxx are ultrasonic sensors used for the non-contact detection of objects, animals, and people. They are ideal for applications such as:

  • Level measurement
  • Object detection
  • Presence detection
  • Collision avoidance

The sensors have a range of up to 1000 mm and a resolution of up to 0.069 mm. They are also highly accurate, with an accuracy of ±1% of the current measured value.

The sensors are easy to install and configure. They can be mounted in any orientation and have a wide range of mounting options. The sensors also have a variety of output options, including analog, digital, and IO-Link.