EM-8283-A Rev.3P. 1 / 6
MD6x-24
MD6x-65
BEFORE USE ....
Thank you for choosing M-System. Before use, check the
contents of the package you received as outlined below.
If you have any problems or questions on the product, please
contact M-System’s Sales Office or representatives.
■ PACKAGE INCLUDES:
Lightning surge protector ..........................................(1)
■ MODEL NO.
Check that model No. described on the specification label is
exactly what you ordered.
■ INSTALLATION / INSTRUCTION MANUAL
This manual describes necessary points of caution when you
use this product, including installation and basic mainte-
nance procedure.
When using this product in potentially explosive atmosphere
or hazardous (classified) location, you have to follow the
safety procedure to install it. Please refer to “SAFE INSTAL-
LATION MANUAL” for each type of certification.
LIMITATION APPLICABLE TO M-RESTER
The M-Rester will protect electronics equipment from dam-
age caused by lightning by absorbing most of the surge
voltages.
However, M-Rester may not be effective against certain
extremely high voltages caused by a direct or almost direct
hit by lightning.
M-Rester must be installed according to this installation /
instruction manual.
INSTRUCTION MANUAL
MODEL
LIGHTNING SURGE PROTECTOR FOR STANDARD
SIGNAL LINE & PULSE USE
(conduit mount, weather-proof)
MD6x-24
MD6x-65
GENERAL
■ FUNCTION & FEATURES
• Designed specifically to protect 4 to 20mA DC and pulse
signal line including both 4-wire and 2-wire transmitters
• Direct mount in a wiring conduit of outdoor enclosures
• Absorbs surges only without affecting transmitted signals
■ SPECIFICATIONS
BETWEEN LINES
LINE TO GND
MD6x-24 MD6x-65
Discharge voltage 30V min. 70V min. ±160V min.
(peak voltage)
Max. surge voltage
* 40V max. 100V max. ±650V max.
Leakage current ≤5µA ≤5µA ≤5µA
@30V DC @70V DC @±160V DC
Max. line voltage 30V DC 70V DC –––
Response time ≤4 nsec. ≤4 nsec. ≤20 nsec.
Capacitance ≤2500 pF ≤2500 pF ≤100 pF
@1kHz @1kHz @1kHz
Discharge current 10000A (8 / 20 µsec.)
Max. load current 100mA
Internal series resist.
approx. 22Ω including return
*The maximum voltage that could pass through M-RESTER.
Protected equipment must be able to withstand this voltage
for a very short time period.
POINTS OF CAUTION
■ GENERAL PRECAUTION
• Before you remove the unit or mount it, turn off the signal
input and the power supply to the connected devices for
safety.
■ ENVIRONMENT
• Do not install the M-RESTER where it is subjected to
continuous vibration. Do not apply physical impact to the M-
RESTER.
• Environmental temperature must be within -40 to +85°C
(-40 to +185°F) in order to ensure adequate life span and
operation.
■ INSULATION RESISTANCE TEST
• Before conducting an insulation test, remove the unit from
the protected signal line. Use a megger of 125V DC at the
maximum. If you use a higher-rated megger, the discharge
elements will start discharging, which will be detected falsely
as insulation failure.
■ AND ....
• We recommend that you keep spare M-RESTERs so that
you can replace them when necessary.