Update notice
5
New parameters and parameter values (EN page 72)
Parameters
Index Name/Selection Description Def
11 REFERENCE
SELECT
Panel reference type, external control location selection and external
reference sources and limits
1106 REF2 SELECT Selects the signal source for external reference REF2. 2 = POT
PID1OUT New value.
PID controller 1 output. See parameter group 40 PROCESS PID
SET 1.
19
14 RELAY OUTPUTS
Status information indicated through relay output, and relay operating delays
1401 RELAY OUTPUT 1 Selects a drive status indicated through relay output RO. The relay energises
when the status meets the setting.
3 =
FAULT(-1)
PID SLEEP New value.
PID sleep function. See parameter group 40 PROCESS PID SET
1.
30
32 SUPERVISION
Signal supervision. The drive monitors whether certain user selectable
variables are within the user-defined limits. The user may set limits for speed,
current etc. Supervision status can be monitored with relay output. See
parameter group 14 RELAY OUTPUTS.
3201 SUPERV 1 PARAM Selects the first supervised signal. Supervision limits are defined by
parameters 3202 SUPERV 1 LIM LO and 3203 SUPERV 1 LIM HI.
103
126, 128, 130, 132 New values.
Parameter index in group 01 OPERATING DATA. E.g. 102 =
0102 SPEED. 0 = not selected.
3204 SUPERV 2 PARAM Selects the second supervised signal. Supervision limits are defined by
parameters 3205 SUPERV 2 LIM LO and 3206 SUPERV 2 LIM HI. See
parameter 3201 SUPERV 1 PARAM.
104
126, 128, 130, 132 New values.
Parameter index in group 01 OPERATING DATA. E.g. 102 =
0102 SPEED
3207 SUPERV 3 PARAM Selects the third supervised signal. Supervision limits are defined by
parameters 3208 SUPERV 3 LIM LO and 3209 SUPERV 3 LIM HI. See
parameter 3201 SUPERV 1 PARAM.
105
126, 128, 130, 132 New values.
Parameter index in group 01 OPERATING DATA. E.g. 102 =
0102 SPEED
34 PANEL DISPLAY
Selection of actual signals to be displayed on the panel
3401 SIGNAL1 PARAM Selects the first signal to be displayed on the control panel in display mode. 103
126, 128, 130, 132 New values.
Parameter index in group 01 OPERATING DATA. E.g. 102 =
0102 SPEED. If value is set to 0, no signal is selected.
3408 SIGNAL2 PARAM Selects the second signal to be displayed on the control panel in display
mode. See par. 3401 SIGNAL1 PARAM.
104
126, 128, 130, 132 New values.
Parameter index in group 01 OPERATING DATA. E.g. 102 =
0102 SPEED. If value is set to 0, no signal is selected.
3415 SIGNAL3 PARAM Selects the third signal to be displayed on the control panel in display mode.
See par 3401 SIGNAL1 PARAM.
105
126, 128, 130, 132 New values.
Parameter index in group 01 OPERATING DATA. E.g. 102 =
0102 SPEED. If value is set to 0, no signal is selected.
LOC
Hz
OUTPUT FWD
491
.
3401
3404
3405