  • Hello! I am an AI chatbot trained to assist you with the DMP Electronics 861 Installation guide. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
861 AUXILIARY POWER DISTRIBUTION
AND BUS MODULE
Installation Guide
DESCRIPTION
MODEL
861
R B R B
RED PWR OUT BLK GND OUT
4-WIRE
BUS-A
RED
PWR IN
BLK
GND IN
4-WIRE
BUS-B
The Model861Auxiliary Power
Distribution and Bus Module
provides multiple auxiliary
power terminals and additional
Keypad Bus or LX‑Bus
connectors for a clean install.
The861Module is compatible with
all DMP XT30/XT50Series and
XR150/XR550Series panels, as well
as panels from other manufacturers.
For maximum flexibility, the
module is rated for either12VDC
or24VDC power input with a
maximum current handling capacity
of8Amps on the module RED PWR
IN and BLK GND IN terminals.
Compatibility
XT30/XT50Series panels
XR150/XR550Series panels
What is Included?
One861Module
One Pair of18AWG Red and
Black Wires (8”)
One Model330 Dual‑Ended
4‑Wire Harness
Hardware Pack
1
MOUNT THE MODULE
Themodule can be mounted in a DMP enclosure using the
standard3‑hole mounting pattern. Refer to Figure 2 as needed
during installation.
1. Hold the plastic standos against the inside of the enclosure
side wall.
2. Insert the included Phillips head screws from the outside of
the enclosure into the standos. Tighten the screws.
3. Carefully snap the module onto the standos.
Figure 1: 861 Module
Figure 2: Stando and Module Installation
BACK
1
2
3
Designed, engineered, and
manufactured in Springfield, MO
using U.S. and global components.
LT-0795 20105
861 AUXILIARY POWER
DISTRIBUTION AND
BUS MODULE
Ordering Information
860 Power Distribution/4 Wire Bus Module
Accessories
330 Dual-Ended 4-Wire Harness
Compatibility
XT30/XT50 Series Panels
XR150/XR550 Series Panels
MODEL
861
R B R B
RED PWR OUT BLK GND OUT
4-WIRE
BUS-A
RED
PWR IN
BLK
GND IN
4-WIRE
BUS-B
INTRUSION FIRE ACCESS NETWORKS
2500 North Partnership Boulevard
Springfield, Missouri 65803-8877
800.641.4282 | DMP.com
© 2020
WIRE THE MODULE
2
The861Module provides8connections to the panel LX‑Bus or Keypad Bus. For example, connect Bus‑A to
the LX‑Bus and Bus‑B to the Keypad Bus. To configure all861Module headers to operate as only LX‑Bus or
Keypad Bus connections, join Bus‑A and Bus‑B together with the provided Model330harness.
Caution: Disconnect all power from the panel before wiring the module. Observe polarity on all
connections. Failure to do so may result in equipment damage or personal injury.
Refer to Figure 3 during wiring.
1. If necessary, join the module buses with the provided Model 330 harness. Connect themodule buses to
the panel.
2. Wire the861RED PWR IN and BLK GND IN Terminals to the panel Keypad Bus or to505‑12DC
terminals.
3. Connect2‑wire devices tomoduleRED PWR OUT and BLK GND OUT as needed.
MODEL
861
RED PWR OUT
To Panel
Keypad Bus
or 505-12
Power Supply
BLK GND OUT
RED
PWR IN
BLK
GND IN
R B
4-WIRE
BUS-B
R B
4-WIRE
BUS-A
RED
BLK
BLK
RED
To LX-Bus or
Keypad Bus
Max 8 Amps
2-Wire Device
Positive
2-Wire Device
Negative
12 VDC or 24 VDC
Bus-A and Bus-B
provide 8 LX-Bus
connections and
8 Keypad Bus
connections. To
configure all headers
to operate as only
Keypad Bus or LX-Bus
connections, wire
Bus-A and Bus-B
together with the
Model 330 harness.
Figure 3: Wiring Connections
/