Aux Relay
Alarm Relay
Output Relay
Ground - REQUIRED
Follow these basic steps to perform desired programming, See programming options table for PROGRAM STEPS.
1. Press arrow buttons or ENT button to ACTIVATE LED display.
2. Press arrow buttons again to CHOOSE desired PROGRAM STEP.
3. Press ENT button to ENTER desired PROGRAM STEP. (LED display number will blink after ENT button has been pressed).
4. Press arrow buttons to choose SELECTION NUMBER for desired function of program step.
5. Press ENT button to program SELECTION NUMBER for desired function of program step. (Function has now been programmed into board).
6. Press ENT button again to exit programming OR after 10 seconds, board will automatically exit programming.
Note: Repeat these steps for all other desired programming functions. Each tracker expansion board will have to be INDIVIDUALLY programmed
with desired functions. After all tracker expansion boards have been programmed.....
Basic Programming Sequence on EACH Wireless Tracker Expansion Board
Manage the Complete Access Control System from Your PC
SOFTWARE
INSTALLED
Refer to the DKS Remote
Account Manager Software
to program and manage the
complete system.
Relay jumpers MUST be
set for each relay used.
Programming Options on EACH Wireless Tracker Expansion Board
Your PC connected to the access control system. Either IM Server OR TCP/IP OR RS-232 OR
Modem to Modem Connection. See PC Programmable Telephone Entry and Access Control
Systems Installation/Owner’s manual for more information about connection options.
14
13
12
11
6
5
4
3
2
1
DOORKING
2363-010
PAIRED
ON
OFF
0
F
E
D
C
B
A
9
8
7
6
5
4
3
2
1
0
F
E
D
C
B
A
9
8
7
6
5
4
3
2
1
RF RANGE
CH
NET
ID
RCVD
ALLOW
DENY
STAT US
SYNC LOST
SYNC REVD
HEARTBEAT
DISPLAY
OFF/ON
RESET
PROG
RF
STAT STRENGTH
RLY 1RLY 2
DOORKING
2361-010
PAIR
34
33
32
31
30
29
28
27
26
25
24
23
22
21
14
15
16
17
18
19
20
13
12
11
10
9
8
7
6
5
4
3
2
1
ON
1
0
BOARD ADDRESS
0
9
8
7
6
5
4
3
2
1
NC
OUTPUT
RELAY
NO
NC
ALARM
RELAY
NO
NC
AUX
RELAY
NO
ENT
RESET
2358-010
RF
DATA
RF
SECURE
RF
STATUS
CODE
SENT
CODE
GOOD
CODE
BAD
PROGRAM
0
F
E
D
C
B
A
9
8
7
6
5
4
3
2
1
0
F
E
D
C
B
A
9
8
7
6
5
4
3
2
1
RF ID RF CH
RF
STRENGTH
RF
LOST
POWER
RF
SYNC
1489-010
RF RANGE
7 8 9
4 5 6
1 2 3
0
OPER
WXYZTUVPQRS
MNOJKLGHI
DEFABCSP
CALL
Z
A
TELEPHONE ENTRY SYSTEM
HOLD TO SCAN
OPERATING INSTRUCTIONS
Use “A to Z” Buttons to Locate
Name and Code Number on Display.
Names are In Alphabetical Order.
To Call, Enter Code Number on
Keypad or Press “Call” Button. If
Line is Busy, Press “#” or “Call” to
Hang Up. Try Again.
Enter on Open Display and Tone.
1.
2.
3.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
00 - 99
00 - 99
00 - 99
00 - 99
00 - 99
0 or 1
0 or 1
0 or 1
0 or 1
0 or 1
0 or 1
0 - 12
0 - 4
5
0 or 1
00
01 - 99
00
01 - 99
00
01 - 99
00
01 - 99
00
01 - 99
0
1
0
1
0
1
0
1
0
1
0
1
0
1
2
3
4
5
6
7
8
9
10
11
12
0
1
2
3
4
5
Program
Step
Factory
Default
Description
Options
Selection
Number
Function
Door Strike Timer
Free Exit Timer, Strike Time
Door Ajar Timer
Aux Relay Timer
Free Exit Timer, Aux Relay
Free Exit, No Strike
Not Used
Door Contact Switch Logic
Auto Relock
Beeper / LED Hold Open
Hold Open or Hold Egress functions
Dual Door Mode
Not Used
Not Used
Aux Relay Functions
Alarm Relay Functions
Not Used
Not Used
Reset to Factory Defaults
View RF POT Setting
View RF Signal Loss
Card Code Forwarding
01 - 1 second
01 - 1 second
12 - 60 secs
12 - 60 secs
01 - 1 second
1 - Activate
0 - N.O.
0 - Disabled
0
0 - No relay
functions
0 - Disabled
0 - Disabled
0 - Disabled
0 - Off
Adjustable Setting
Displays on LED
Door Operation Note:
PROPER Condition: The access control
system OR request to exit device HAS
activated the OUTPUT RELAY on the
tracker expansion board and the door
contact switch is CLOSED (Door is
OPEN). This indicates that the door has
been PROPERLY OPENED.
FORCED Condition: The access control
system OR request to exit device has
NOT activated the OUTPUT RELAY on
the tracker expansion board and the
door contact switch is CLOSED (Door is
OPEN). This indicates that the door has
been FORCED OPENED.
Sets Strike Time for output relay (term 25 & 26)
0.25 second strike time
Strike time in 1-second increments
Set Strike Time for RX (Request to Exit) of output relay (input at term 18)
0.25 second Egress Strike time
Egress Strike time in 1-second increments
Timer starts when valid access has been granted.
1 second Door Ajar Timer
Timer set in 5-second increments: 01 = 5 seconds, 10 = 50 seconds
Timer setting for Aux Relay activation in 5-second increments
1 second Door Ajar Timer
Timer set in 5-second increments: 01 = 5 seconds, 10 = 50 seconds
Set Strike Time for RX (Request to Exit) of Aux relay (ONLY available if Dual Door Mode step 12 is ON)
0.25 second Egress Strike time
Egress Strike time in 1-second increments
Set RX (Request to Exit) function. Activate Output Relay or do not Activate Output Relay
Do Not Activate Output Relay or Reader Beeper/LED when RX input is received
Activate Output Relay and Reader Beeper/LED for Free Exit Strike Time when RX received
Sets type of Door Switch contacts
N.O. contact from door switch with Door Closed (Circuit Open - CO)
N.C. contact from door switch with Door Closed (Circuit Close - CC)
Turns on Auto Relock function (not available if Dual Door Mode, step 12 is ON)
Output Relay is activated for Strike Time
Door Contact Switch required. If door returns to closed position during Strike Time
door will “relock” after 1 second, even if strike time has not expired.
Sets how BEEPER or LED will function during Hold Open
When Hold Open occurs, Beeper or LED is active only during Strike Timer
When Hold Open occurs, Beeper or LED will remain active during Hold Open
Sets how Aux & Alarm Relay responds during Hold Open or Hold Egress situation
No Aux Relay functions. Alarm will be in “Reset”. If Alarm Relay is set for “integral” mode, Alarm relay will not activate. If
Alarm Relay set for “Bypass” mode, Alarm Relay will activate for Hold Open period or Extended Egress Hold.
Aux Relay will function for all settings. If Alarm Relay is set for “integral” mode, Alarm relay will not activate. If Alarm Relay set
for “Bypass” mode, Alarm Relay will activate for Hold Open period or Extended Egress Hold.
Sets Tracker to function as 2 Access Points (2 tracker addresses)
Disabled, Tracker functions as single access point
Dual Mode: Tracker functions as set board address and next sequential address
Card Read will be sent to controller as set board address, access is granted or denied
Card then sent as set address +1, access granted or denied. Aux Relay becomes 2nd output relay. All other Aux Relay functions
disabled. Door Contact switch becomes RX (Request to Exit) for 2nd address.
Sets function for Aux Relay
Aux Relay Disabled
No Door Ajar Timer: Requires Door Contact Switch. Aux Relay activates when Door Not Closed.
No Door Ajar Timer, Pulse: Requires Door Contact Switch. Aux Relay “pulses” when Door Not Closed.
Door Ajar Timer: Requires Door Contact Switch. When door opens, start Door Ajar Timer. When timer expires Aux Relay
activates for Aux Relay timer or until door closes, whichever occurs first.
Door Ajar Timer, Pulse: Requires Door Contact Switch. When door opens, start Door Ajar Timer. When timer expires Aux Relay
Pulses for Aux Relay timer or until door closes, whichever occurs first.
Door Ajar, Pulse warning the ON: Requires Door Contact Switch. When door opens, Pulse Aux Relay and start Door Ajar Timer.
When timer expires Aux Relay ON for Aux Relay timer or until door closes, whichever occurs first.
Door opens for any reason, Start Door Ajar timer and pulse Aux Relay. When Door Ajar timer expires, start Aux Timer and
continue Pulsing Aux Relay.
When Door Closes or both timers expire, turn off Aux Relay
Aux Relay as 2nd Alarm Relay. Aux Relay will mirror Alarm Relay functions.
Aux Relay as 2nd Alarm Relay, PULSE. Aux relay will Pulse during any Alarm Relay activation.
Good Card: Aux Relay will activate for Aux Relay timer for any Access Granted Card
Any Card: Aux Relay will activate for Aux Relay Timer when any card has been presented.
Bad Card: Aux Relay will activate for Aux Relay timer when a card has been denied
Warn before Hold Open or Release of Hold Open: Aux relay will activate for Aux Relay timer when scheduled Hold Open begins
or ends. Output Relay will be delayed until Aux Timer expires. DO NOT set Aux Timer above 60 seconds in this mode.
Sets function for Alarm Relay
Aux Relay Disabled
Bypass Mode: Alarm Relay provides “Bypass” to Alarm Door Switch. With proper door input (access or egress) activate Alarm
Relay, start Strike timer and Door Ajar timer. When Door Ajar timer expires, deactivate Alarm Relay.
If second Door Contact Switch is provided, generate transaction for Door Ajar and Door Closed following Door Forced condition.
Also generate transaction for Door Forced condition.
Integral Mode, Door Ajar Timer: Door Contact Switch connected to Tracker, Alarm Relay provides connection directly to Alarm
System. When door is opened for any reason, start Door Ajar timer. When Door Ajar timer expires and Door is still OPEN,
activate Alarm Relay. Reset when door closes.
Send Door Ajar and Door Close transactions.
Integral Mode, Proper and Forced condition: Door Contact Switch connected to Tracker, Alarm Relay provides connection
directly to Alarm System. With proper door input (access or egress) start Strike timer and Door Ajar timer. When Door Ajar
timer expires and Door is still OPEN, activate Alarm Relay. Reset when door closes.
If door is opened without proper condition, activate alarm relay. When door closes deactivate Alarm Relay. Send Door Ajar,
Door Close and Door Forced transactions.
Gate Alarm Function: Alarm Relay will activate for 1 second when tracker board receives a “Gate Forced” or “Gate Obstructed”
transaction from the operator control board.
Sets all parameters to Factory Default
Sets maximum amount of allowable signal strength loss
Displays current signal loss between Base and Tracker.
Sets Wireless Tracker to act as Repeater
ONLY USE AS DIRECTED BY DOORKING TECH SUPPORT 0=Repeater Mode OFF 1=Repeater Mode ON
Rev-E 1-13-14
UNPAIRED MODE:
Steady Red – Board is communicating with unpaired wireless baseboard.
Blinking Red – Board is NOT communicating with unpaired wireless baseboard.
PAIRED MODE:
Steady Green - Board is communicating with paired wireless baseboard.
Blinking Green - Board is NOT communicating with paired wireless baseboard.
QUICKSTART ADJUSTMENTS AND PROGRAMMING OPTIONS FOR WIRELESS BOARDS GUIDELINES
PAIRED
ON
OFF
Baseboard LED Display
LED Display
When board is powered up OR PROG
Button is pressed, LED display (display
jumper ON) shows RF RANGE adjustment
setting on board for a few seconds
(number has a decimal point in
the lower right of the LED
Display), then LED display will
automatically change to RF STRENGTH
number continuously (NO decimal point
displayed for RF strength number). This
number is the ACTUAL RF signal loss
being sent/received by the board.
Display Jumper
Program Button - Press after adjustment is made to RF RANGE,
RF ID or RF CHANNEL before changes will take effect.
RF STAT
ON - Connection to at least 1 remote
Blinking - No connection
RED - Not paired
Green - Paired
STRENGTH
Green - Good
Amber - Marginal
Red - Poor
RF STRENGTH
Green - Good
Amber - Marginal
Red - Poor
PAIR Button - Press and hold 3 sec. to PAIR with all wireless tracker boards.
Press to display RF RANGE and RF STRENGTH on LED Display.
Relay 2 (2C) Com
Relay 2 (2RY)
Relay 1 (1C) Com
Relay 1 (1NO or 1NC)
RESET Button - Press to reboot board.
RESET Button -
Press to reboot board.
CH
NET
ID
0
F
E
D
C
B
A
9
8
7
6
5
4
3
2
1
0
F
E
D
C
B
A
9
8
7
6
5
4
3
2
1
All tracker expansion boards
MUST be set to SAME channel
number as wireless baseboard.
All tracker expansion boards
MUST be set to SAME NET ID
number as wireless baseboard.
IMPORTANT
IMPORTANT
RF
CH
RF
ID
0
F
E
D
C
B
A
9
8
7
6
5
4
3
2
1
0
F
E
D
C
B
A
9
8
7
6
5
4
3
2
1
All tracker expansion boards
MUST be set to SAME channel
number as wireless baseboard.
All tracker expansion boards
MUST be set to SAME NET ID
number as wireless baseboard.
IMPORTANT
IMPORTANT
4-Pin Terminal:
RLY 2: Must connect to access control
system’s Relay 2 for wireless tracker
expansion board addresses 3-10.
Access control system’s relay 2 jumper
MUST be set to NO or NC.
RLY 1: Must connect to access control system’s
Relay 1 for wireless tracker expansion board
addresses 11-18. See instruction sheet with
wireless baseboard kit for more information.
RF RANGE
Set to max (full clockwise). This may
need to be changed when using a
repeater. See Repeater instruction
sheet and Wireless Start-Up guide for
more information.
RF Range
Set to max (full clockwise). This may
need to be changed when using a
repeater. See Repeater instruction sheet
and Wireless Start-Up guide for more
information.
Power
Transformer
Power
Transformer
16.5 VAC
20 VA
Antenna is REQUIRED.
Antenna is REQUIRED.
REQUIRED
REQUIRED
18 AWG 100 ft max
16 AWG 200 ft max
18 AWG 100 ft max
16 AWG 200 ft max
Connect Existing
Auxiliary Terminal
Access Control
System Power
HARDwired Card Reader or Relay 1/Wiegand 1
connection ONLY. DO NOT connect HARDwired tracker
expansion boards or card reader to wiegand 1
(terminals 11-14) if WIRELESS boards will be using
wiegand 1).
See instruction sheet with wireless baseboard kit
for more information.
For COMPLETE programming and adjustment instructions, please refer to the instruction sheets included with the wireless kits,
Wireless Layout and Start-Up Guide and the HARDwired Installation/Owner’s manual (P/N 2358-065).
16.5 VAC
20 VA
Wireless Baseboard
RF SYNC:
Slowly Blinking Blue -
Sync to baseboard.
Board addresses MUST be set for
each board used.
See other side for more information.
Access Control Device
26, 30, 31-Bit Wiegand
Data 0
Data 1
Com
12 VDC
Request to Exit
Door Contact Switch
Card Reader
LED/Beeper
Control
RF SECURE:
Press after adjustment has been made to
RF RANGE, RF ID or RF CH before
changes will take effect.
Press and hold for 3 sec. to PAIR to
wireless baseboard, may take up to 20 sec.
(RF SECURE LED Paired - steady GREEN).
Press and hold again for 3 sec. to UNPAIR
from wireless baseboard if necessary
(RF SECURE LED Unpaired - steady RED).
•
•
•
Program Button:
Channel and ID
Wireless Tracker Expansion RF Board Adjustments
Wireless Tracker
Expansion Board
RF DATA – (Green) Reply from baseboard.
RF STATUS – (Green) Not used.
CODE SENT – (Yellow) Card code is sent to baseboard.
CODE GOOD – (Green) Access granted.
CODE BAD – (Red) Access denied or card code not in database.
Yellow - RECD
Green - ALLOW
Red - DENY
Not used - STATUS
Normal Data
Communication
Red - No Signal - SYNC LOST
SYNC REVD:
Blinking Blue - Searching
Steady Green - connected.
HEARTBEAT:
Blinking Green - Normal
IMPORTANT Display Decimal Point Note
When decimal point is
displayed: Indicates you are
SELECTING a program step.
When decimal point is NOT
displayed: Indicates you are
IN a program step.
DO NOT connect HARDwired tracker expansion boards to wiegand 1 (terminals 11-14)
if WIRELESS boards will be using wiegand 1).
ON - Only accepts card codes
from PAIRED tracker boards.
OFF - Normal Setting - Allows
card codes from paired or
unpaired tracker boards.