Danfoss Controller for evaporator control AK2-CC 303A Menu operation via AKM User guide

Type
User guide

Danfoss Controller for evaporator control AK2-CC 303A Menu operation via AKM is a versatile device that can be used for a variety of applications. With its ability to monitor and control multiple parameters, this device can help you to optimize the performance of your refrigeration and air conditioning systems.

Some of the key features of the Danfoss Controller for evaporator control AK2-CC 303A Menu operation via AKM include:

  • Monitoring of up to eight measurements
  • Control of various settings, including ON/OFF settings, variable value settings, time settings, and reset alarms
  • Documentation of settings for individual controllers

Danfoss Controller for evaporator control AK2-CC 303A Menu operation via AKM is a versatile device that can be used for a variety of applications. With its ability to monitor and control multiple parameters, this device can help you to optimize the performance of your refrigeration and air conditioning systems.

Some of the key features of the Danfoss Controller for evaporator control AK2-CC 303A Menu operation via AKM include:

  • Monitoring of up to eight measurements
  • Control of various settings, including ON/OFF settings, variable value settings, time settings, and reset alarms
  • Documentation of settings for individual controllers
REFRIGERATION AND
AIR CONDITIONING
Controller for evaporator control
AK2-CC 303A
Menu operation via AKM
2 Menu operation RC8BP202 © Danfoss 05/2005 AK2-CC 303A Version 1.0x
Menu list This menu function can be used together with system software type AKM. The description is divided
up into function groups that can be displayed on the PC screen. Within each group it is now possible
to show the measured values, or settings. Regarding the use of AKM, reference is made to the AKM
Manual.
Measurements The various measurements can be read directly. If a graphic display of the measurements is required,
up to eight of them can be shown. Select the required measurements and push Trend”.
Settings Settings can only be made for the daily operation. Configuration settings cannot be seen, changed or
written out. They can only be made from the Service Tool programme.
There are four kinds of settings, ON/OFF settings, settings with a variable value, time settings and
“reset alarms”.
Enter the new value or move the sliding scale up or down.
The new value will apply, when OK” is pushed.
Set the required value and push OK”
Validity This menu operation (from Dec. 2004) applies to controller type AK2-CC 303A, code Nos
080Z0121 - 080Z0122 - 080Z0123 with programme version 1.0x.
The operation is divided up into several
function groups. When a selection has been
made, push OK”, and you may continue to
the next display. By way of example, “Com
-
mon thermostat” has been selected here.
From the measure line the different val
-
ues can be read. The values are constantly
updated.
In the list of settings the set values can be
seen. If a setting has to be changed, select
the parameter and proceed via “OK”.
Function groups
AK2-CC 303A Version 1.0x Menu operation RC8BP202 © Danfoss 05/2005 3
Go through the individual functions one by one and make the required settings. When settings have
been made for one controller, the set values may be used as basis in the other controllers of the same
type and with the same software version. Copy the settings by using the copy settings function in the
AKM programme, and adjust subsequently any settings where there are deviations.
NB! If a list is required for noting down the individual settings, a printout can be made of it with
a function in the AKM programme. Read the next section, “Documentation.
Documentation Documentation of the settings of the individual controllers can be made with the print function in the
AKM programme. Select the controller for which documentation of the settings is required and select
the “Print Settings” function (cf. also the AKM Manual).
Functions Shown below are function groups with corresponding measurements and settings. A printout of the
given settings can be made using the AKM function “Print Settings (see above).
4 Menu operation RC8BP202 © Danfoss 05/2005 AK2-CC 303A Version 1.0x
Select application
Measurements AK2 error When “ON”, the controller is in alarm condition.
Reg. condition A Regulation condition for section A
0 = Main switch interrupted
1 = Startup
2 = Adaptive regulation
3= Fill evaporator
4 = Defrost
5 = Startup after defrost
6 = Forced closing
7 = Injection problem
8 = Emergency cooling (sensor error)
9 = Modulating thermostat regulation
10 = Melt function active
11 = Door open
12 = Appliance cleaning
13 = Cutout thermostat
14 = Forced cooling
Reg. condition B Regulation condition for section B
Same as for Reg. condition A
Reg. condition C Regulation condition for section C
Same as for Reg. condition A
Reg. condition D Regulation condition for section D
Same as for Reg. condition A
No. of evaporators Readout number of evaporators
Valve type Readout of selected valve type
0 = Ventil type not selected, 1= AKV, 2 = TEV
Refrigerant R Readout of selcted refrigerant
Configuration lock Not used
Select application Not used
Select refrigerant Not used
Settings Main switch Main switch: ON: Regulation
OFF: Controller stopped
Common thermostat
Measurements AK2 error When “ON”, the controller is in alarm condition.
Reg. condition A Regulation condition for section A
0 = Main switch interrupted
1 = Startup
2 = Adaptive regulation
3= Fill evaporator
4 = Defrost
5 = Startup after defrost
6 = Forced closing
7 = Injection problem
8 = Emergency cooling (sensor error)
9 = Modulating thermostat regulation
10 = Melt function active
11 = Door open
12 = Appliance cleaning
13 = Cutout thermostat
14 = Forced cooling
Reg. condition B Regulation condition for section B
Same as for Reg. condition A
AK2-CC 303A Version 1.0x Menu operation RC8BP202 © Danfoss 05/2005 5
Reg. condition C Regulation condition for section C
Same as for Reg. condition A
Reg. condition D Regulation condition for section D
Same as for Reg. condition A
Night status Status of night setback function
ON: Thermostat cutout value to be raised by ”Night setoff setting
OFF: Normal situation (day)
Thermostat band Actual thermostat band: 1= Band 1 and 2=Band 2
Ext. Ref offset K Contribution from external reference displacement
Settings Main switch Main switch: ON: Regulation
OFF: Controller stopped
Thermostat type Select thermostat type:
0= no thermostat, 1= ON/OFF regulation, 2= Modulating thermostat
Common Ther. (A) Select common or individual thermostat function:
ON = thermostat in section A only (All sections follows thermostat A)
OFF = Individual thermostat function in all sections
Ther. band control Select thermostat band function active
Ther. band select Select thermostat band: 1 = Thermostat band 1 is active, 2 = Thermostat band 2 is
active
Day/Night control Select day/night function (yes/no)
Melt function Select melt function (yes /no)
Melt interval min Set time interval between melt functions
Melt time min Set melt time
Ext. Ref. control Select reference displacement for thermostat via external voltage signal
Ext.Ref. offset Max Displacement of reference at max. signal
Ext.Ref. offset Min Displacement of reference at min. signal
Section A - Thermostat
Measurements AK2 error When “ON”, the controller is in alarm condition.
Reg. condition A Regulation condition for section A
0 = Main switch interrupted
1 = Startup
2 = Adaptive regulation
3= Fill evaporator
4 = Defrost
5 = Startup after defrost
6 = Forced closing
7 = Injection problem
8 = Emergency cooling (sensor error)
9 = Modulating thermostat regulation
10 = Melt function active
11 = Door open
12 = Appliance cleaning
13 = Cutout thermostat
14 = Forced cooling
Reg. condition B Regulation condition for section B
Same as for Reg. condition A
Reg. condition C Regulation condition for section C
Same as for Reg. condition A
Reg. condition D Regulation condition for section D
Same as for Reg. condition A
Ther. Air A °C Actual air temperature for thermostat in section A
Actual Cutin A °C Actual cutin value for thermostat in section A
Actual Cutout A °C Actual cutout value for thermostat in section A
S3A °C Temperature at S3 sensor in section A
S4A °C Temperature at S4 sensor in section A
Ther. runtime A min Duration of latest or ongoing thermostat cutin time
Ther. duty cycle A % Percentage of time during the latest 24 hour period where thermostat has been cut in
6 Menu operation RC8BP202 © Danfoss 05/2005 AK2-CC 303A Version 1.0x
Alarm Air A °C Actual air temperature for alarm thermostat
Alarm Air A Max °C Maximum air temperature for alarm thermostat during the last 24 hours
Alarm AirA outs.lim% Percentage of time during the latest 24 hour period where the air temperature for
the alarm thermostat has been outside de indicated alarm limits
Product temp. A °C Actual air temperature for product sensor
Display readout A °C Actual temperature readout on diplay
Settings Main switch Main switch: ON: Regulation
OFF: Controller stopped
Ther. air S4% Day S4 weighting by day. S3 is automatically weighted.
Ther. Air S4% Night S4 weighting by day. S4 is automatically weighted
Cutout °C Setting of thermostat cutout value Section A
Diff. K Setting of thermostat differential Section A
Cutout 2 °C Setting of thermostat band 2 cutout value
Diff. 2 K Setting of thermostat differential for thermostat band 2
Night setback K Night setback value section A
S4 Frost function Select frost alarm function for low S4 temperature
S4 Frost limit °C Set alarm limit for frost alarm function
Alarm thermostat Select alarm thermostat
Alarm Air S4% Weighting of S4 for alarm thermostat
High limit °C Set high alarm limit for alarm thermostat
High limit 2 °C Set high alarm limit for alarm thermostat band 2
High delay min Time delay for high temperature alarm during normal regulation
High del. pulld. min Time delay for high temperature alarm after startup or duirng defrost
Low limit °C Set low alarm limit for alarm thermostat
Low limit 2 °C Set low alarm limit for alarm thermostat band 2
Low delay min Time delay for alarm when too low temperature is registered
Section B - Thermostat
Same settings as above for section B
Section C - Thermostat
Same settings as above for section C
Section D - Thermostat
Same settings as above for section D.
The functions "Display control", "Display S4%" and "Display Offset K" are not in section D.
AK2-CC 303A Version 1.0x Menu operation RC8BP202 © Danfoss 05/2005 7
Section A - Injection
Measurements AK2 error When “ON”, the controller is in alarm condition.
Reg. condition A Regulation condition for section A
0 = Main switch interrupted
1 = Startup
2 = Adaptive regulation
3= Fill evaporator
4 = Defrost
5 = Startup after defrost
6 = Forced closing
7 = Injection problem
8 = Emergency cooling (sensor error)
9 = Modulating thermostat regulation
10 = Melt function active
11 = Door open
12 = Appliance cleaning
13 = Cutout thermostat
14 = Forced cooling
Reg. condition B Regulation condition for section B
Same as for Reg. condition A
Reg. condition C Regulation condition for section C
Same as for Reg. condition A
Reg. condition D Regulation condition for section D
Same as for Reg. condition A
AKV opening A % AKV valves opening degree (%)
Average AKV OD A % Average AKV opening degree for the latest 24 hour period
Te temp. °C Evaporating temperature measured in °C
S2A °C Gas outlet temperature on evaporator
Superheat A K Superheat
Superheat Ref. A Reference for superheat in section A
Forced closing status Status on forced closing of valve
1-2: means that valve is force-closed via Injection ON input or via network signal
0 no forced closing
1 Forced closing, fans run
2 Forced closing, fans stopped
Pe pressure Bar Evaporating pressure measured in Bar
Pc pressure Bar Condensing pressure measured in Bar
Tc temp. °C Condensing temperature measured in °C
TEV valve state A Status on TEV valve
Settings Main switch Main switch: ON: Regulation
OFF: Controller stopped
AKV Injection Ctrl. AKV injection function (OFF = no injcection)
Superheat min. K Min. superheat measured in K
Superheat max. K Max. superheat measured in K
MOP control MOP function
MOP temperature °C Setting of MOP temperature in °C
TEV injection ctrl. TEV injection functions (OFF = no injection)
Section B - Injection
Same settings as above for section B
8 Menu operation RC8BP202 © Danfoss 05/2005 AK2-CC 303A Version 1.0x
Section C - Injection
Same settings as above for section C
Section D - Injection
Same settings as above for section D
Defrost
Measurements AK2 error When “ON”, the controller is in alarm condition.
Reg. condition A Regulation condition for section A
0 = Main switch interrupted
1 = Startup
2 = Adaptive regulation
3= Fill evaporator
4 = Defrost
5 = Startup after defrost
6 = Forced closing
7 = Injection problem
8 = Emergency cooling (sensor error)
9 = Modulating thermostat regulation
10 = Melt function active
11 = Door open
12 = Appliance cleaning
13 = Cutout thermostat
14 = Forced cooling
Reg. condition B Regulation condition for section B
Same as for Reg. condition A
Reg. condition C Regulation condition for section C
Same as for Reg. condition A
Reg. condition D Regulation condition for section D
Same as for Reg. condition A
Defrost condition A Defrost condition for section A
0: no defrost
1: Pump down
2: Delay
3: Defrost
4: Wait after defrost
5: Emptying
6: Drip-off
7: Fan delay
8: Defrost (special)
Defrost condition B Defrost condition for section B
Same settings as for Defrost Condition A
Defrost condition C Defrost condition for section C
Same settings as for Defrost Condition A
Defrost condition D Defrost condition for section D
Same settings as for Defrost Condition A
Defrost temp. A Temperature at defrost sensor in sektion A
Defrost temp. B Temperature at defrost sensor in sektion B
Defrost temp. C Temperature at defrost sensor in sektion C
Defrost temp. D Temperature at defrost sensor in sektion D
AK2-CC 303A Version 1.0x Menu operation RC8BP202 © Danfoss 05/2005 9
DOD status A Status on adaptive defrost
0: Signal error
1: Tuning
2: OFF
3: No ice build-up
4: A little ice build-up
5: Medium ice build-up (start of defrost)
6: Heavy ice build-up
DOD status B Status on adaptive defrost
Same setting as for DOD status A
DOD status C Status on adaptive defrost
Same setting as for DOD status A
DOD status D Status on adaptive defrost
Same setting as for DOD status A
Defrost time A min Actual defrost cutin time or duration of the latest finished defrosting period in section A
Defrost time B min Actual defrost cutin time or duration of the latest finished defrosting period in section B
Defrost time C min Actual defrost cutin time or duration of the latest finished defrosting period in section C
Defrost time D min Actual defrost cutin time or duration of the latest finished defrosting period in section D
Avg. def. time A min Average defrost time for latest 10 defrosts in section A
Avg. def. time B min Average defrost time for latest 10 defrosts in section B
Avg. def. time C min Average defrost time for latest 10 defrosts in section C
Avg. def. time D min Average defrost time for latest 10 defrosts in section D
Settings Main switch Main switch: ON: Regulation
OFF: Controller stopped
Defrost control Select defrost. Yes/no
Defrost type Select defrost type
1: Electric defrost
2: Naturaly defrost
Manuel start defrost Start of manual defrost. Activated by ON.
Manuel stop defrost Stop of manual defrost.
Fan run during def. Setting of fan operation during defrost.
Defrost stop sensor Select defrost stop sensor
1: Stop on time
2: Stop on S2
3: Stop on S3
4: Stop on S4
5: Stop on S5-1
6: Stop on S5-1 and S5-2 (when both sensors has reached the stop temperature)
Defrost stop temp °C Temperature value for defrost stop (stop on time as security)
Max. Defr. time min. Max. Permisible defrost time in minutes. (security time on tempeature stop)
Pump down delay min Time delay before start of defrost. The valve is closed and the evaporator is emptied
of refrigerant.
Drip delay min Time delay after defrost where drops of water run off the evaporator.
Fan delay min Max. time delay from injection start and until the fans start (freezing of water drops)
Fan start temp. °C Setting of S5 temperature for start of fans
Max. hold time min Max. time delay for start of refrigeration when the controller’s defrost is coordinated
with other controllers via the data communication
DOD mode Setting of adaptive defrost
0: No adaptive defrost
1: Monitor ice build-up (no defrost start)
2: Adaptive defrost can start defrosts during the day
3: Adaptive defrost can start defrosts day and night
DOD reset Reset adaptive defrost (in some cases a defrost is started)
Min. time betw. Def. Minimum time between defrosts. Ensures that a defrost schedule does not start a
defrost just after a adaptive defrost has been started.
10 Menu operation RC8BP202 © Danfoss 05/2005 AK2-CC 303A Version 1.0x
Common functions
Measurements AK2 error When “ON”, the controller is in alarm condition.
Reg. condition A Regulation condition for section A
0 = Main switch interrupted
1 = Startup
2 = Adaptive regulation
3= Fill evaporator
4 = Defrost
5 = Startup after defrost
6 = Forced closing
7 = Injection problem
8 = Emergency cooling (sensor error)
9 = Modulating thermostat regulation
10 = Melt function active
11 = Door open
12 = Appliance cleaning
13 = Cutout thermostat
14 = Forced cooling
Reg. condition B Regulation condition for section B
Same as for Reg. condition A
Reg. condition C Regulation condition for section C
Same as for Reg. condition A
Reg. condition D Regulation condition for section D
Same as for Reg. condition A
Cleaning runtime min Duration of ongoing or last concluded appliance cleaning
Fan status Status on fan
Rail heat status Status on rail heat
Light status Status on light
Door switch status Status on door contact
Door open time min Duration of ongoing or latest door opening
Door open 24h min Total duration of door openings during the latest 24 hour period
Door openings 24h Number of door openings within the latest 24 hour period
Compressor status Compressor status
Ext. Main switch Status on external Main switch
DI alarm Status on DI alarm
AI alarm % Status on AI alarm
Alarm relay Status on alarm relay
Settings Main switch Main switch: ON: Regulation
OFF: Controller stopped
Case cleaning ctrl. Select whether appliance cleaning function is to be active.
Case cleaning mode Appliance cleaning function
0: Appliance cleaning not started
1: Only fan is operating (defrost of evaporator)
2: All outputs in pos. OFF (cleaning can be carried out)
Defr. at case clean. Select whether a defrost is to be accomplished when the appliance cleaning is
activated
Pulse fans mode Select fan pulsation
0: no pulse
1: Pulse in thermostats cut out periode
2: Pulse in thermostats cutout periode during night
Fan ON % Setting of the fans ON periode in procent of the time.
Fan duty cycle Period time for total ON/OFF time
Fan stop on S5 Select whether fan to be stopped at high S5 temperature
Fan stop temp °C Fan stop based on temperature (uses S5A sensor)
Rail heat control Select rail heat control (0=OFF, 1=ON)
Rail ON Day % During day operation: Setting of rail heat ON-period in procent of the time.
Rail ON Night % Durign night operation: Setting of rail heat ON-period in procent of the time.
Rail duty cycle min Periodtime for toatal ON/OFF time
Rail heat at defrost Rail heat during defrost
AK2-CC 303A Version 1.0x Menu operation RC8BP202 © Danfoss 05/2005 11
Light control Select whether light control is to be active
Light mode Select light control function
1: Light controlled according to day/night function (light ON during the day)
2: Light controlled via network signal
3: Light controlled via door switch
Light off at defrost Light switch off during defrost
Door switch mode Door contact function
0: no door contact
1: Door alarm function
2: Door alarm as well as stop of injections and fans
Cooling restart min If the door has not been closed by the expiry of this time delay refrigeration will be
restarted (only if ”Door switch mode” is set at 2)
Door alarm delay Delay on door alarm
Door Light OFF delay When the door has been closed the light is switched off after expiry of this tuime
delay
Compressor control Select compressor control
Min. ON time m Min. operation time in minuttes for compressor
Min. restart time m Min. restart time in minutes for compressor
Runtime total h Total operation time in minutes for compressor
12 Menu operation RC8BP202 © Danfoss 05/2005 AK2-CC 303A Version 1.0x
Master control
Measurements AK2 error When “ON”, the controller is in alarm condition.
Reg. condition A Regulation condition for section A
0 = Main switch interrupted
1 = Startup
2 = Adaptive regulation
3= Fill evaporator
4 = Defrost
5 = Startup after defrost
6 = Forced closing
7 = Injection problem
8 = Emergency cooling (sensor error)
9 = Modulating thermostat regulation
10 = Melt function active
11 = Door open
12 = Appliance cleaning
13 = Cutout thermostat
14 = Forced cooling
Reg. condition B Regulation condition for section B
Same as for Reg. condition A
Reg. condition C Regulation condition for section C
Same as for Reg. condition A
Reg. condition D Regulation condition for section D
Same as for Reg. condition A
MC Defrost relays This readout is used for coordination of defrost via data communication
Settings Main switch Main switch: ON: Regulation
OFF: Controller stopped
MC Night signal This setting is used for control of day/night function via data communication
MC Light signal This setting is used for control of light via data communication
MC Forced Close This setting is used for forced closing of injection valve via data communication
MC Defrost start This setting is used for start of defrost via data communication
MC Defrost hold This setting is used for coordination of defrost via data communication
RC-ET
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products
already on order provided that such alternations can be made without subsequential changes being necessary in specifications already agreed.
All trademarks in this material are property of the respecitve companies. Danfoss and Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12

Danfoss Controller for evaporator control AK2-CC 303A Menu operation via AKM User guide

Type
User guide

Danfoss Controller for evaporator control AK2-CC 303A Menu operation via AKM is a versatile device that can be used for a variety of applications. With its ability to monitor and control multiple parameters, this device can help you to optimize the performance of your refrigeration and air conditioning systems.

Some of the key features of the Danfoss Controller for evaporator control AK2-CC 303A Menu operation via AKM include:

  • Monitoring of up to eight measurements
  • Control of various settings, including ON/OFF settings, variable value settings, time settings, and reset alarms
  • Documentation of settings for individual controllers