8
6. Operation
After the unit is mounted to the control panel and wiring is completed, operate the unit following the procedure below.
(1) Turn the power supply to the ACS-13A-
/A ON.
(2) Set up the unit. (Refer to “5. Operation Flowchart”.) Setup (setting the Temperature range, Alarm type,
Direct/Reverse action, etc.) should be done in Setup mode before using this controller. If the user’s specifications are
the same as the factory default of the instrument, it is not necessary to set up the controller. Proceed to Step (3).
(3) Input each set value. Input each set value. Refer to “5. Operation Flowchart” and “7. Basic Settings”.
(4) Turn the load circuit power ON. Control action starts so as to keep the control target at the SV.
7. Basic Settings
Main Setting Mode (When setting SV to 100.0 ) Auto-tuning Perform/Cancel (PID control)
Proceed to Main setting mode.
Press the key in PV/SV
Display Mode. The unit proceeds
to Main setting mode.
Proceed to Sub setting mode.
Press the , keys (in that order)
together in PV/SV Display Mode.
The unit proceeds to Sub setting mode.
Set SV with the or key.
Select AT Perform/Cancel.
Select AT Perform with the key, or
select AT Cancel with the key.
Register the SV by pressing the
key. The unit reverts to PV/SV
Confirm AT Perform/Cancel.
Press the key. The unit reverts to
PV/SV Display Mode.
Control starts so as to keep the
measuring temperature at 100.0
.
While AT is performing, the AT indicator
flashes, and it turns off if AT is cancelled.
8. Specifications
Power supply voltage: 100 to 240 V AC 50/60 Hz, 24 V AC/DC 50/60 Hz
Allowable voltage fluctuation: 100 to 240 V AC: 85 to 264 V AC, 24 V AC/DC: 20 to 28 V AC/DC
Accuracy (Setting, Indication): Within
0.2% of temperature span 1 digit
Control output (OUT1):
Relay contact 1a, Control capacity: 3 A 250 V AC (resistive load)
1 A 250 V AC (inductive load cos
=0.4), Electrical life: 100,000 cycles
Non-contact voltage (for SSR drive): 12 V DC
15%, Max. 40 mA DC (short circuit protected)
Direct current: 4 to 20 mA DC, Load resistance: Max. 550
Alarm 1, Alarm 2 (A2 option), Heater burnout alarm output (W, W3 option):
Relay contact 1a, Control capacity: 3 A 250 V AC (resistive load), Electrical life: 100,000 cycles
Control output (OUT2) (D
option):
Relay contact 1a, Control capacity: 3 A 250 V AC (resistive load), Electrical life: 100,000 cycles
Non-contact voltage (for SSR drive): 12 V DC
15%, Max. 40 mA DC (short circuit protected)
Contact input: Circuit current when closed: Approx. 12 mA
Power consumption: Approx. 8 VA
Ambient temperature: 0 to 50
(32 to 122 ) (No icing)
Ambient humidity: 35 to 85 %RH (Non-condensing)
Weight: Approx. 120 g
Accessories included: Instruction manual: 1 copy, Mounting frame: 1 piece
Gasket A (Front mounted to the ACS-13A-
/A): 1 piece
CT (Current transformer):
CTL-6S: 1 piece [W (20A) option], 2 pieces [W3 (20A) option]
CTL-12-S36-10L1U : 1 piece [W (50A) option], 2 pieces [W3 (50A) option]
Accessories sold separately: Terminal cover
SHINKO TECHNOS CO., LTD.
OVERSEAS DIVISION
Head Office:
URL
:
E-mail:
2-5-1, Senbahigashi, Minoo
, Osaka, Japan
http://www.shinko-technos.co.jp/e/
overseas@shinko-technos.co.jp
Tel :
Fax:
+81-72-727-6100
+81-72-
727-7006
• In order to decide each P, I, D and ARW values automatically,
the auto-tuning process has been made to fluctuate to get an
optimal value.
• Sometimes the auto-tuning process will not fluctuate if auto-tuning is
performed at or near room temperature. Therefore, auto-tuning
might not finish normally.
• Auto-reset is available for P or PD action. Auto-reset is cancelled
in approx. 4 minutes. It cannot be released while performing this