Legrand LMPS-6000 Skylight Photocell Installation guide

  • Hello! I am an AI chatbot trained to assist you with the Legrand LMPS-6000 Skylight Photocell Installation guide. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
Installation Instructions
LMPS-6000
Skylight Photocell
for Digital Lighting Management (DLM)
LMRJ Cables
Occupancy Sensor
Switch
LMPS-6000
Skylight
Photocell
DLM Local Network
Example 1
LMIO-301
Line Voltage
J-Box
0-10 Volt
Ballast
0-10 Volt
Ballast
LMRC-3xx
Room Controller
w/ Network
Bridge
LM-MSTP Wire
LM-MSTP
Wire
Segment Manager
or BACnet BAS
LMRJ Cables
Occupancy Sensor
Switch
LMPS-6000
Skylight
Photocell
Example 2
LMIO-301
Loads
1
2
Line Voltage
LMRC-102
Room
Controller
J-Box
LMBC-300
Network Bridge
Segment Manager
or BACnet BAS
SPECIFICATIONS:
Footcandle range LMPS-6000 . . . . . . . . . . .24 - 6000 fc
Calibration . . . . . .None, controlled by system software
Input voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24VDC
Sensor output . . . . . . . . . . . . . . . . . . . . . . . . . . 1-10VDC
Peak current . . . . . . . . . . . . . . . . . . . .4.5 mA Maximum
Slew rate . . . . .1 minute full scale response time filter
Operating temperature -40˚F to 140˚F (-40˚C to 60˚C)
Wire color code
Red . . . . . . . . . . . . . . . . . . . . Input Voltage +24 VDC
Black . . . . . . . . . . . Input Return/Output Common
Yellow . . . . . . . . . . . . . . . . . 1-10VDC Output Signal
Housing
UV stabilized plastic with dome lens
Mounting . . . . . . . . . . . . . . . . . . . . . ½" NPT x .69" stem
Overall dimensions . . . . . . . . . . . . .2.55"L x 1.28"D
WIRING
Connect the sensor to the LMIO-301 as shown.
#20 AWG up to 250 feet
#18 AWG up to 1000 feet
Class 2 wiring
Common (Black)
LMIO-301
4
57
8
9
1610
2
3
+24VDC Input Voltage (Red)
1-10VDC Output Signal (Yellow)
LMIO-301 Terminals
LMPS-6000
Skylight Photocell
Skylight
Well
Vertical
Orientation
Option
Please
Recycle
2800 De La Cruz Blvd.
Santa Clara, CA 95050
Phone: 800.879.8585
www.wattstopper.com
DESCRIPTION
The LMPS-6000 is a daylight sensor specifically
designed to be used in conjunction with a LMIO-301
DLM Photocell Input Module. The LMIO-301 converts
the 10 VDC signal from the photocell sensor to a digital
signal that is shared across the DLM Local Network.
The signal is forwarded as a BACnet object via a DLM
network bridge to the segment network for load control
via a DLM segment manager or BACnet compatible
Building Automation System (BAS).
INSTALLATION
Install the sensor on the side wall of the skylight well
as shown in the Wiring diagram. The sensor housing is
equipped with a ½" NPT nipple and will thread into any
suitable box or fitting, or mount into a ½" knockout. This
sensor is also suitable for use in atrium or clerestory
applications where high sunlight levels are common.
MAINTENANCE
At least once every two months wipe the lens clean
with a non-scratching clean cloth. Check the housing
for damage and that no moisture has penetrated the
sensor, as this will likely render it inoperable.
6/2010
13822r1
/