Mircom LT-6612 RB-MAM-1000KIT Installation guide

  • Hello! I am an AI chatbot trained to assist you with the Mircom LT-6612 RB-MAM-1000KIT Installation guide. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
LT-6612 Rev. 0 January 2017 Page 1 of 2
U.S.A
4575 Witmer Industries
Niagara Falls, NY 14305
Tel: (888) 660-4655
Canada
25 Interchange Way
Vaughan, ON L4K 5W3
Tel: (888) 660-4655
www.mircomgroup.com
RB-MAM-1000KIT Installation Instructions
1 Power off the Unit and Disconnect AC and Batteries
2 Upgrade the Chip on the Main Board
1. See the upgrade chip instructions (LT-1081) included in this kit.
2 Remove the Old Display Plate and Install the New Display Plate
3 Connect the New Display
1. Connect the ribbon cable from the display to P3 on the main board.
Use these screws to
attach the display to
the chassis
Attach braided
ground wire here
Attach green
ground wire from
main board to this
screw
LT-6612 Rev. 0 January 2017 Page 2 of 2
2 Connect the ground wires
1. Connect the green ground wire from the main board to the upper left screw on the new display.
2. Connect the included ground braid to the hole on the top of the new display plate.
3. Connect the other end of the ground braid to the hole on the chassis.
1 814181818
Connect included
ground braid to
these holes with the
included screws
1/2