Model 702G/O Advanced gas/oil burners — Instruction manual
Carlin part number MN702GO Rev. 06/23/14 – 3 –
Where appliance instructions differ from this manual, follow the appliance instructions.
Burner applications
Followallinstructionsinthismanual,theprimarycontroldatasheetand
theappliancemanual.
Verifytheburneriscorrectfortheappliancebeingusedandforallap-
plicablecodes/standards.
Adjustthenozzleselection/ringrateifnecessaryduetopositiveoverre
pressureand/oraltitudesmorethan2,000feetabovesealevel.Seethe
NOTICEundertheRatingsinformationatright.Whereapplianceappli-
cationinformationisavailable,therecommendedringrateandburner
informationwillincludeappropriate adjustments for positive overre
pressureandrecommendationsforhighaltitudes.Followtheappliance
manualguidelineswhenavailable.
Damage or shortage claims
Theconsigneeoftheshipmentmustledamageorshortageclaims
immediatelyagainstthetransportationcompany.SeetheNOTICEon
page1forburnercartoninformation.
When calling or writing about the
burner:
PleaseprovideuswiththeULserialnumberandburnermodelnumber
toassistusinlocatinginformation.Thisinformationcanbehelpfulwhen
troubleshootingorobtainingreplacementparts.
Codes and standards
Certification
702G/OburnersareU.L.listedfortheU.S.,certiedtocomplywith:
• ANSI/UL296,forusewith#1or#2heatingoil(perstandardASTMD396).
• UL795,forusewithnaturalgasorpropane.
• Burnerlabelslistcompliance,whenrequired,withspeciallocal,state
orprovincialapprovals.
Installthisburnerinaccordancewithalllocalcodesand
authoritieshavingjurisdiction.Regulationsoftheseauthori-
tiestakeprecedenceoverthegeneralinstructionsprovided
inthismanual.
United States installations
Burner/applianceinstallationsintheUnitedStatesmustcomplywiththe
latesteditionsof:
• InstallationofDomesticGasConversionBurners,ANSIZ21.8.
• NationalFuelGasCode,ANSIZ223.1/NFPA54.
• StandardfortheInstallationofOil-BurningEquipment,NFPA31
• NationalElectricalCode,ANSI/NFPA70.
• Alladditionalapplicablenational,stateandlocalcodes.
Ratings
(With0.00”w.c.overrepressure,altitude2,000feetmax.;seeNOTICE
below)
Oil Input
................................................................Highre:6.0to11.2GPH
................................................................. Lowre:3.5to6.5GPH
Gas Input
............................................................ Highre:840to1,600MBH
...............................................................Lowre:490to940MBH
Fuels
......................................................................No.1orNo.2Fueloil
....................................................................Naturalgasorpropane
Fuel unit & oil valves:
................ Fuelunit,2-stage, 300 psig(withinternalblockingvalve)
..................................................................... (2)Oilsolenoidvalves
Gas train: (availableinstraightorangledconguration)
............................(2)Maingasvalves&RV-61orRV-81regulator
............................................ Butterygasvalveforinputregulation
................ 1"gastrainstandard;1¼",1½"or2"gastrainavailable
Electrical
Power............................................................. 120V/60Hz/1-Phase
Limitcircuitinput(RM7895CorRM7897C).............. 120vac/60hz
Controlcircuitload(120vac)............................................. 1.2 amps
Motor................................... 1/2 hp, 3450 rpm, 48-frame, “N” flaNge
.............................. 115 / 208-230 vac/60 hz/1-ph, 8.4 / 3.8-4.2 amps
Oilvalve/gasvalvepower.......................................... 120 vac/60 hz
Dampermotor(withendswitch).........................hoNeywell m436a
Ignition & primary control
.............................CarlinModel41000solidstateelectronicignitor
Ignitionvoltage............................................................. 14,000volts
Primarycontrol...............................................HoneywellRM7897C
Agencies
................................................................................. ULListed(US)
Reducenozzle/ring rate whenrequired— Maximum burner
capacityisreducedwhenoverrepressureispositiveandfor
altitudesabove2,000 feet. See below,and adjustringrate/
nozzleselectionifnecessary.
702G/O — Maximum firing rate for
positive overfire pressure and high altitude
Overfire pressure (Inches w.c.) Oil – GPH Gas – MBH
0.00 11.2 1,600
0.10 10.9 1,530
0.20 10.7 1,500
0.30 10.6 1,480
0.40 10.3 1,440
0.50 10.2 1,430
0.60 9.9 1,390
Altitudes:For altitudes more than 2,000 feet above sea level, reduce the above
capacities an additional 4% per 1,000 feet higher than 2,000 feet
above sea level.