Resol DeltaSol BX L Installation Operation And Care

Type
Installation Operation And Care
Thank you for buying this RESOL product.
Please read this manual carefully to get the best performance from this unit. Please keep this
manual carefully.
DeltaSol®
BX L
www.resol.com
Manual
en
Installation
Operation
Functions and options
Troubleshooting
Manual for the
specialised craftsman
*48006810*
48006810
2
Information about the product
Proper usage
The solar controller is designed for use in 2-store and
3-store solar thermal systems in compliance with the
technical data specified in this manual.
Improper use excludes all liability claims.
CE-Declaration of conformity
The product complies with the relevant di-
rectives and is therefore labelled with the
CE mark. The Declaration of Conformity is
available upon request, please contact RESOL.
Note
Strong electromagnetic fields can impair the
function of the controller.
ÎMake sure the controller as well as
the system are not exposed to strong
electromagnetic fields.
Disposal
Dispose of the packaging in an environmentally
sound manner.
Dispose of old appliances in an environmentally
sound manner. Upon request we will take back
your old appliances bought from us and guarantee
an environmentally sound disposal of the devices.
Subject to technical change. Errors excepted.
Safety advice
Please pay attention to the following safety advice
in order to avoid danger and damage to people and
property.
Target group
These instructions are exclusively addressed to au-
thorised skilled personnel.
Only qualified electricians should carry out electrical
works.
Description of symbols
WARNING! Warnings are indicated with a warn-
ing triangle!
ÎThey contain information
on how to avoid the danger
described.
Signal words describe the danger that may occur,
when it is not avoided.
WARNING means that injury, possibly life-threat-
ening injury, can occur.
ATTENTION means that damage to the appli-
ance can occur.
Note
Notes are indicated with an information
symbol.
ÎArrows indicate instruction steps that should be
carried out.
Contents
1 Overview .................................................... 3
2 Installation ................................................. 4
2.1 Mounting ....................................................................4
2.2 Electrical connection ...............................................4
2.3 Data communication / Bus ..................................... 5
2.4 SD memory card slot .............................................. 6
2.5 Overview of basic system layouts ........................6
2.6 System layouts ...........................................................7
3 Operation and function .......................... 35
3.1 Buttons .....................................................................35
3.2 Selecting menu points and adjusting values .....35
3.3 Menu structure .......................................................35
3.4 Shortcut .................................................................... 36
3.5 Indications and system monitoring display .......36
3.6 Further indications ................................................. 38
4 Status menu ............................................. 38
5 Initial commissioning .............................. 38
6 Functions and options ............................. 41
6.1 Status level ...............................................................41
6.2 Adjustment channels .............................................43
6.3 Overview of options and their para meters .....62
7 User code and short menu - Adjustment
values ........................................................ 64
8 Messages ................................................... 64
9 Troubleshooting ....................................... 65
9.1 Miscellaneous ..........................................................66
10 Accessories ............................................. 68
10.1 Sensors and measuring instruments ..................68
10.2 Interface adapters ...................................................69
10.3 Visualisation modules ............................................69
11 Index ......................................................... 70
© 20130813_48006810_DeltaSol_BX_L.monen.indd
en
3
1 Overview
Extra large graphic display
4 relay outputs
5 sensor inputs
Data logging onto SD card
Thermal disinfection
Time-controlled thermostat function
RESOL VBus®
Energy-saving switch-mode power supply
Included:
1 x DeltaSol® BX L
1 x accessory bag
3 x screw and wall plug
8 x strain relief and screws
1 x manual
Note
For more information about accessories,
see p. 55
Technical data
Housing: plastic, PC-ABS and PMMA
Protection type: IP 20 / EN 60529
Protection class: I
Ambient temp.: 0 ... 40 °C
Dimensions: 204 x 170 x 47 mm
Mounting: wall mounting, also suitable for mounting
into patch panels
Display: System-Monitoring-Display for system visu-
alisation, 16-segment display, 7-segment display, 9 sym-
bols, control lamp (directional pad) and background
illumination
Operation:
7 push buttons at the front of the housing
Functions: Controller for multi-store solar thermal
systems. Functions such as: T control, pump speed
control, heat quantity measurement, operating hours
counter for the solar pump, tube collector function,
thermostat function, store loading in layers, priority
logic, heat dump function, thermal disinfection func-
tion, function control according to BAFA guidelines.
Inputs: 5 inputs for Pt1000 temperature sensors,
1 V40 impulse input
Outputs: 3 semiconductor relays, 1 standard relay
Interfaces: RESOL VBus®, SD card slot
Power supply: 100 ... 240 V~, 50 ... 60 Hz
Switching capacity per relay:
1 (1) A 100 ... 240 V~ (semiconductor relay)
2 (1) A 100 ... 240 V~ (standard relay)
Total switching capacity: 4 A
Standby power consumption: < 1W
Mode of operation: type 1.Y
en
4
The unit must only be located in dry interior rooms.
The controller must additionally be supplied from a
double pole switch with contact gap of at least 3 mm.
Please pay attention to separate routing of sensor ca-
bles and mains cables.
In order to mount the device to the wall, carry out
the following steps:
ÎUnscrew the cross-head screw from the cover
and remove it along with the cover from the
housing
ÎMark the upper fastening point on the wall. Drill
and fasten the enclosed wall plug and screw leav-
ing the head protruding
ÎHang the housing from the upper fastening point
and mark the lower fastening points (centres
150 mm)
ÎInsert lower wall plugs
ÎFasten the housing to the wall with the lower fas-
tening screws and tighten
ÎCarry out the electrical wiring in accordance
with the terminal allocation, see chap. 2.2
ÎPut the cover on the housing
ÎAttach with the fastening screw
upper fastening point
lower fastening point
cover
screw
2 Installation
2.1 Mounting
WARNING! Electric shock!
Upon opening the housing, live parts
are exposed.
ÎAlways disconnect the con-
troller from power supply
before opening the housing!
ATTENTION! ESD damage!
Electrostatic discharge can lead to
damage to electronic components!
ÎTake care to discharge
properly before touching
the inside of the device! To
do so, touch a grounded
surface such as a radiator
or tap!
Note
Strong electromagnetic fields can impair the
function of the controller.
ÎMake sure the controller as well as the
system are not exposed to strong elec-
tromagnetic fields.
Note
The pump speed must be set to 100 % when
auxiliary relays or valves are connected.
2.2 Electrical connection
en
5
WARNING! Electric shock!
Upon opening the housing, live parts
are exposed.
ÎAlways disconnect the con-
troller from power supply
before opening the housing!
WARNING! Electric shock!
L' is a fused contact permanently car-
rying voltage.
ÎAlways disconnect the con-
troller from power supply
before opening the housing!
Note
The connection depends on the system lay-
out selected, see chap. „2.6 System layouts“
on page 7.
Note
For more details about initial commissioning,
see chap. 5, page 39.
Temp. Sensor
Pt1000
T4A
100 ... 240 V~
50-60 Hz
1 (1) A (100 ... 240) V~
2 (1) A (100 ... 240) V~
R1-R3
R4
L
R3
R2
R1
GND
S1
S2
S3
S4
S5
VBus
N
R4
V40
L'
DeltaSol® BX L
Made in Germany
IP 20
CU 72102083.01
VBus
GND
The controller is supplied with power via a mains
cable. The power supply of the device must be
100 ... 240 V~ (50 ... 60 Hz).
The controller is equipped with 4 relays in total to
which loads such as pumps, valves, etc. can be con-
nected:
The relays R1 ... R3 are semiconductor relays,
designed for pump speed control:
Conductor R1... R3
Neutral conductor N
Protective conductor
• Relay 4 is a standard relay
Conductor R4
Neutral conductor N
Protective conductor
Depending on the product version, mains cables and
sensor cables are already connected to the device. If
that is not the case, please proceed as follows:
Connect the temperature sensors (S1 to S5) to
the corresponding terminals with either polarity:
S1 = Sensor 1 (collector sensor)
S2 = Sensor 2 (e. g. store sensor base)
S3 = Sensor 3 (e. g. collector sensor collector 2)
S4 = Sensor 4 (e. g. store sensor store 2)
S5 = Sensor 5 (e. g. store sensor store 3)
A V40 flowmeter can be connected to the terminals
V40 and GND (either polarity).
The mains connection is at the terminals:
Neutral conductor N
Conductor L
Conductor L' (L' is not connected with the mains
cable. L' is a fused contact permanently carrying
voltage)
Protective conductor
Note
Connecting the device to the power supply
must always be the last step of the installa-
tion!
2.3 Data communication / Bus
The controller is equipped with the RESOL VBus® for
data transfer with and energy supply to external mod-
ules. The connection is carried out at the two termi-
nals marked “VBus” and “GND” (either polarity). One
or more RESOL VBus® modules, depending on their
current consumption and the current supply of the
controller, can be connected via this data bus, such as:
RESOL GA3 Large Display module / Smart Display
SD3
RESOL AM1 Alarm module
RESOL DL2 Datalogger
Furthermore, the controller can be connected to a
PC via the RESOL VBus®/USB or VBus®/LAN interface
adapter (not included with the DeltaSol® BX L).
With the RESOL ServiceCenter Software (RSC),
measured values can be read, processed and visualised.
Note
For more information about accessories, see
p. 68.
en
6
2.4 SD memory card slot
The controller is equipped with an SD card slot for
storing system data onto an SD card. The values
can be opened and visualised, e. g. in a spreadsheet
programme.
A standard SD card is not included with the
DeltaSol® BX L, but can also be purchased at
RESOL.
For more information about using an SD card, see
page 61, “SD card”.
Standard SD and SD-HC cards can be used.
2.5 Overview of basic system layouts
2-store system with valve logic, 1
pump, 3 sensors and 3-port valve
(page 7)
2-store solar system with valve
logic and heat exchange control
(page10)
2-store solar system with pump
logic (page 13)
2-store solar system with pump
logic and heat exchange control
(page 16)
3-store solar system with valve
logic and heat exchange control
(page 19)
3-store solar system with pump
logic and heat exchange control
(page 22)
Solar system with store loading
in layers and 2 stores (page 25)
Solar system with east-/west
collectors and 2 stores (valve
logic) (page 28)
3-store solar system with east-/
west collectors (page 31)
5 6
7 8 9
123
4
en
7
2.6 System layouts
The controller compares the temperature at sensor
S1 to the temperatures at sensors S2 and S4. If the
measured temperature differences are higher than
the adjusted switch-on temperature differences, the
pump (R1) will be activated and the corresponding
store will be loaded up to the adjusted maximum
temperature via the valve (R3). Store 1 is loaded with
priority.
System 1
2-store system with valve logic, 1 pump, 3 sensors and 3-port valve
Note: 3-port valve normally open - store 1 (S2)
Sensor/
terminal Designation Description
S1 TCOL Temperature collector
S2 TST1B Temperature store 1 base
S3 Optional sensor for measure-
ment purposes or options
S4 TST2B Temperature store 2 base
S5 Optional sensor for measure-
ment purposes or options
V40
Relay Description
R1 Solar pump
R2/R4 optional:
Thermal disinfection
Parallel relay
Heat dump
R3 3-port valve store 1/2
en
8
Adjustment channels
Channel Sub channel 1 Sub channel 2 Factory setting Change to Description Page
ARR 1 System 43
ROSA 0000 5 ROSA number 60
LOAD1 > Loading 1
DT1O 6 K Switch-on temperature difference 1 44
DT1F 4 K Switch-off temperature difference 1 44
DT1S 10 K Set temperature difference 1 44
RIS1 2 K Rise 1 44
S1MAX 60 °C Store maximum limitation 1 44
SMXS1 2 Sensor store max 1 44
LOAD2 > Loading 2
DT2O 6 K Switch-on temperature difference 2 44
DT2F 4 K Switch-off temperature difference 2 44
DT2S 10 K Set temperature difference 2 44
RIS2 2 K Rise 2 44
S2MAX 60 °C Store maximum limitation 2 44
SMXS2 4 Sensor store max 2 44
LST2 ON Loading store 2 45
COL > Collector
CEM 130 °C Collector emergency temperature 46
OCCO* OFF Collector cooling option 46
CMAX 110 °C Collector maximum temperature 46
OCMN OFF Collector minimum limitation option 46
CMIN 10 °C Minimum collector temperature 46
OTCO OFF Tube collector function option 46
TCST 07:00 Tube collector starting time 47
TCEN 19:00 Tube collector ending time 47
TCRU 30 s Tube collector runtime 47
TCIN 30 min Tube collector standstill interval 47
OCFR OFF Collector frost protection option 47
CFR O 4 °C Antifreeze temperature collector on 47
CFR F 5 °C Antifreeze temperature collector off 48
FRPST 1 Antifreeze store selection 48
LLOGI > Loading logic
LOGIC PRIO Priority logic 48
en
9
Adjustment channels
Channel Sub channel 1 Sub channel 2 Factory setting Change to Description Page
PRIO1 1 Priority logic store 1 48
OSTS OFF Store set option 50
TST1 45 °C Set store temperature store 1 50
TST2 45 °C Set store temperature store 2 50
tLB 2 min Loading break time 48
tRUN 15 min Circulation runtime 48
PSPEE OFF Pause speed option 51
PDELA OFF Pump delay option 51
COOL > Cooling functions
OSYC* OFF System cooling 51
OSTC OFF Store cooling 52
OHDP* OFF Heat dump 52
ODTFT > T function option 54
OTH > Thermostat function option 56
PUMP > Speed
PUMP1 OnOF Speed variant pump 1 45
PUMP2 OnOF Speed variant pump 2 45
PUMP3 OnOF Speed variant pump 3 45
MAN > Manual mode
MAN1 Auto Manual mode 1 56
MAN2 Auto Manual mode 2 56
MAN3 Auto Manual mode 3 56
MAN4 Auto Manual mode 4 56
BLPR > OFF Blocking protection 56
OTDIS > OFF Thermal disinfection option 57
OPARR > OFF Parallel relay option 58
OHQM > OFF Heat quantity measurement option 58
DATE> Enter date 60
LANG > dE Language 61
UNIT > °C Unit 60
OSDC > SD card option 61
CODE 0000 User code 64
RESET OFF Factory setting
* are blocked against each other
en
10
The controller compares the temperature at sensor
S1 to the temperatures at sensors S2 and S4. If the
measured temperature differences are higher than
the adjusted switch-on temperature differences, the
pump (R1) will be activated and the corresponding
store will be loaded up to the adjusted maximum
temperature via the valve (R3). Store 1 is loaded with
priority. Heat exchange from store 2 to store 1 (R2)
is possible with another temperature differential func-
tion (S3-heat sink / S5-heat source).
System 2
2-store solar system with valve logic and heat exchange control
Note: 3-port valve normally open - store 1 (S2)
Sensor/
terminal Designation Description
S1 TCOL Temperature collector
S2 TST1B Temperature store 1 base
S3 TST1T Temperature store 1 top
S4 TST2B Temperature store 2 base
S5 TST2T Temperature store 2 top
V40 optional: flowmeter
Relay Description
R1 Solar pump
R2 Heat exchange pump
R3 3-port valve store 1/2
R4 optional:
Thermal disinfection
Parallel relay
Heat dump
en
11
Adjustment channels
Channel Sub channel 1 Sub channel 2 Factory setting Change to Description Page
ARR 1 2 System 43
ROSA 0000 16 ROSA number 60
LOAD1 > Loading 1
DT1O 6 K Switch-on temperature difference 1 44
DT1F 4 K Switch-off temperature difference 1 44
DT1S 10 K Set temperature difference 1 44
RIS1 2 K Rise 1 44
S1MAX 60 °C Store maximum limitation 1 44
SMXS1 2 Sensor store max 1 44
LOAD2 > Loading 2
DT2O 6 K Switch-on temperature difference 2 44
DT2F 4 K Switch-off temperature difference 2 44
DT2S 10 K Set temperature difference 2 44
RIS2 2 K Rise 2 44
S2MAX 60 °C Store maximum limitation 2 44
SMXS2 4 Sensor store max 2 44
LST2 ON Loading store 2 45
COL > Collector
CEM 130 °C Collector emergency temperature 46
OCCO* OFF Collector cooling option 46
CMAX 110 °C Collector maximum temperature 46
OCMN OFF Collector minimum limitation option 46
CMIN 10 °C Minimum collector temperature 46
OTCO OFF Tube collector function option 46
TCST 07:00 Tube collector starting time 47
TCEN 19:00 Tube collector ending time 47
TCRU 30 s Tube collector runtime 47
TCIN 30 min Tube collector standstill interval 47
OCFR OFF Collector frost protection option 47
CFR O 4 °C Antifreeze temperature collector on 47
CFR F 5 °C Antifreeze temperature collector off 48
FRPST 1 Antifreeze store selection 48
LLOGI > Loading logic
LOGIC PRIO Priority logic 48
PRIO1 1 Priority logic store 1 48
OSTS OFF Store set option 50
TST1 45 °C Set store temperature store 1 50
TST2 45 °C Set store temperature store 2 50
en
12
Adjustment channels
Channel Sub channel 1 Sub channel 2 Factory setting Change to Description Page
tLB 2 min Loading break time 48
tRUN 15 min Circulation runtime 48
PSPEE OFF Pause speed option 51
PDELA OFF Pump delay option 51
COOL > Cooling functions
OSYC* OFF System cooling 51
OSTC OFF Store cooling 52
OHDP* OFF Heat dump 52
DT4 > Heat exchange
DT4O 6 K Switch-on difference 52
DT4F 4 K Switch-off difference 52
DT4S 10 K Set difference 53
RIS4 2 K Rise 53
MAX4O 60 °C Switch-on temperature (maximum limitation) 53
MAX4F 58 °C Switch-off temperature (maximum limitation) 53
MIN4O 5 °C Switch-on temperature (minimum limitation) 53
MIN4F 10 °C Switch-off temperature (minimum limitation) 53
OTH > Thermostat function option 56
PUMP > Speed
PUMP1 OnOF Speed variant pump 1 45
PUMP2 OnOF Speed variant pump 2 45
PUMP3 OnOF Speed variant pump 3 45
MAN > Manual mode
MAN1 Auto Manual mode 1 56
MAN2 Auto Manual mode 2 56
MAN3 Auto Manual mode 3 56
MAN4 Auto Manual mode 4 56
BLPR > OFF Blocking protection 56
OTDIS > OFF Thermal disinfection option 57
OPARR > OFF Parallel relay option 58
OHQM > OFF Heat quantity measurement option 58
DATE> Enter date 60
LANG > dE Language 61
UNIT > °C Unit 60
OSDC > SD card option 61
CODE 0000 User code 64
RESET OFF Factory setting
* are blocked against each other
en
13
The controller compares the temperature at sensor
S1 to the temperatures at sensors S2 and S4. If the
measured temperature differences are higher than
the adjusted switch-on temperature differences, the
pump (R1 and/or R2) will be activated and the cor-
responding store will be loaded up to the adjusted
maximum temperature at most.
System 3
2-store solar system with pump logic
Sensor/
terminal Designation Description
S1 TCOL Temperature collector
S2 TST1B Temperature store 1 base
S3 Optional sensor for measure-
ment purposes or options
S4 TST2B Temperature store 2 base
S5 Optional sensor for measure-
ment purposes or options
V40
Relay Description
R1 Solar pump store 1
R2 Solar pump store 2
R3 optional:
Thermal disinfection
Parallel relay
Heat dump
R4
en
14
Adjustment channels
Channel Sub channel 1 Sub channel 2 Factory setting Change to Description Page
ARR 1 3 System 43
ROSA 0000 6 ROSA number 60
LOAD1 > Loading 1
DT1O 6 K Switch-on temperature difference 1 44
DT1F 4 K Switch-off temperature difference 1 44
DT1S 10 K Set temperature difference 1 44
RIS1 2 K Rise 1 44
S1MAX 60 °C Store maximum limitation 1 44
SMXS1 2 Sensor store max 1 44
LOAD2 > Loading 2
DT2O 6 K Switch-on temperature difference 2 44
DT2F 4 K Switch-off temperature difference 2 44
DT2S 10 K Set temperature difference 2 44
RIS2 2 K Rise 2 44
S2MAX 60 °C Store maximum limitation 2 44
SMXS2 4 Sensor store max 2 44
LST2 ON Loading store 2 45
COL > Collector
CEM 130 °C Collector emergency temperature 46
OCCO* OFF Collector cooling option 46
CMAX 110 °C Collector maximum temperature 46
OCMN OFF Collector minimum limitation option 46
CMIN 10 °C Minimum collector temperature 46
OTCO OFF Tube collector function option 46
TCST 07:00 Tube collector starting time 47
TCEN 19:00 Tube collector ending time 47
TCRU 30 s Tube collector runtime 47
TCIN 30 min Tube collector standstill interval 47
OCFR OFF Collector frost protection option 47
CFR O 4 °C Antifreeze temperature collector on 47
CFR F 5 °C Antifreeze temperature collector off 48
FRPST 1 Antifreeze store selection 48
LLOGI > Loading logic
LOGIC PRIO Priority logic 48
PRIO1 1 Priority logic store 1 48
en
15
Adjustment channels
Channel Sub channel 1 Sub channel 2 Factory setting Change to Description Page
OSTS OFF Store set option 50
TST1 45 °C Set store temperature store 1 50
TST2 45 °C Set store temperature store 2 50
OSE OFF Spread function option 50
DTSE 20 K Spread difference 50
SLSTR 3 Store spread function 50
tLB 2 min Loading break time 48
tRUN 15 min Circulation runtime 48
PSPEE OFF Pause speed option 51
PDELA OFF Pump delay option 51
COOL > Cooling functions
OSYC* OFF System cooling 51
OSTC OFF Store cooling 52
OHDP* OFF Heat dump 52
ODTFT > T function option 54
OTH > Thermostat function option 56
PUMP > Speed
PUMP1 OnOF Speed variant pump 1 45
PUMP2 OnOF Speed variant pump 2 45
PUMP3 OnOF Speed variant pump 3 45
MAN > Manual mode
MAN1 Auto Manual mode 1 56
MAN2 Auto Manual mode 2 56
MAN3 Auto Manual mode 3 56
MAN4 Auto Manual mode 4 56
BLPR > OFF Blocking protection 56
OTDIS > OFF Thermal disinfection option 57
OPARR > OFF Parallel relay option 58
OHQM > OFF Heat quantity measurement option 58
DATE> Enter date 60
LANG > dE Language 61
UNIT > °C Unit 60
OSDC > SD card option 61
CODE 0000 User code 64
RESET OFF Factory setting
* are blocked against each other
en
16
The controller compares the temperature at sensor
S1 to the temperatures at sensors S2 and S4. If the
measured temperature differences are higher than the
adjusted switch-on temperature differences, the pump
5
(R1 and/or R2) will be activated and the correspond-
ing store will be loaded up to the adjusted maximum
temperature. Store 1 is loaded with priority.
Sensor/
terminal Designation Description
S1 TCOL Temperature collector
S2 TST1B Temperature store 1 base
S3 TST1T Temperature store 1 top
S4 TST2B Temperature store 2 base
S5 TST2T Temperature store 2 top
V40 optional: flowmeter
Relay Description
R1 Solar pump store 1
R2 Solar pump store 2
R3 Heat exchange pump
R4 optional:
Thermal disinfection
Parallel relay
Heat dump
System 4
2-store solar system with pump logic and heat exchange control
Heat exchange from store 2 to store 1 (R3) is pos-
sible with another temperature differential function
(S3 - heat sink / S5 - heat source).
en
17
Adjustment channels
Channel Sub channel 1 Sub channel 2 Factory setting Change to Description Page
ARR 1 4 System 43
ROSA 0000 17 ROSA number 60
LOAD1 > Loading 1
DT1O 6 K Switch-on temperature difference 1 44
DT1F 4 K Switch-off temperature difference 1 44
DT1S 10 K Set temperature difference 1 44
RIS1 2 K Rise 1 44
S1MAX 60 °C Store maximum limitation 1 44
SMXS1 2 Sensor store max 1 44
LOAD2 > Loading 2
DT2O 6 K Switch-on temperature difference 2 44
DT2F 4 K Switch-off temperature difference 2 44
DT2S 10 K Set temperature difference 2 44
RIS2 2 K Rise 2 44
S2MAX 60 °C Store maximum limitation 2 44
SMXS2 4 Sensor store max 2 44
LST2 ON Loading store 2 45
COL > Collector
CEM 130 °C Collector emergency temperature 46
OCCO* OFF Collector cooling option 46
CMAX 110 °C Collector maximum temperature 46
OCMN OFF Collector minimum limitation option 46
CMIN 10 °C Minimum collector temperature 46
OTCO OFF Tube collector function option 46
TCST 07:00 Tube collector starting time 47
TCEN 19:00 Tube collector ending time 47
TCRU 30 s Tube collector runtime 47
TCIN 30 min Tube collector standstill interval 47
OCFR OFF Collector frost protection option 47
CFR O 4 °C Antifreeze temperature collector on 47
CFR F 5 °C Antifreeze temperature collector off 48
FRPST 1 Antifreeze store selection 48
LLOGI > Loading logic
LOGIC PRIO Priority logic 48
PRIO1 1 Priority logic store 1 48
OSTS OFF Store set option 50
TST1 45 °C Set store temperature store 1 50
TST2 45 °C Set store temperature store 2 50
OSE OFF Spread function option 50
en
18
Adjustment channels
Channel Sub channel 1 Sub channel 2 Factory setting Change to Description Page
DTSE 20 K Spread difference 50
SLSTR 3 Spread function option 50
tLB 2 min Loading break time 48
tRUN 15 min Circulation runtime 48
PSPEE OFF Pause speed option 51
COOL > Cooling functions
OSYC* OFF System cooling 51
OSTC OFF Store cooling 52
OHDP* OFF Heat dump 52
DT4 > Heat exchange
DT4O 6 K Switch-on difference 52
DT4F 4 K Switch-off difference 52
DT4S 10 K Set difference 53
RIS4 2 K Rise 53
MAX4O 60 °C Switch-on temperature (maximum limitation) 53
MAX4F 58 °C Switch-off temperature (maximum limitation) 53
MIN4O 5 °C Switch-on temperature (minimum limitation) 53
MIN4F 10 °C Switch-off temperature (minimum limitation) 53
OTH Thermostat function option 56
PUMP > Speed
PUMP1 OnOF Speed variant pump 1 45
PUMP2 OnOF Speed variant pump 2 45
PUMP3 OnOF Speed variant pump 3 45
MAN > Manual mode
MAN1 Auto Manual mode 1 56
MAN2 Auto Manual mode 2 56
MAN3 Auto Manual mode 3 56
MAN4 Auto Manual mode 4 56
BLPR > OFF Blocking protection 56
OTDIS > OFF Thermal disinfection option 57
OPARR > OFF Parallel relay option 58
OHQM > OFF Heat quantity measurement option 58
DATE> Enter date 60
LANG > dE Language 61
UNIT > °C Unit 60
OSDC > SD card option 61
CODE 0000 User code 64
RESET OFF Factory setting
* are blocked against each other
en
19
The controller compares the temperature at sen-
sor S1 to the temperatures at sensors S2, S4 and S5.
If the measured temperature differences are higher
than the adjusted switch-on temperature differences,
the pump (R1) will be activated and the correspond-
ing store will be loaded up to the adjusted maximum
temperature via the valves (R3, R4). In this system, the
desired store sequence can be adjusted. Depending
on the valve type used, the corresponding valve logic
has to be selected.
System 5
3-store solar system with valve logic and priority logic
Ventillogik 1
2
3
4
Durchflussrichtung
im stromlosen Zustand
Sensor/
terminal Designation Description
S1 TCOL Temperature collector
S2 TST1B Temperature store 1 base
S3 Optional sensor for measure-
ment purposes or options
S4 TST2B Temperature store 2 base
S5 TST3B Temperature store 3 base
V40 Optional sensor for measure-
ment purposes or options
Relay Description
R1 Solar pump store 1
R2
R3 Valve store 1/2, 3
R4 Valve store 2/3
Ventillogik
1
2
3
4
Durchflussrichtung
im stromlosen Zustand
Ventillogik 1
2
3
4
Durchflussrichtung
im stromlosen Zustand
Valve logic
Flow direction when the
valve is normally open
en
20
Adjustment channels
Channel Sub channel 1 Sub channel 2 Factory setting Change to Description Page
ARR 1 5 System 43
ROSA 0000 225 ROSA number 60
VLOG 1 Valve logic 60
LOAD1 > Loading 1
DT1O 6 K Switch-on temperature difference 1 44
DT1F 4 K Switch-off temperature difference 1 44
DT1S 10 K Set temperature difference 1 44
RIS1 2 K Rise 1 44
S1MAX 60 °C Store maximum limitation 1 44
SMXS1 2 Sensor store max 1 44
LOAD2 > Loading 2
DT2O 6 K Switch-on temperature difference 2 44
DT2F 4 K Switch-off temperature difference 2 44
DT2S 10 K Set temperature difference 2 44
RIS2 2 K Rise 2 44
S2MAX 60 °C Sensor store max 2 44
LST2 ON Loading store 2 45
LOAD3 Loading 3
DT3O 6 K Switch-on temperature difference 3 44
DT3F 4 K Switch-off temperature difference 3 44
DT3S 10 K Set temperature difference 3 44
RIS3 2 K Rise 3 44
S3MAX 60 °C Sensor store max 3 44
LST3 ON Loading store 3 45
COL > Collector
CEM 130 °C Collector emergency temperature 46
OCCO* OFF Collector cooling option 46
CMAX 110 °C Collector maximum temperature 46
OCMN OFF Collector minimum limitation option 46
CMIN 10 °C Minimum collector temperature 46
OTCO OFF Tube collector function option 46
TCST 07:00 Tube collector starting time 47
TCEN 19:00 Tube collector ending time 47
TCRU 30 s Tube collector runtime 47
TCIN 30 min Tube collector standstill interval 47
OCFR OFF Collector frost protection option 47
CFR O 4 °C Antifreeze temperature collector on 47
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72