  • Hello! I am an AI chatbot trained to assist you with the Resol DeltaSol AX Mounting, Connection, Operation. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
DeltaSol
® AX
www.resol.de
Thank you for buying a RESOL product.
Please read this manual carefully in order to put this controller to the best possible use.
RESOL DeltaSol
® AX
Mounting
Connection
Operation
Application examples
manual
*48000250*
48000250
DeltaSol
® AX
© RESOL 06255 deltasol_ax.monen.indd
| 2
Contents
Imprint ................................................................................2
Security devices ..................................................................2
Technical data and function survey ..................................3
1. Installation ...................................................................4
1.1 Mounting ......................................................................................... 4
1.2 Electrical connection .................................................................... 4
2. Functions and Settings ...............................................5
2.1 Micro-switch and potentiometer .............................................. 5
2.2 Switch-on temperature difference ............................................ 5
Scope of delivery:
• controllerDeltaSol
® AX
(full kit incl. 2 temperature sensors)
• sparefuseundercover
• accessorybagconsistingofsiliconesealing,fastening
screwsanddowels,strainreliefclampandscrews
• manual
2.3 Manual operation .......................................................................... 5
2.4 Maximum temperature limitation ............................................. 6
2.5 Anti-Freeze protection ................................................................ 6
2.6 Minimum temperature limitation .............................................. 6
2.7 Blinking codes ................................................................................ 6
3. Tips for fault diagnostics ............................................ 7
4. Applications of use ..................................................... 7
5. Annex: Fault diagnostics .......................................... 10
Security advice
Pleasepayattentiontothefollowingsecurityadviceinorder
toavoiddangeranddamagetopeopleandproperty.
Instructions
Attentionshouldbepaid
-tothestatutoryprovisionsforpreventionofindustrial
accidents,
-tothestatutoryprovisionsforenvironmentalprotection,
-totheHealthandSafetyatWorkAct1974
- to Part P of the Building Regulations 2005
- to BS7671 Requirements for electrical installations and
relevantsafetyregulationsofDIN,EN,DVGW,TRGI,TRF
andVDE.
Thisinstructionisexclusivelyaddressedtoauthorised
skilled personnel.
-Onlyqualifiedelectriciansshouldcarryoutelectrical
works.
-Initialinstallationshouldbeeffectedbynamedqualied
personnel
Declaration of conformity
We, RESOL Elektronische Regelungen GmbH, D-45527
Hattingen, declare under our sole responsibility that our
product DeltaSol
® AX complies with the following stan-
dards:
EN55014-1
EN60730-1
Accordingto theregulations ofthe abovedirectives, the
productislabelledwith :
89/336/EWG
73/23/EWG
Hattingen,07.07.2006
RESOLElektronischeRegelungenGmbH,
ppa.GeraldNeuse
DeltaSol
® AX
© RESOL 06255 deltasol_ax.monen.indd
3 |
Electrostatical discharges can lead to damages of
electronic components!
Dangerousvoltageoncontact!
DeltaSol
® AX
Thanks to its tough and deliberately simple design concept this low priced
differentialcontrollercanbewidelyusedinsolar,heatingandairconditioning
systems.Thelargecontrolrangeandadjustabletemperaturedifferencesensure
thatthisunitcanbeusedinalmostallapplicationswhereswitchingprocesses
arecontrolledbytemperaturedifference.
The outer cover is available with an optional seal to protect the electronics
against dripping water.
The controller checks a temperature diffference T measured by two tem-
perature sensors by comparing this difference with a preadjusted switch-on
difference(adjustablewithintherangeof2...16K).Thecontrolofthesystemis
effectedbyastandardrelay(=changeovercontact),towhichseveralmotorsor
electricalvalvescanbeconnected.Thecontrollerswitches-ON,iftheadjusted
temperaturedifferenceisexceeded;ifthisdifferenceisunderrunby1,6K,the
controller switches-OFF.
130
45
Technical data
Housing:
plug-in plastic PC-ABS
Protection type: IP20/DIN40050
Ambient temp.: 0 ... 40 °C
Size: Ø130mm,45mmheight
Mounting: wall mounting
Display: 1 function control lamp
Inputs: 2sensorinputsPT1000
Outputs: 1standardrelay(changeover
contact)
Switch-on difference:
T2...16Kadjustable
Switch-off difference:
1,6Kbelowswitch-ondifference
Control range: -20 ... +150 °C
Power consumption: max. 4 A
Powersupply:220...240V~
Order indications
RESOL DeltaSol AX 115 211 70
RESOL DeltaSol A X- full kit - 115 211 80
incl. 2 temperature sensors Pt1000 (1xFKP6,1xFRP6)
Accessory
Overvoltage protection
ItishighlyrecommendedtoconnecttheRESOLovervoltageprotectionSP1to
allcollectorsensorsinordertoavoidovervoltages(e.g.bylightning).
RESOL SP1 180 110 10
DeltaSol
® AX
© RESOL 06255 deltasol_ax.monen.indd
| 4
Theunitshouldbelocatedinternally.Itisnotsuitablefor
installationinhazardouslocationsandshouldnotbesited
neartoanyelectromagneticeld.Pleaseensuresensorcables
andacpowersupplyareseparated.
1. Choose a location, drill two holes of Ø6 mm side by
sidewithadistanceof113mmandtintheenclosed
dowels.
2. Fixthecontrollerbymeansoftheenclosedscrews(4x
40 mm)(pos. 1).
3.Theelectricalconnectionmustbeeffectednow.Power
supplyofthecontroller(210...250V)mustbeeffected
byexternalpowerswitch.
Connection of the sensors at the clamps:
1/2 = sensor1(e.g.collectorsensor)
3/4 = sensor2(e.g.storesensor)
Connection of the consumer to the clamps:
7 = normallyopencontactrelay(RO)
8 = breakcontactrelay(RC)
9 = neutralcontactrelay(N)
ground clamp (collective terminal strip)
ac power supply to the clamps:
10 = neutralconductorN
11 = conductorL
ground clamp (collective terminal strip)
Theguidesoftherequiredinsertionchannelsmustbebroken
awayatthebottomsideofthecover.
Thecablesaretobexedtothehousingbyenclosedstrain
relief supports and screws (pos.2).
If necessary, activate anti-freeze function by jumper. If
protection against dripping water is required insert the
siliconesealingringintothegrooveonthebaseplatetaking
care not to stretch it.
Putonthecoverandscrewit(pos.3).Ifnecessary,adjust
temperature difference T.
Putonhousingcoverandscrewit(pos.4).
1. Installation Warning!
Switch-off power supply before opening
the housing.
1
4
3
2
housingcover
cover
base
sensor 1
sensor 2
relay(consumer)
acpowersupply
ground clamp
(collectiveterminalstrip)
fuseT4A
1.2 Electrical connection
Insertsealingbandwithoutstrainintothenut
DeltaSol
® AX
© RESOL 06255 deltasol_ax.monen.indd
5 |
2.1 Micro-Switch and Potentiometer
2. Functions and Settings
Themicro-switch(A)activates(ON)deactivates(OFF)
following functions:
•Manualoperation(micro-switch1)
•Maximumtemperaturelimitation(micro-switch2)
•Anti-freezeprotection(micro-switch3)
•Minimumtemperaturelimitation(micro-switch4)
Potentiometer(B)adjuststhetemperatureforthemaxi-
mum or minimum temperature limitation in °C.
Potentiometer(C)adjuststheswitch-ontemperatureinK
2.3 Manual operation mode
ON
OFF
1234
1
ON
OFF
1234
ON
OFF
1234
B
C
2.2 Switch-on temperature difference
ON
OFF
1234
A
Thecontrollercheckstheexistingtemperaturedifference
betweentemperaturesensorS1andtemperaturesensor
S2withtheadjustedtemperaturedifferenceTatthe
potentiometer(C).Thecontrollerswitchesovertherelay
assoonasthetemperaturereachestheadjustednominal
value,theoperatingcontrollampashesgreen.Iftheset
valueisunderrunbyadifferenceof1,6K(hysteresis,cannot
bechanged)thecontrollerswitchestherelayback.
Thefactorysettingfortheswitch-ontemperaturedifference
ispreadjustedto6K.Adjustabletemperaturedifference
withinarangeof2...16K.
ON
OFF
1234
C
A
Duringcomissioningandmaintenancetherelaycanbe
switched-onpermanentlybymanualoperation.
Themanualoperationmodeisactivatedanddeactivated
bythemicro-switch.Whenthemanualoperationmodeis
activated,theoperatingcontrollampashesgreen.
Thefactorysettingforthemanualoperationmodeisdeac-
tivated(micro-switchinOFF-position),thecontrollerisin
automatic operation.
DeltaSol
® AX
© RESOL 06255 deltasol_ax.monen.indd
| 6
Micro-switch3activatesananti-freezeprotectionfunction.
Theanti-freezeprotectionfunctionreactsto thetempe-
rature of sensor S1(e.g. a collector sensor). As soon as
thissensormeasuresatemperaturebelow+4°C,warmer
waterispumpedfromthestoretothecollectortoprevent
damages to the collector; in the course of this the operating
control lamp ashes green.As soon as a temperature of
+5°Cisreached,thepumpswitches-offagain.
Please note:Asthereisonlyalimitedheatquantityof
thestoreavailableforthisfunction,theanti-freezefunction
shouldonlybeusedinregionswithfewdaysoftemperatures
around freezing point.
Thefactorysettingfortheanti-freezefunctionisdeactivated.
(micro-switch in OFF-position).
2.5 Anti-freeze protection
3
ON
OFF
1234
2.6 Minimum temperature limitation
4
Micro-switch4activatesthetemperaturelimitationasami-
nimumtemperaturelimitation.Thetemperatureisadjusted
asalimitingvalueforthesensormountedontheterminals
S1atthepotentiometer„temperaturelimitation“.Therelay
won’tswitchuntiltheadjustedtemperatureisreached.This
functionshouldpreferablybeusedincombinationwitha
solidfuelboilerinordertoavoiduegascondensation
withintheboiler.Bymaintainingaminimumtemperature
limitationintheheatgeneratorauegascondensationon
the boilerwalls isavoided.Iftheminimumtemperatureis
underrun,theoperatingcontrollampashesred.
Thefactorysettingfortheminimumtemperaturelimitation
isdeactivated(micro-switchinOFF-position).Whenactiva-
ted,atemperaturelimitationof60°Cispreadjusted.
ON
OFF
1234
ON
OFF
1234
A
A B
2.4 Maximum temperature limitation
2
Micro-switch2activatesthetemperaturelimitationasa
maximumtemperaturelimitation.Thetemperatureforthe
temperaturesensormountedonclampS2isadjustedasa
limitingvalueatthepotentiometer(B).Iftheadjustedma-
ximumtemperatureisexceeded,therelayisswitchedover
andsopreventse.g.afurtherstoragecharge(protection
againstoverheating).Ifthemaximumstoretemperatureis
exceeded,theoperatingcontrollampashesred.
Thefactorysettingforthemaximumtemperaturelimitation
isactivated(micro-switchinON-position),Thetemperature
limitationispreadjustedto60°C.Adjustabletemperature
differencewithinarangeof20...90°C.
ON
OFF
1234
ON
OFF
1234
BA
2.7 Blinking codes
TheLEDshowstheactualoperatingstatusofthecont-
roller.
Readyforuse red
Relayactive green
Manualmodeactive green(blinking)
Maximum temperature exceeded red(blinking)
Anti-freezeprotectionactive green(blinking)
Minimum temperature under-run red(blinking)
DeltaSol
® AX
© RESOL 06255 deltasol_ax.monen.indd
7 |
4. Application examples
Standard solar system with 1 store
IfthecurrenttemperaturedifferenceTbetweencollector
sensor S1 and store sensor S2 exceeds the temperature
differenceadjustedatthecontroller,thesolarpumpis
switched-on. Heat is transported from the collector to the
store; in the course of this the temperature difference is
reduced.Iftheadjustedtemperaturedifferenceisunderrun
byadifferenceof1,6K(hysteresis,cannotbechanged),the
pump is switched-off again.
Ifthecontrollerdoesnotworkperfectly,pleasecheckthe
following items:
Ifthecontrollerdoesnotswitchonwhenthereisapower
supply available please check the fuses.The controller is
protectedbyanefuseT4A,whichcanbereplacedafter
havingremovedthehousingandthecover.Asparefuseis
enclosedonthebacksideofthecover.
Pleasecheckthesensors.Sensorswhicharenotconnected,
musthavefollowingresistancevaluesdependingonthegiven
temperature.
3. Tips for fault diagnostics
ResistancevaluesofthePt1000-sensors
S1
RO
S2
ON
OFF
1234
C
ON
OFF
1234
A
ON
OFF
1234
B
S1=collectorsensor
S2=storesensor
RO=solarpump
bracketforsparefuse
(interiorpartofcover)
Usegroundclampcollectiveterminal
strip!
°C -10 -5 0 5 10 15 20 25 30
W961 980 1000 1019 1039 1058 1078 1097 1117
°C 35 40 45 50 55 60 65 70 75
W1136 1155 1175 1194 1213 1232 1252 1271 1290
°C 80 85 90 95 100 105 110 115
W1309 1328 1347 1366 1385 1404 1423 1442
DeltaSol
® AX
© RESOL 06255 deltasol_ax.monen.indd
| 8
1
S1 S2
2347
RO RC NNL
8910 11
S2
Heat exchange
(betweentwostores)
S1
R0
ON
OFF
1234
C
ON
OFF
1234
A
IfthetemperaturedifferenceTbetweenstore(1)-sensor
S1andstore(2)-sensorS2exceedsthetemperatureadjus-
tedatthecontroller,thecirculationpumpisswitched-on.
Heat is transported from the store (1) into store (2); in the
course of this the temperature difference is reduced.
Iftheadjustedtemperaturedifferenceisunderrunbyadif-
ferenceof1,6K(hysteresis,cannotbechanged),thepump
is switched-off again.
S1 = store(1)sensor
S2 = store(2)sensor
RO= circulationpump
IfthetemperaturedifferenceTbetweenstoresensorS1
and heating circuit return sensor S2 exceeds the tempera-
turedifferenceadjustedatthecontroller,the3-way-valveis
switched-over.Thereturntemperatureoftheheatingcircuit
israisedbytheheatofthestoresothatlessconventional
energyisnecessarytoreachtherequiredowtemperature;
in the course of this the temperature difference is reduced.
Iftheadjustedtemperaturedifferenceisunderrunbyadif-
ferenceof1,6K(hysteresis,cannotbechanged),thevalveis
switched to initial position.
S1 = storesensor
S2 = heatingcircuitreversesensor
RO= 3-way-valve
Heating circuit - raising the return temperature
1
S1 S2
2347
RO RC NNL
8910 11
S1
C
A
RO
S2
ON
OFF
1234
ON
OFF
1234
Usegroundclampcollectiveterminal
strip!
Usegroundclampcollectiveterminal
strip!
DeltaSol
® AX
© RESOL 06255 deltasol_ax.monen.indd
9 |
Thecontrollercomparesthetemperatureatthesensorof
thesolidfuelboilerorboilerinsertedinstove(S1)with
thetemperatureatthesensoratstore(S2).Ifthedetec-
ted temperature difference is higher than or equals the
preadjustedvalueT,thepump(RO)isswitched-onwhen
simultaneouslythegivenminimumtemperatureisreached
orexceeded.Thetemperaturedifferenceisreduced.
Store charge
1
S1 S2
2347
RO RC NNL
8910 11
S1
R0
S2
ON
OFF
1234
C
ON
OFF
1234
A
ON
OFF
1234
B
Ifthedifference1,6K(hysterisis,candifferenceisreduced,
cannotbechanged)underrunstheadjustedtemperature
difference,thepumpisswitched-offagain.
S1=boilersensor
S2=storesensor
RO=circulationpump
t
Usegroundclampcollectiveterminal
strip!
DeltaSol
® AX
© RESOL 06255 deltasol_ax.monen.indd
| 10
Pumpstartsforashortmoment,switches-off,switches-on
again,etc.(„controllerhunting“)
Isthetemperaturedif-
ference at the controller
too small?
no yes
Wrongpositionofthe
collector sensor?
yes
ChangeTon and Toff
accordingly.
Mount the collector sen-
soratsolarow
warmest collector out-
put);
Pumpstartsupverylateandsoonstopsworkingsoon. Thetemperaturedifferencebetweenstoreandcollector
increasesenormouslyduringoperation;thecollectorcir-
cuit cannot dissipate the heat.
Collector circuit pump
defect ?
no yes
Heat exchanger calci-
ed??
yes
Conrtol/replacement
Decalicatiom
no
Heatexchangerblocked?
yesno Cleaning
Heat exchanger too
small?
yes Newcalculationofthe
dimension.
ChangeTon and Toff
accordingly.
Switch-on-temperature
difference Ton too large
no yes
Collectorsensorunfavour-
ableplaced(e.g.contact
sensor instead of immersion
sleevesensor?
o.k.no
Pumpisoverheated,butnoheattransferfromcollector
tothestore,feedowandreturnowareequallywarm,
perhapsalsobubbleinthelines.
Ventsystem;increasesys-
tem pressure to at least
staticprimarypressure
plus0,5bar;ifnecessa-
rycontinuetoincrease,
switch the pump for a
short time off and on.
Airinthesystem?
no yes
Isthecollectorcircuit
blockedatthedirttrap?
yes
Clean the dirt trap
Ifnecessaryactivatetube
collector function.
yes
o.k.
5. Annex: Fault finding
DeltaSol
® AX
© RESOL 06255 deltasol_ax.monen.indd
11 |
Stores are cooled during the night.
Doescollectorcircuit
pump run during the
night?
no yes
Check the controller
functions
Collector temperature is
higher at night than am-
bienttemperature?
no yes Check operation of non
returnvalves.
Istroreinsulationsuf-
cient?
yes no
Intensifytheinsulation.
Isstoreinsulationclose
enough to the store?
yes no
Replaceorintesifythe
insulation.
Are the store connceti-
ons insulated?
yes no Insulateconnections.
Warmwateroutow
upwards?
no yes
Change connection and
let the water flow side-
wards or through a siphon
(bowdownwards);less
store losses now?
Thesolarcircuitpumpdoesnotworkalthoughthecoll-
ectorisobviouslywarmerthanthestore.
DoesthecontrolLED
ash?
yes no
Doesthepumpstartup
in manual operation?
yes
Thereisnocurrent;check
fuses/replacethemand
checkpowersupply.
Theadjustedtemperature
difference for starting the
pump is too high; choose
avaluewhichmakesmore
sense.
no
Isthecurrentofthe
pumpreleasedbythe
controller?
Free the pump using a
screwdriver;inoperation
now?
Isthe pumpdefective -
replace it.
Are the fuses of the
controller o.k.?
Controllerseemstobe
defective-replaceit.
no
no
no yes
Replace the fuses.
no yes
o.k.
Controlthereturnow
preventerinwarmwater
circulation- o.k.
no
Cleaning or replacement.
yes Isthepumpstuck?
yes
DeltaSol
® AX
© RESOL 06255 deltasol_ax.monen.indd
| 12
Distributed by:
Comments:
Thedesignandthespecicationscanbechangedwithoutadvancenotice.