Powersupplywiring
Tighteningtotorquefortheterminalscrews
Electricalcharacteristic
SpecicationsforeldsuppliedELBandwire
MainbusandR/Ccommunciationwiring
1.Unscrewandremovetheservicelid.
2.Connect the power supply wiring to the power supply
terminalblock.
3.Whendoingthis,pressthe powersupplywiring underthe
wirecliptightly.
1.Usethecorrectscrewdriverfortighteningtheterminalscrews.Ifthebladeofscrewdriveristoosmall,theheadofthescrewmightbedamaged,andthe
screwwillnotbeproperlytightened.
2.Iftheterminalscrewsaretightenedtoohard,screwsmightbedamage.
3.Refertothetablebelowforthetighteningtorqueoftheterminalscrews.
1.Unscrewandremovetheservicelid.
2.ConnecttheR/CwiringstoR1,R2terminalblockandthe
mainbuswiringstoF1,F2terminalblock.
3.Pressthewiringsunderthewirecliptightly.
Terminal Size Tighteningtorque
Remotecontroller,Transmissionwiringandforcedoffterminalblock(4P) M3.5 0.8~1.0N.m
PowersupplyandGroundterminalblock(3P) M4 1.2~1.5N.m
Unit Powersupply Fanmotor
Model Hz Volts MCA MFA KW FLA
LEV22
50 220~240
0.23 16 0.02 0.06
LEV28 0.23 16 0.02 0.06
LEV36 0.23 16 0.02 0.06
LEV45 0.23 16 0.02 0.07
LEV56 0.23 16 0.02 0.07
LEV63 0.23 16 0.02 0.07
MCA:Min.CircuitAmps(A)
MFA :Max.FuseAmps(A)
KW :FanMotorRatedoutput(KW)
FLA :FullLoadAmps(A)
Model Powersupplywiring
Remotecontrollerwiring
communicationwiring
PNV007 FieldELB WireandSize Wire Size
PNV009
16A
Mustcomply
withmaximum
currentandlocal
codes(≥0.75mm
2
)
Twisted-
pairwires
≥1.0mm
2
PNV012
PNV015
PNV018
PNV021
All fieldsupplied parts andmaterials and electrics worksmust
conformtolocalcodes.
Usecopperwireonly.
Allwiringmustbeperformedbyanauthorizedelectrician.
Everyindoorunitmusthavea subcircle breakerandthewhole
systemmusthaveamaincirclebreaker.
Besuretogroundtheairconditioner.
The appliance shall be installed in accordance with national
wiring regulations, and shall be provided to ensure all-pole
disconnectionfromthesupplymains,anddistancebetweenthe
polesshallbemorethan3mm.
CHECK ITEMS
BEFORE POWER ON
�
Isthereanygasleakageatarenutconnections?
�
Hastheheatinsulationbeencarriedoutatarenutconnection?
�
Istheconnectingcablebeingxedtoterminalboardrmly?Isthe
connectingcablebeingclampedrmly?
�
Isthedrainageok?
�
(Referto"Checkthedrainage"section)
�
Istheearthwireconnectionproperlydone?
�
Istheindoorunitproperlyhookedtotheinstallationplate?
�
Isthepowersupplyvoltagecompliedwithratedvalue?
AFTER POWER ON
�
Isthereanyabnormalsound?
�
Isthecoolingoperationnormal?
�
Isthethermostatoperationnormal?
�
Istheremotecontrol'sLCDoperationnormal?
NOTE:Forthepipingandwiringmethods,leakagetest,vacuumprocessandinstallationsetting
throughHMI,pleaserefterto“OutdoorunitInstallationManual”.
NOTE:Forhowtoconnectthepowerwireandcommunicationwirebetweenoutdoorunitandindoorunits,pleasereferto
chapter9“FieldWiring”inoutdoorunitinstallationmanual.