Airwell SXV 009 Installation guide

Category
Split-system air conditioners
Type
Installation guide
INSTALLATION MANUAL
MODELS
Floor/Ceiling unit
SXV 007 SXV 009
SXV 012 SXV 015
SXV 018 SXV 021
SXV 024
SAFETY PRECAUTIONS
Part NO:468050100/02
● Readthefollowing"SAFETYPRECAUTIONS"carefullybeforeinstallation.
● Carryouttestrunningtoconrmthatnoabnormalityoccursaftertheinstallation.Then,explaintousertheoperation,careandmaintenanceasstatedin
instructions.Pleaseremindthecustomertokeeptheoperatinginstructionsforfuturereference.
Thisindicationshowsthepossibilityofcausingdeathorseriousinjury.
WARNING
Thisindicationshowsthepossibilityofcausingharmordamagetheequipment.
CAUTION
WARNING
1)Usequaliedinstallerandfollowcarefullythisinstructions.Otherwiseitwillcauseelectricalshock,waterleakage,orestheticproblem.
2)Installatastrongandrmlocationwhichisabletowithstandtheset'sweight.Ifthestrengthisnotenoughorinstallationisnotproperlydone,theset
willdropandcauseinjury.
3)Forelectricalwork,followthelocalnationalwiringstandard,regulationandthisinstallationinstruction.Anindependentcircuitandsingleoutletmust
beused.Ifelectricalcircuitcapacityisnotenoughordefectfoundinelectricalwork,itwillcauseelectricalshockorre.
4)Usethespeciedcableandconnecttightlyforindoorconnection.Connecttightlyandclampthecablesothatnoexternalforcewillbeactedonthe
terminal.Ifconnectionorxingisnotperfect,itwillcauseheat-uporreattheconnection.
5)Wireroutingmustbeproperlyarrangedsothatcontrolboardcoverisxedproperly.Ifcontrolboardcoverisnotxedperfectly,itwillcauseheat-up
atconnectionpointofterminal,reorelectricalshock.
6)Whencarryingoutpipingconnection,takecarenottoletairsubstancesotherthanthespeciedrefrigerantgointorefrigerationcycle.Otherwise,it
willcauselowercapacity,abnormalhighpressureintherefrigerationcycle,explosionandinjury.
7)Donotdamageoruseunspeciedpowersupplycord.Otherwise,itwillcausereorelectricalshock.
8)Thisequipmentmustbeearthed.Itmaycauseelectricalshockifthegroundingisnotperfect.
9)Donotinstalltheunitatplacewhereleakageofammablegasmayoccur.Incasegasleaksandaccumulatesatsurroundingoftheunit,itmay
causere.
CAUTION
1)Selectionoftheinstallationlocation.
Selectainstallationlocationwhichisrigidandstrongenoughtosupportorholdtheunit,andselectalocationforeasymaintenance.
2)Donotreleaserefrigerant.
Donotreleaserefrigerantduringpipingworkforinstallation,reinstallationandduringrepairingarefrigerationparts.Takecareoftheliquidrefrigerant.
itmaycausefrostbite.
3)Itmayneedtwopeopletocarryouttheinstallationwork.
4)Donotinstallthisapplianceinalaundryroomorotherlocationwherewatermaydripfromtheceiling,etc.
5)Carryoutdrainagepipesasmentionedininstallationinstructions.Ifdrainageisnotperfect,watermayentertheroomanddamagethefurniture.
IM_SXV_1 A 1 _GB
1
SELECT THE BEST LOCATION
2
INSTALLATION Of uNIT SuppOrT
Requiredtoolsforinstallationworks
Attachedaccessories
No. Accessoriesparts Qty. No. Accessoriesparts Qty. No. Accessoriesparts Qty.
1
Mountingplate
1 2
Tubelocatingtemplate
1 3
Unitoperationmanual
Installationmanual
2
Thereshouldnotbeanyheatsourceorsteamneartheunit.
Thereshouldnotbeanyobstaclesblockingtheaircirculation.
Aplacewhereaircirculationintheroomisgood.
Aplacewheredrainagecanbeeasilydone.
Donotinstalltheunitnearthedoorway.
Recommendedinstallationheightforindoorunitshallbeatleast2.3m(forceilingunit).
InstallthewallsupportoftheSXVusingtheinstallationtemplatesuppliedwiththeunit.(Fig1)
Thecut-outsfortheunitareshownonthistemplate.
ReminderofMINIMUMclearancestobeprovided.(Fig2)
CoolantconnectionscanbemadeontheLHside,ontheRHsideorattherear.(Fig3)
Condensateevacuationpossibilities:right,left,rearandfrontinthecaseofaceilingmountedunit.(2condensateoutputsareavailableontherecoverytray).
80mm
190mm
900mm
200mm
50mm:ceilingmounted
20mm:ooringmounted
630mm
Liquidpipe
ModelSXV007/009/012A=820mmB=660mm
ModelSXV015/018/021/024A=1200mmB=1040mm
Indoorunitdimensions=A
Fixingboltpitch=B
Fixingboltpitch=300mm
Fixingboltpitch=300mm
Freshairintake
ConnectiontotheSXVtobe
MANDATORILYinsulated
RHoutput
Outputtorear
RH andLH outputsofcondensate
recoverytray
Condensateoutputinthecaseof
aceilingmountedunit
LHoutput
Fig 1
Fig 2
Fig 3
1.Screwdriver 4.Hexagonalwrench 7.Knife
2.Electricdrill,holecoredrill(60mm) 5.Pipecutter 8.Measuringtape
3.Spanner 6.Reamer 9.Torquewrench
INSTALLATION
RemovethewallsupportmountedtherearofyourSXV.
Toinstallthewallsupport,locatethetemplateinordertoobservethecorrectdistancebetweenmountingholesmarkedonit.
Securethewallsupportwith4screws(notsupplied).
NOTE for ooring installation:
Afterdeterminingtheoutletforthecondensate
evacuation(LH,RH,rear),
takecaretoinstallwithapositiveslopfor
condensatedrainage.
Condensatesevacuation
Locationofthreadedrods(Dia8mmmax)forceilinginstallations.Mountingholesforwallinstallation
3
pIpE SELECTION ANd prE-INSTALLATION
ThemainadvantageofyourSXVproductsistogivethepossibilityoflocatingthecoolanttubingonthewallsupportbeforeinstallingtheunit(usingthe
templatesupplied).
Placethetubelocatingtemplateonthewallsupport.(Fig7-1,Fig7-2)
Afterchoosingyourcoolanttubinginputlocation(right,leftorrear),youcansetupyourtubing.Todothis,usetheinstallationtemplateinordertoform
thetubecorrectlyandthusfacilitateconnection.
Locatetheliquidpipeabovethegaspipe.
Press
Slide under
bracket
Locationof
tubingclamps
Pressfully
home
Recessfor
FLAREnuts
All4must
support the
part
ΦLiquidPipe ΦGasPipe
SXV 007 1/4" 1/2"
SXV 009 1/4" 1/2"
SXV 012 1/4" 1/2"
SXV 015 1/4" 1/2"
SXV 018 1/4" 1/2"
SXV 021 3/8" 5/8"
SXV 024 3/8" 5/8"
Fig 4
Fig 5
Fig 6
o
o
Fig7-1
Fig7-2
Fig7-3
Fig 8
Fitthenutsofthe(formed)tubingintotherecessprovidedonthetemplate.(Fig7-2)
Securethetubingwiththeclampsprovided.(Fig9)
Removethetubingtemplate;youcannowinstallyourunitonitssupport.
NOTE
output from the rear
Theslantedholepreventscondensatesorrainfromenteringtheunit.
FitaDia.70mmsleeveintothehole.
Insulatedliquidpiping
Insulatedgaspiping
Securethepipingwith
theclampsprovided
WARNING
Thepipingmustbe
closedtoprevent
impuritiesfromentering
Removethetemplate
4
uNIT INSTALLATION
A
Install the unit to wall support
FOR THE AIR INLET GRILL:
 1Pullthegrillforwards.
 2Removethetwoendscrews.
 3Unscrewthecentralscrew,butdonotremoveitcompletely.
 4Unhookthegrid.
FOR THE SIDE PANELS:
 5Removethesidepanels(downwardmovement).
IMPERATIVE
- For ceiling mounting, install the two clamp
screws (provided) for the unit on the support.
1
B
Installation of the SXV on the wall support
● Refertothediagrambelow,forinstallationoftheSXV.
● Ceilingmounting(refertotheNOTEbelow).
Fig 9
Fig 10
Fig 11
Fig 12
Fig 13
A Connect the drain pipe
●Watercondensationmustbeevacuateddirectlytotheoutside;observeanappropriateslopefortheevacuationduct,whichshouldslopedownwardsthe
caseofaconnectiontothewastewatersystem(2.5cm/mslope).
●AnS-bendmustbeinstalledontheevacuationduct,belowtheleveloftherecoverytrayoftheunit.
●Provideinsulationfortheevacuationpipinginthecaseofariskoffreezingorcondensation.
●Evacuationwithpumpkit:(refertoinstructionsprovidedwithkit).
 a.Theunitissuppliedwithanevacuationpiping.
 b.Therightandleftoutletsareblockedoffbyaplug.Donotforgettoremovethisplugbeforeconnectingtheevacuationpiping.
●Inthecaseofaceilingmountedinstallation,runtheevacuationpipingdownalongthesidepanelandsecureitwithclampsasshownbelow.Alsobreak
thepreformedcut-outintheconeroftheintakegrid.
Condensate recovery
tray
Evacuation
tube
Gas tube
7
ELECTrICAL WIrING CONNECTION
Tighteningtorquefortheterminalscrews
Use the correct screwdriver for tighteningthe terminal
screws.Ifthebladeofscrewdriveristoosmall,thehead
ofthescrewmightbedamaged,andthescrewwillnotbe
properlytightened.If the terminalscrewsaretightened
too hard, screws might be damage. Refer to the table
rightforthetighteningtorqueoftheterminalscrews.
Terminal Size Tighteningtorque
Terminalblock
M3.5 0.8~1.0N.m
5
drAINAGE pIpE CONNECTION
Fig 14
Fig 15
Fig 16
Fig 17
Liquid
tube
B Drainage test
Pouraglassofwaterintothedraintray-styrofoam,ensurethatwaterowsoutfromdrainhose
oftheindoorunit,alongof1minisallowedbeforedischarging,accordingtothelengthofthe
drainpipe,andcheckwhetherwaterleaksfromthejoints.
CAUTIONS:
Ifthereisanymalfunction,pleaseresolveitimmediately.
6
HEIGHT COMpENSATION SETTING
InstallationHeight HeightCode DS11 DS12
2.3-2.7(m) H0 OFF OFF
2.7-3.1(m) H1 OFF ON
3.1-3.5(m) H2 ON OFF
>3.5(m) H3 ON ON
Note
1.Pleasedisconnecttheunitfrompower
supplywhenchangethesesettings.
2.Ifyoufeeltoonoisy,pleasesetDS11and
DS12tolowerheightcodelevel.
Thecompensationsettingaccordingtoinstallationheightcanbedonebyusingthedipswitch11and12oncontrollerPCB.
Powersupplywiring MainbuscommunicationandR/Cwiring
1.Unscrewandremovetheelectricalboxcover.
2.Connectthepowersupplywiringstothepowersupply
terminalblock.
3.Whendoingthis,pressthepowersupplywirings
cunderthewireclip.
1.Unscrewandremovetheelectricalboxcover.
2.ConnectR/CwiringstoR1,R2terminalblockandthe
mainbuswiringstoF1,F2terminalblock.
3.Pressthewiringsunderthewirecliptightly.
NOTE:
Forhowtocnnectthepowerwireandcommunicationwirebetweenoutdoorunitandindoorunits,pleaserefertochapter9
“Fieldwiring”inoutdoorunitinstallationmanual.
ELB:ElectricityLeakageBreaker.
AH:Assistantheater.
Electricalcharacteristics
SpecicationsforeldsuppliedELBandwire
Unit Powersupply Fanmotor
Model Hz Volts MCA MFA KW FLA
SXV007
50 220~240
0.37 16 0.06 0.18
SXV009 0.37 16 0.06 0.18
SXV012 0.37 16 0.06 0.18
SXV015 0.68 16 0.13 0.41
SXV018 0.68 16 0.13 0.41
SXV021 0.68 16 0.13 0.41
SXV024 0.68 16 0.13 0.41
Model
Powersupplywiring
Remotecontrollerwiring
communicationwiring
FieldELB WireandSize Wire Size
SXV007
16A
Mustcomply
withmaximum
currentandlocal
codes(0.75mm
2
)
Twisted-pairwires 1.0mm
2
SXV009
SXV012
SXV015
SXV018
SXV021
SXV024
NOTE:
All field supplied parts and materials and
electricsworksmustconformtolocalcodes.
Usecopperwireonly.
Allwiringmustbeperformedbyanauthorized
electrician.
Every indoor unit must have a sub circle
breaker and the whole system must have a
maincirclebreaker.
Besuretogroundtheairconditioner.
�
Theapplianceshallbeinstalledinaccordance
withnationalwiringregulations,andshallbe
providedtoensureall-poledisconnectionfrom
thesupplymains,anddistancebetweenthe
polesshallbemorethan3mm.
MCA:Min.CircuitAmps(A)
MFA :Max.FuseAmps(A)
KW :FanMotorRatedoutput(KW)
FLA :FullLoadAmps(A)
CHECK ITEMS
NOTE:
Forthepipingandwiringmethods,leakagetest,vacuumprocessandinstallationsetting
throughHMI,pleaserefterto“OutdoorunitInstallationManual”.
Powersupply
Main R/C
BusWiring
BEFORE POWER ON
■Isthereanygasleakageatflarenutconnections?
■Hastheheatinsulationbeencarriedoutatflarenutconnection?
■Istheconnectingcablebeingfixedtoterminalboardfirmly?
■Istheconnectingcablebeingclampedfirmly?
■Isthedrainageok?(Referto"Drainagetestsection)
■Istheearthwireconnectionproperlydone?
■Istheindoorunitproperlyhookedtotheinstallationplate?
■Isthepowersupplyvoltagecompliedwithratedvalue?
AFTER POWER ON
■Isthereanyabnormalsound?
■Isthecoolingoperationnormal?
■Isthethermostatoperationnormal?
■Istheremotecontrol'sLCDoperationnormal?
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6