Viessmann 7968315 is a low gas pressure switch designed to protect your heating system by shutting down the burner when gas pressure drops below a safe level. Suitable for use with Vitocrossal CM2 boilers, this device enhances safety and prevents potential damage caused by low gas pressure. Its adjustable setpoint allows customization based on specific system requirements. Installation requires professional expertise, and the device should be integrated with the boiler's gas supply line.

Viessmann 7968315 is a low gas pressure switch designed to protect your heating system by shutting down the burner when gas pressure drops below a safe level. Suitable for use with Vitocrossal CM2 boilers, this device enhances safety and prevents potential damage caused by low gas pressure. Its adjustable setpoint allows customization based on specific system requirements. Installation requires professional expertise, and the device should be integrated with the boiler's gas supply line.

Installation Instructions
6179 770 - 01 10/2021
Auxilliary Low Gas Pressure Switch
Part No. 7968315 CM2 186
Part No. 7968316 CM2 246 to 620 (TX)
Please file in Service Binder
Refer to the applicable boiler Installation
Instructions.
Ensure that main power to the equipment being serviced
is off.
Ensure that the main fuel supply valve to the boiler is
closed.
Take precautions to avoid accidental activation of power
or fuel during service work.
Do not perform service work on any component part
without ensuring safe operation of the heating system.
When replacing parts, use original Viessmann or
Viessmann approved replacement parts.
Safety and Installation Requirements
Please ensure that these instructions are read and
understood before starting any service work. Failure to
comply with these instructions may cause product/property
damage, severe personal injury and/or loss of life.
Working on the equipment
The installation, adjustment, service and maintenance of
this product must be performed by a licensed professional
heating contractor who is qualified and experienced in
the installation, service, and maintenance of hot water
boilers. There are no user serviceable parts on the boiler,
burner or control.
Codes
Refer to current CAN/CSA B149.1 and .2 or National
Fuel Gas Code ANSI Z223.1/NFPA 54, as well as
local codes for gas piping requirements and sizing.
Pipe size to the boiler must be determined based on:
- pipe length
- number of fittings
- type of gas
- maximum input requirements of all gas appliances
in the residence.
Design piping layout in such a way that piping does not
interfere with serviceable components.
All electrical wiring is to be done in accordance with the
latest edition of CSA C22.1 Part 1 and/or local codes. In
the U.S. use the National Electrical Code ANSI/NFPA 70.
CAUTION
Low gas pressure can cause the heating system to shut
down.
IMPORTANT
Low pressure switches are suitable for making and/or
breaking a circuit when the medium pressure changes
relative to the setpoint. The setpoint can be set in the
field by an adjustable dial with an integrated scale.
Installation Steps
IMPORTANT
for use by heating contractor
for use with:
Vitocrossal CM2 boilers
2
6179 770 - 01
CM2 Low Gas Pressure Switch Installation
Installation - CM2 186 to 620 TX
Installation steps
1. Disconnect boiler power supply.
2. If the boiler has already been installed, shut off main
gas supply to the boiler and disconnect gas supply
piping.
3. Supply and install gas piping components as required
(see illustration on page 5).
4. Route supplied cable beneath the top rail 1 as shown.
Secure using plug-in cable retainers as shown.
5. Remove jumper from terminals 26 and 27 and make
electrical connections as shown between the boiler
and the low gas pressure switch as required..
6. Set the low gas pressure switch to 4.5” wc.
7. Open gas supply to the burner.
Note: The setting must be higher then the GW1
pressure switch (4” w.c.) located on the gas
valve. If a 4” w.c. setting is required then the
GW1 pressure switch must be set below 4”w.c.
8. Using an approved gas leak detector, check gas line
and low gas pressure switch.
9. Reconnect power to the boiler.
Note: Venting is not required, subject to the authority
have jusisdition. The switch has a built-in vent limiter.
Legend
1 Low gas pressure cable (supplied)
CM2 Boiler
connection
Low pressure
gas switch
connection
Cable color
26 (G) Green (GN)
26 (L) COM Black (BK)
26 (N) N White (WT)
27 (L) NO Red (RD)
Legend
A DIN rail (junction box)
B Auxiliary low gas pressure switch (Dungs)
3
6179 770 - 01
CM2 Low Gas Pressure Switch Installation
Operation
Legend
A Nipple (supplied with boiler)
B Elbow (supplied with boiler)
C Reducing tee (kit part)
D Short nipple kit (field supplied)
E Manual gas shutoff valve (supplied with boiler)
F Ground joint union (recommended) (field supplied)
G Reducing bushing kit (only for 7968316)
H Short nipple (kit part)
I Low gas pressure switch*
* the switch can be installed in the gas line anywhere
near the boiler.
Operation
When sufficient gas pressure is available, the low gas
pressure switch contact terminals 3(COM) and 2(NO)
will close. The burner control is then energized and the
system will operate normally.
When sufficient gas pressure is no longer available, the
low gas pressure switch contact terminals 3(COM) and
2(NO) will open. The burner control will stop operating
and generate a fault C1 at the boiler control (the indicator
light on the pressure switch will be illuminated).
To restart the boiler, press the low gas pressure switch
reset button (only once) and reset the boiler control fault.
If the fault persists, verify the gas supply pressure. There
should be a minimum operating pressure of 4.5” w.c., if
not contact your local gas company.
Gas Piping Components
Note: Typical gas piping shown.
6179 770 - 01 Technical information subject to change without notice. Printed on environmentally friendly
(recycled and recyclable) paper.
CM2 Low Gas Pressure Switch Installation
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4

Viessmann 7968315 User manual

Type
User manual

Viessmann 7968315 is a low gas pressure switch designed to protect your heating system by shutting down the burner when gas pressure drops below a safe level. Suitable for use with Vitocrossal CM2 boilers, this device enhances safety and prevents potential damage caused by low gas pressure. Its adjustable setpoint allows customization based on specific system requirements. Installation requires professional expertise, and the device should be integrated with the boiler's gas supply line.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI