INSTALLATION INSTRUCTIONS - WIRING METHOD
“B” - O.E.M.
STEP 1 - REMOVING THE OLD SYSTEM
1. Turn o all electrical power to the furnace being serviced.
2. Double check exisng wiring against wiring method “B” schemac
on page one. If idencal, then proceed as directed below.
3. Disconnect all the wires from the gas valve and the ignion control
unit terminals D, M and TR. Discard these wires. NOTE:The gas
valve is not removed.
4. Disconnect the orange high voltage wire from the top of the ignion
control unit.
5. Remove the heat sensor/ame switch from the pilot burner. It will
not be reused. Do not disturb the electrode which is riveted to the
pilot burner frame.
6. At the ignion control unit, disconnect the wire at terminal T1. Cut
the connector and wire-nut this wire to the gray wire in the new
replacement wiring harness.
7. Disconnect the wire from terminal T2 and wire nut this wire to the
black wire in the new wiring harness. Move the new wiring harness
aside for the moment. Proceed to step 2 below.
STEP 2 - PILOT ELECTRODE/SENSOR ASSEMBLY
There are two types of pilots that may be encountered on your
applicaon: O.E.M. type and retroed type. To determine which
type you have and how to “modernize” it, turn to page 5. Follow the
instrucons given on page 5, then return to this page and connue
to Step 3.
STEP 3 - INSTALLING AND WIRING NEW SYSTEM
1. Install the new ignion control unit using the mounng screws or
double-faced tape included in the modernizaon kit.
2. The new wiring harness in the modernizaon kit should be pre-
wired. If for any reason it isn’t, connect the harness to the ignion
control units as follows: NOTE: Three-wire connector (green, white
and black wire) may be connected to any terminal labeled GND, MV/
PV or TR.
Terminal
WireColor Connecon
Green GND
White Three-wire MV/PV
Black Connector TR
Red MV
Blue PV
Gray TH
3. Install the ground terminal included in the modernizaon kit.
Assemble terminal to valve, see gure 1.
4. Connect the white sensor wire to the “SENSE” terminal.
5. Connect the green ground wire to the ground terminal on the gas
valve. NOTE: System must be grounded or severe damage to gas
valve may result.
6. Connect the RED, WHITE and BLUE wires in the blue wire harness
to the IGNITION CONTROL UNIT and GAS VALVE as shown in the
wiring schemac below.
7. Locate the white jumper wire in the kit. Aach this wire to the
screw terminal TR on the gas valve operator. Aach the other end of
this white wire to one terminal of the solenoid valve.
8. Set thermostat heat ancipator to .7 Amp.
9. Modernizaon of system to FLAME RECTIFICATION is now
complete. Restore electrical power to the furnace and proceed to
SYSTEM CHECKOUT PROCEDURES, page 6. NOTE:The system
circuit is closed when the thermostat contacts close. Power is
supplied to the new ignion control unit terminals TH and TR.
3