Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com
Eaton’s wireless business
www.eaton.com/wireless
Eaton is a registered trademark.
All other trademarks are property
of their respective owners.
105U-2 wireless extension I/O installation guide
EATON_105U-2 Install Guide
Instruction Leaflet IL032003EN
Effective December 2015
Version 2.0
© 2014 Eaton
All Rights Reserved
Printed in USA
Publication No. IL032003EN
December 2015
Installation
Choose a power supply option:
•
12–24Vac, 1.5A CSA certified
Class 2
•
15–30Vdc, 1.5A CSA certified
Class 2
•
11–15Vdc, 1.5A
•
Solar panel with battery
After choosing a power supply
option, wire the module as
shown in Figure 2.
ote:N All I/O must be SELV.
When the wiring is completed,
connect the module to a
computer (PC) and configure
it using the configuration
software. For details, refer to
the user manual.
Before operating the module,
read the sections on operation
and configuration in the user
manual to take advantage of all
product features.
WARNING
EXPLOSION HAZARD
Do not disconnect while circuit
is live unless area is known to be
non-hazardous.
Figure 2. Wiring Diagram
11–15 Vdc Supply or
Optional 12V Backup Battery
12 Ah for AC/DC
100 Ah for Solar
-
+AI 2
-
+AI 1
+24V
DI 3
SOL
DI 2
DI 1
GND
COM
DI 4
SUP2
SUP1
BAT+
AI 3 +
AI 4 +
AI 6 +
AI 5 +
GND
+24V
DOT
COM
OUTPUT
1
3
4
INPUTS
COM
ELPRO
105U-2 Multi I/O
2A
+
-
-
-
+
+
-
+
External-Powered
Analog Transducer
Loop-
Powered
Analog
Transducer
Digital Input
Voltage-Free
Contact or
Transistor
Device
To Earth Stake
DC Supply
15–30 Vdc
Min. 17 Vdc
for Battery
Charging
SOL
GND
SUP2
SUP1
AC Supply
12–24 Vac
Min. 15 Vac
for Battery
Charging
Do not earth
SUP1 or SUP2
connection.
12V Solar
Panel Supply;
Max. 20 Vdc
Max. 30 W
Panel
Digital Output
Max. 30 Vdc, 500 mA
DC Relay Supply
DC Load