Schneider Electric Smart-UPS Ultra User manual

Category
Uninterruptible power supplies (UPSs)
Type
User manual
User Manual
Smart-UPS Ultra On-Line
Uninterruptible Power Supply
SRTL3KRM1UWC
SRTL3KRM1UWNC
SRTL3KRM1UIC
SRTL3KRM1UINC
SRTL2K2RM1UWC
SRTL2K2RM1UWNC
SRTL2K2RM1UIC
SRTL2K2RM1UINC
suo2079a
1SRTL3KRM1U WC/WNC/IC/INC, SRTL2K2RM1U WC/WNC/IC/INC
General Information
Important Safety Instructions
SAVE THESE INSTRUCTIONS - This manual contains important instructions that should be followed during
installation and maintenance of the APC Smart-UPS Ultra and batteries.
Read the instructions carefully to become familiar with the equipment before attempting to install
and operate the equipment UPS.
The following special messages may appear throughout this manual or on the equipment to warn of potential
hazards or to call attention to information that clarifies or simplifies a procedure.
The addition of this symbol either to a “Danger” or “Warning” safety label indicates that an electrical
hazard exists which will result in personal injury if the instructions are not followed.
This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all
safety messages that follow this symbol to avoid possible injury or death.
Product Handling Guidelines
DANGER
DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury.
WARNING
WARNING indicates a hazardous situation which, if not avoided, could result in death or serious
injury.
CAUTION
CAUTION indicates a hazardous situation which, if not avoided, could result in minor or moderate
injury.
NOTICE
NOTICE is used to address practices not related to physical injury.
<18 kg
<40 lb
18-32 kg
40-70 lb
32-55 kg
70-120 lb
>55 kg
>120 lb
SRTL3KRM1U WC/WNC/IC/INC, SRTL2K2RM1U WC/WNC/IC/INC2
Safety and General Information
Adhere to all national and local electrical codes.
All wiring must be performed by a qualified electrician.
Connect only SELV circuits to all the communication ports.
Changes and modifications to this unit not expressly approved by Schneider Electric could void the
warranty.
This UPS is intended for indoor use only.
Do not operate this UPS in direct sunlight, in contact with fluids, or where there is excessive dust or
humidity.
Be sure the air vents on the UPS are not blocked. Allow adequate space for proper ventilation.
For a UPS with a factory installed power cord, connect the UPS power cable directly to a wall outlet.
Do not use surge protectors or extension cords.
The equipment is heavy. Always practice safe lifting techniques adequate for the weight of the equipment.
The replaceable battery modules (RBM) are heavy. Remove the RBMs before installing the UPS and
external battery packs (XLBPs), in a rack.
Always install XLBPs at the bottom in rack-mount configurations. The UPS must be installed above the
XLBPs.
Always install peripheral equipment above the UPS in rack-mount configurations.
Additional safety information can be found in the Safety Guide supplied with this unit.
Deenergizing safety
The UPS contains RBM and may present a shock hazard even when disconnected from the branch circuit (mains).
Before installing or servicing the equipment check that the:
input circuit breaker is in the OFF position.
RBMs are removed.
XLBPs are disconnected.
Electrical safety
Do not handle any metallic connector before power has been disconnected.
The connection to the branch circuit (mains) must be performed by a qualified electrician.
The protective earth conductor for the UPS carries the leakage current from the load devices (computer
equipment). An insulated ground conductor is to be installed as part of the branch circuit that supplies the
UPS. The conductor must have the same size and insulation material as the grounded and ungrounded
branch circuit supply conductors. The conductor will typically be green and with or without a yellow stripe.
The UPS input ground conductor must be properly bonded to protective earth at the service panel.
Leakage current for a pluggable Type A UPS may exceed 3.5 mA when a separate ground terminal is used.
If the UPS input power is supplied by a separately derived system, the ground conductor must be properly
bonded at the supply transformer or motor generator set.
3SRTL3KRM1U WC/WNC/IC/INC, SRTL2K2RM1U WC/WNC/IC/INC
Battery safety
* Contact APC by Schneider Electric Worldwide Customer Support to determine the age of the installed RBMs.
Note: Servicing of battery modules should be performed or supervised by personnel knowledgeable about batteries
and the required precautions.
The RBMs typically lasts for eight to ten years. Environmental factors impact life of the RBM. Elevated
ambient temperatures, poor quality utility power, and frequent short duration discharges will shorten battery
life.
For longer performance of the RBM, the ambient temperature should be maintained between 68 and 77 °F
(20 and 25 °C).
Schneider Electric uses Maintenance-free Lithium-Ion batteries. Under normal use and handling, there is no
contact with the internal components of the RBM.
Do not drive nails into the RBM.
Do not strike the RBM with a hammer.
Do not stand on the RBM.
Do not short circuit RBM.
Do not place or use the RBM near heat or fire.
Do not use a dropped, damaged or deformed RBM.
Do not use the RBM to power other equipment.
CAUTION: A battery can present a risk of electrical shock and high short-circuit current. Contact with any
part of a grounded battery can result in electrical shock. The following precautions should be observed
when working on RBMs:
Disconnect the charging source prior to connecting or disconnecting battery terminals.
Do not wear any metal objects including watches and rings.
Do not lay tools or metal parts on top of batteries.
Use tools with insulated handles.
Wear rubber gloves and boots.
Determine if RBM is either intentionally or inadvertently grounded. Contact with any part of a
grounded battery can result in electric shock and burns by high short-circuit current. The risk of such
hazards can be reduced if grounds are removed during installation and maintenance by a skilled person.
CAUTION: Before installing or replacing the RMBs, remove jewelry such as wristwatches and rings.
High short circuit current through conductive materials could cause severe burns.
CAUTION: Do not dispose of RBMs in a fire. The RBM may explode.
CAUTION: Do not open or tamper with the RBM enclosure. Doing so will expose the cell terminals which
poses an energy hazard.
CAUTION: Do not open or mutilate RBM. Released material is harmful to the skin and eyes and may be
toxic.
CAUTION: Failed RBMs can reach temperatures that exceed the burn thresholds for touchable surfaces.
WARNING
RISK OF CHEMICAL HAZARD AND EXCESSIVE HEAT
Replace the RBM at least every 10 years, or at the end of its service life, which ever is earlier.
Replace the RBM immediately when the UPS indicates battery replacement is necessary.
Replace RBM with the same type as originally installed in the equipment.
Replace the RBM immediately when the UPS indicates a battery over-temperature condition or UPS
internal over-temperature. Power off the UPS, unplug it from the AC input, and disconnect the RBM. Do
not operate the UPS until the RBM has been replaced.
*Replace all XLBPs which are older than one year, when installing additional XLBPs.
Failure to follow these instructions can result in death or serious injury.
SRTL3KRM1U WC/WNC/IC/INC, SRTL2K2RM1U WC/WNC/IC/INC4
General information
The UPS will recognize as many as 5 XLBPs (SRTL50RMBP1U-LI) connected to the UPS.
Note: For each XLBP added, increased recharge time will be required.
The model and serial numbers are located on a small, rear panel label. An additional label is located on the
draw out tray behind the front bezel. Refer “Location of QR Codes for Product information and
Registration” on page 8 for details.
Always recycle used RBMs.
Recycle the package materials or save them for reuse.
Radio Frequency Warning
This is a category C2 UPS product. In a residential environment, this product may cause radio interference, in
which case the user may be required to take additional measures.
5SRTL3KRM1U WC/WNC/IC/INC, SRTL2K2RM1U WC/WNC/IC/INC
Package Contents
Inspect the contents upon receipt. Notify the carrier and dealer if the unit is damaged.
Product Description
The APC Smart-UPS Ultra SRTL is a high power density and high performance uninterruptible power supply
(UPS). The UPS helps to provide protection for electronic equipment from utility power blackouts, brownouts,
sags, surges, small utility power fluctuations and large disturbances. The UPS also provides battery backup power
for connected equipment until utility power returns to acceptable levels or the batteries are completely discharged.
This user manual is available on www.schneider-electric.com. By scanning the QR code provided with the specific
product, you can visit the product webpage and get all relevant product information.
UPS USB cable User documentation 3 input power cords
IEC C20 – C19
IEC C19 – CEE 7
IEC C19 - BS 1363
IEC C13 - C14
Flat head screws (10X)
Washers (8X)
Ornamental Screws (2X)
Panhead screws (8X)
Front bezel Network cable PCSS insert
Battery module EPO terminals Rails
Rack-mount / wall mount
brackets (4X)
Stabilizers (4X) Cleats Flat head screws (8X)
1234
gen1079a
SRTL3KRM1U WC/WNC/IC/INC, SRTL2K2RM1U WC/WNC/IC/INC6
Product Overview
Specifications
For additional specifications visit our web site, www.schneider-electric.com.
Environmental
Physical
The products are heavy. Follow all lifting guidelines.
Electrical
CAUTION: To reduce the risk of fire, connect only to a circuit provided with recommended maximum branch
circuit overcurrent protection in accordance with the National Electrical Code, ANSI/NFPA 70 and the Canadian
Electrical Code, Part I, C22.1., for North America, IEC/EN 60934 for Europe, 208V single phase without N in
North American, recommended Double - Pole branch circuit over current protection.
Applicable power grid power distribution system TN Power System
Overvoltage category II
Applicable standard IEC 62040-1
Temperature Operating 0 to 40 ºC (32 to 104 ºF)
Storage -15 to 45 ºC (5 to 113 ºF)
Elevation Operating 0 - 3,000 m (0 - 10,000 ft)
Storage 0 - 15,000 m (50,000 ft)
Humidity 0% to 95% relative humidity, non-condensing
Pollution degree 2
International Protection Code IP20
Note: Charge the battery modules every twelve months during storage.
Environmental factors impact battery life. Elevated ambient temperatures, high humidity, poor quality mains power, and
frequent short duration discharges will shorten battery life.
Unit weight, without packaging (approx.) 14 kg (30.9lb)
Unit weight, with packaging 24.2 kg (53.3 lb)
Unit dimensions, without packaging
Height x Width x Depth
43 x 432 x 560 mm
(1.7 x 17 x 22 in)
Unit dimensions, with packaging
Height x Width x Depth
278 x 576 x 764 mm
(10.95 x 22.68 x 30.10 in)
Models SRTL3KRM1UWC
SRTL3KRM1UWNC
SRTL3KRM1UIC
SRTL3KRM1UINC
SRTL2K2RM1UWC
SRTL2K2RM1UWNC
SRTL2K2RM1UIC
SRTL2K2RM1UINC
Maximum Output Rating 3000 VA / 3000 W 2200 VA / 2200 W
Branch Circuit
Overcurrent Rating /
Building Circuit Breaker
(CB) Current Rating
250V; 20A (North American), 250V;16A (Europe)
Output
Output Frequency 50/60 Hz ± 3 Hz
Nominal Output Voltage 208 V, 220 V, 230 V,
240 V
220 V, 230 V, 240 V 208 V, 220 V, 230 V,
240 V
220 V, 230 V, 240 V
Connector Type
Main Outlet Group (1) IEC 320 C13 + (1) C19
Switched Outlet Group (2) IEC 320 C13 + (1) C19
Input
Connector Type IEC C20
Input Frequency 50/60 Hz ± 3 Hz (auto sensing)
Nominal Input Voltage 208 V ~ 240 V 220 V ~ 240 V 208 V ~ 240 V 220 V ~ 240 V
Nominal Input Current 16 A
Input Voltage Range 160 to 275 V ± 5 V
7SRTL3KRM1U WC/WNC/IC/INC, SRTL2K2RM1U WC/WNC/IC/INC
Battery
Front Panel Features
Battery type Lithium-Ion
Internal RBM
Refer to the appropriate replacement battery user manual for installation instructions.
Contact your dealer or visit our web site, www.schneider-electric.com for information on
replacement batteries.
APCRBC173-LI
Number of RBMs in UPS 1
Voltage of each RBM 50.4 V
Ah rating 5.16 Ah
Compatible XLBP SRTL50RMBP1U-LI
LCD display
POWER button
Draw out tray containing QR codes and MAC Address label of NMC
RBM thumbscrew
RBM
Front bezel
suo2081a
SRTL3KRM1U WC/WNC/IC/INC, SRTL2K2RM1U WC/WNC/IC/INC8
Location of QR Codes for Product information and
Registration
Rear Panel Features
Note: Refer to the table “Key to identify rear panel features” on page 9, that provides a key to the callout numbers
for the rear panel graphics depicted in this manual.
SRTL3KRM1U WNC/INC, SRTL2K2RM1U WNC/INC
Remove the front bezel
Pull out the tray.
QR code for SmartConnect. Refer “APC SmartConnect” on
page 26 for details.
MAC address label for downloading user documentation and
product information.
suo2082a
suo2083a
suo2084a
suo2077a
9SRTL3KRM1U WC/WNC/IC/INC, SRTL2K2RM1U WC/WNC/IC/INC
SRTL3KRM1U WC/IC, SRTL2K2RM1U WC/IC
Key to identify rear panel features
Chassis Ground Screw The UPS and XLBPs have ground screws for connecting the ground leads. Prior to
connecting a ground lead, disconnect the UPS from mains power.
External battery connector
receptacle (power and
communication)
Use the external battery cable on the XLBP to connect the UPS and XLBP.
XLBPs provide extended runtime during power outages. The UPS will
automatically recognize up to 5 external battery packs.
NOTE: A CAN bus terminator is installed in this receptacle before shipping the
UPS from the factory. While connecting an XLBP, remove the CAN bus terminator
from the UPS and install it in the battery connector receptacle in the XLBP. Refer to
the XLBP installation manual for detailed instructions.
EPO terminal The Emergency Power Off (EPO) terminal allows the user to connect the UPS to a
central EPO system.
Universal I/O port Connect temperature sensors, temperature/humidity sensors, and relay input/output
accessory connectors to this port.
USB port Support for NMC and UPS firmware updates and the optional APC USB Wi-Fi
Device (AP9834).
Ethernet port Embedded Ethernet for
SmartConnect (UC models)
NMC 3 (UNC models)
Data port The Data port is used to connect either a server for native operating system
communications, or for software to communicate with the UPS.
Micro USB port This is an NMC console port.
Connect the NMC to a local computer, using a micro-USB cable
(APC part number 960-0603), to configure initial network settings or access the
command line interface (CLI).
RESET button Press this button to Restart the network management interface.
NOTE: This does not affect the output of the UPS.
Main outlet group Connect electronic devices to the main outlet.
Switched outlet group Connect electronic devices to these outlets.
UPS Input Connect electronic devices to the input.
Serial port The Serial port is used to communicate with the UPS.
Use only interface kits supplied or approved by APC by Schneider Electric.
Any other serial interface cable will be incompatible with the UPS connector.
suo2078a
SRTL3KRM1U WC/WNC/IC/INC, SRTL2K2RM1U WC/WNC/IC/INC10
Installation
Rack Installation
4 post rack mounting
Refer to the Rail Kit Installation Guide for instructions on rail installation.
CAUTION
RISK OF FALLING EQUIPMENT
The equipment is heavy. Always practice safe lifting techniques adequate for the weight of the equipment.
Always use the recommended number of screws to secure brackets to the UPS.
Always use the recommended number of screws and cage nuts to secure the UPS to the rack.
Always install the UPS at the bottom of the rack.
Always install the external battery pack below the UPS in the rack.
Failure to follow these instructions can result in equipment damage and minor or moderate injury.
Install the cleats to the
UPS.
Install the rack-mount
brackets to the UPS.
Install the UPS to the 4 post rack.
4X
suo2085a
4X
suo2086a
11SRTL3KRM1U WC/WNC/IC/INC, SRTL2K2RM1U WC/WNC/IC/INC
Install the RBM in the UPS.
Tighten the RBM thumbscrew.
Install the front bezel.
su o2 08 8a
suo2089a
suo2090a
SRTL3KRM1U WC/WNC/IC/INC, SRTL2K2RM1U WC/WNC/IC/INC12
2 post rack-mounting
Tower Installation
Install the rack-mount brackets to the UPS.
Install the UPS to the 2 post rack.
Install the RBM as per steps and in “4 post rack mounting” on page 10.
Install the front bezel as per step in “4 post rack mounting” on page 10.
CAUTION
RISK OF FALLING EQUIPMENT
The equipment is heavy.
Always practice safe lifting techniques adequate for the weight of the equipment.
Failure to follow these instructions can result in equipment damage and minor or moderate injury.
Assemble the foot stabilizers. Install the stabilizers on the UPS.
Install the RBM as per steps and in “4 post rack mounting” on page 10.
Install the front bezel as per step in “4 post rack mounting” on page 10.
suo2165a
4X
2X
suo 216 6a
suo2093a
suo2094a
13SRTL3KRM1U WC/WNC/IC/INC, SRTL2K2RM1U WC/WNC/IC/INC
Wall Installation
CAUTION
RISK OF FALLING EQUIPMENT
The equipment is heavy.
Always practice safe lifting techniques adequate for the weight of the equipment.
Failure to follow these instructions can result in equipment damage and minor or moderate injury.
Install the rack-mount brackets to the
UPS.
Install the RBM as per steps and in “4 post rack mounting” on page 10.
Install the front bezel as per step in “4 post rack mounting” on page 10.
8X
suo2095a
8X
SRTL3KRM1U WC/WNC/IC/INC, SRTL2K2RM1U WC/WNC/IC/INC14
Operation
Connect Equipment and Input Power
Note: The UPS RBM will charge to 90% capacity in the first 1.5 hours of normal operation. Do not expect full
battery runtime capability during this initial charge period.
1. Connect equipment to the outlets on the rear panel of
the UPS.
Refer to Controllable Outlet Groups” on page 23.
2. Connect the UPS to the building utility power.
Turn the UPS On/Off
The first time the UPS is turned on the Setup Wizard screen will run. Follow the prompts to configure UPS
settings. Refer to “Configuration” on page 18.
To turn on the UPS and all connected equipment, touch the POWER button on the display panel. Follow the prompts
to either turn the UPS on immediately or after a delay, then touch the OK button.
NOTE: When there is no input power and the UPS is off, the cold start feature can be used to turn on the UPS and
connected equipment using battery power.
To perform a cold start, touch the POWER button.
The display panel will illuminate.
To turn on the output power touch the POWER button again. Select the prompt to either TurnOn-No Delay or
TurnOn-Use Delay, then touch the OK button.
To turn output power off, touch the POWER button. Follow the prompts to either turn the UPS off immediately or
after a delay, then touch the OK button.
NOTE: Once the UPS output power has been turned off and the AC input has been disconnected, the UPS will
continue to use the battery for internal power for 10 minutes. To remove power completely touch the
POWER button. Follow the prompt to select Internal Power Off, then touch the OK button.
CAUTION
RISK OF ELECTRIC SHOCK
Disconnect the mains input circuit breaker before installing or servicing the UPS or connected equipment.
Disconnect internal RBM and XLBPs before installing or servicing the UPS or connected equipment.
The UPS contains internal RBM and XLBPs that may present a shock hazard even when disconnected
from the mains.
UPS AC hardwired and pluggable outlets may be energized by remote or automatic control at any time.
Disconnect equipment from the UPS before servicing any equipment.
Do not use the UPS as a safety disconnect.
Failure to follow these instructions can result in minor or moderate injury.
suo2097a
15SRTL3KRM1U WC/WNC/IC/INC, SRTL2K2RM1U WC/WNC/IC/INC
UPS Display Interface
UPS Display Interface operation
The UPS display interface is a touchscreen interface.
Touch on the icon to activate the key function.
Use the UP/DOWN buttons to scroll through the options. Touch the OK button to accept the selected option. Touch
the ESC button to return to the previous menu.
.
MENU/ESCAPE button
Battery capacity icon
Battery charging icon
Green mode icon
Operation mode icon
UP button
UPS status information
DOWN button
controllable outlet group status icon
Mute icon
Load icon
OK button
POWER button with LED
Touch the button to wake up the UPS, when it is off state.
A short touch of the button will display the control menu.
Follow the prompts on the screen to either turn the UPS on/off immediately or after a delay.
LED illumination indications are the same as the Status LED.
Status LED
Not illuminated: UPS output is off.
Illuminates steady green: UPS is in on-line mode.
Flashes red every 2 seconds: UPS is in on-line status and battery is disconnected.
Illuminates amber: UPS is in battery mode.
Illuminates steady red: UPS has detected an internal error.
The icons on the LCD display interface screen may vary depending on the installed firmware versions and specific UPS
models.
Load icon: The approximate load capacity percentage is indicated by the number of load bar
sections illuminated. Each bar represents 20% of the load capacity.
Mute icon: Indicates the audible alarm is disabled/muted.
su o2 100a
SRTL3KRM1U WC/WNC/IC/INC, SRTL2K2RM1U WC/WNC/IC/INC16
UPS Status Information
The status information field provides key information on the status of the UPS.
The menu will allow the user to select one of the five screens listed below or scroll through the five screens
automatically.
Use the UP/DOWN buttons to scroll through the screens.
Input Voltage
Output Voltage
Output Frequency
•Load
• Runtime
In the case of a UPS event, status updates will be displayed defining the event or condition that has occurred.
The display screen illuminates amber to indicate an alert and red to indicate an alarm depending on the severity of the
event or condition.
Operation Mode Icons
Output Off: The UPS isn't supplying power to connected equipment.
Battery mode: The UPS is supplying battery power to connected equipment.
On-Line mode: The UPS is supplying conditioned mains power to connected equipment.
Bypass mode: The UPS is in Bypass mode and the connected equipment will receive mains
power as long as the input voltage and frequency are within the configured limits.
Green mode Icon
Green mode: When in Green mode mains power is sent directly to the load.
When enabling Green mode consideration should be given to devices that may be sensitive to
power fluctuations.
Controllable Outlet Group Icons
Controllable outlet group - output on.
Controllable Outlet Group - output off.
Battery Status Icons
Battery charge status: Indicates the battery charge status.
Battery disconnected icon: Flashes to indicate that the UPS has detected that the battery is
disconnected.
Battery charge in progress: Indicates the battery is charging.
17SRTL3KRM1U WC/WNC/IC/INC, SRTL2K2RM1U WC/WNC/IC/INC
LCD display interface angle adjustment
The orientation of the LCD display interface gets adjusted automatically based on UPS orientation.
Menu overview
The UPS Display Interface has Standard and Advanced menu screens. The preference for Standard or Advanced
menu selections is made during initial installation and can be changed at any time through the Configuration
menu.
The Standard menus include the most commonly used options.
The Advanced menus provide additional options.
NOTE: Actual menu screens may differ by model and firmware version.
Horizontal Vertical
su o2 06 2a
suo206 3a
UPS Menu Overview
Configuration Menu**
UPS
Battery
Outlets Groups**
Communication
USB Device***
Display
Install FW**
Efficiency Test Mode*
UPS**
Green Mode
Voltage AC Setting
Battery Setting Runtime Alert
Self Test Schedule
Default Setting
Energy Meter
*
USB Device***
Eject***
Save Log File***
Save Config File***
Install Config File***
Install UPS FW***
Install NMC FW***
suo2 039a
Accessory***
Probe1: Temp***
***Probe1: Humidity
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37

Schneider Electric Smart-UPS Ultra User manual

Category
Uninterruptible power supplies (UPSs)
Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI