4
FIG. 10
FIG. 11
C. WIRING PROCEDURE
1. All Wiring connections use FIG. 10.
2. Connect White Sensor Harness (Supplied) to P4 plug on
Main Printed Circuit Board (if Remote Sensor is used, it
should be unplugged).
3. Connect White Sensor Harness into either of the 2-pin
socket on Dometic Furnace Signaling Interface Module.
(Plug Remote Sensor if used into the remaining 2-pin
Socket).
4. Make a short (8 - 10”) communication cable with RJ11-6P-
4C connectors on each end. See FIG. 11.
5. Connect the new communications cable into one of the
RJ11-6P-4C sockets on the Two Speed Power Module.
6. Connect the remaining end of the new communications
cable into P1 or P2 (it makes no difference) on the main
printed circuit board. If both P1 and P2 have a communica-
tion cable plugged into the main circuit board, remove one
and plug it into the open RJ11-6P-4C socket on the Dometic
Furnace Signaling Interface Module.
7. Use a wire nut to connect the green wire of the Dometic
Furnace Signaling Interface Module to input signal
ground connection ( Atwood Green Wire).
8. Use a wire nut to connect the blue furnace wire of the
Dometic Furnace Signaling Interface Module to furnace in-
put signal connection (Atwood Blue Wire - Nominal + 8.5
VDC).
9. Set the Dip Switch #5 (furnace of the Main Printed Circuit
Board to “ON”.
10. Turn “ON” the Dip Switch on the Dometic Furnace Signal-
ing Interface Module to match the zone number of the main
printed circuit board dip switch.
NOTE: Dip Switches 1 and 5 are not used on the Dometic
Furnace Signaling Interface Module and should always be
in the “OFF” position. Dip switches 2 , 3 and 4 match the
zones of the main printed circuit board.
11. After the unit is installed and power is available, the Com-
fort Control CenterTM must be reset. See Section D.
D. SYSTEM RESET
After setting the dip switches in the electronic control kit,
do a system reset.
1. Turn the ON/OFF switch to the "OFF" position.
2. Simultaneously depress and hold the MODE and ZONE
push-buttons while turning the ON/OFF switch to "ON". FF
should appear in LCD display until the mode and zone push-
buttons are released.
3. When a dip switch is turned on after initial configuration, a
system reset will need to be done before the Comfort Control
CenterTM will recognize the updated selection.
e. Brisk Air units being installed with 3308120 Return
Air Cover.
1. Brisk Air Models installed with the 3308120 Return
Air Cover require the 3109226.005 electric kit to be
mounted on the front lip of the ceiling template. See
FIG. 10.
Peel Off Tape
Place Dometic
Furnace Signaling
Interface Module
on Side of Control
Box and Secure
with Screws
Mount Control Box
on Front Lip of
Ceiling Template
2. The Dometic Furnace Signaling Interface Module is
to be placed on the side of control box between the
its’ cover and the right edge. See FIG.10.
3. Peel the protective tape off the Dometic Furnace
Signaling Module and fasten it on the side of the
control box with a blunt point screws. See Section
C Wiring Procedure.
4. Install unit per its installation instructions.
f. Penguin Model units being installed with
3308120 Return Air Cover.
1. Some Penguin Models installed with the 3308120
Return Air Cover require the control box to be
mounted across the large opening in the ceiling
template (except models shown in Section B, item
2, paragraph c). See Fig. 11.
2. Peel the protective tape of the Dometic Furnace
Signaling Interface Module. Place it on the upper
flat surface of the control box (on the opposite side
of the cover of the control box, aligned with one
hole and box edge) as shown in FIG. 11.
3. Secure Dometic Furnace Signaling Interface Mod-
ule with a blunt screws. See Section C Wiring Pro-
cedure.
4. Install unit per its installation instructions.
Peel Off Tape Place Dometic Furnace
Signaling Interface Module on Top Side of
Control Box and Secure with Screw
FIG. 10 Screw