Viessmann Versatronik 503 NR2/Analog Bridge Operating instructions

Type
Operating instructions
Please file in Service Binder6204788 - 02 11/2023
NR2/Analog Bridge
Installation and
Operating Instructions
for use by heating contractor
Versatronik 503 Communication Module
Part Number: 7984983
Product may not be exactly as shown
Read and save these instructions
for future reference.
IMPORTANT
LR 102874
2
6204788 - 02
Versatronik 503 NR2/Analog Bridge
HDangerous Conditions
- Deactivate main power immediately.
- Close gas supply valve.
HIn Emergencies
Immediately switch off the external power supply to
the panel. e.g. at the separate fuse or power supply
HInstallation of additional Components
The installation of additional components which
have not been tested together with the panel can
adversely affect the function and performance of
the panel.
Our warranty does not cover and we accept no
liability for damage attributable to the installation of
such components.
2
Safety, Installation and Warranty Requirements
Safety
fProduct documentation fLicensed professional heating contractor
Read all applicable documentation before
commencing installation. Store documentation
near heat pump in a readily accessible
location for reference in the future by service
personnel.
The installation, adjustment, service and
maintenance of this equipment must be
performed by a licensed professional heating
contractor.
u For a listing of applicable
literature, please see section entitled
“Important Regulatory and Safety
Requirements”.
u Please see section entitled “Im-
portant Regulatory and Installation
Requirements”.
fAdvice to owner fWarranty
Once the installation work is complete, the heating
contractor must familiarize the system operator/
ultimate owner with all equipment, as well as safety
precautions/requirements, shutdown procedure, and
the need for professional service annually before the
heating season begins.
Information contained in this and
related product documentation must
be read and followed. Failure to do so
renders the warranty null and void.
Please ensure that these instructions are read and understood before commencing installation. Failure to
comply with the instructions listed below and details printed in this manual can cause product/property
damage, severe personal injury, and/or loss of life. Ensure all requirements below are understood and
fulfilled (including detailed information found in manual subsections).
3
6204788 - 02
Versatronik 503 NR2/Analog Bridge
3
Table of Contents
Index
Safety
Safety, Installation and Warranty Requirements ................................... 2
Table of Contents
Index .............................................................................................. 3
Important Precautions
Important Regulatory and Installation Requirements .............................. 4
General Information
About these Installation Instructions ................................................... 5
Intended Use ................................................................................... 5
Installation
Mounting the Communication Module ................................................. 6
Overview of Electrical Connections ..................................................... 7
Connections
Setting the Rotary Switch S1 ............................................................ 8
Setting the DIP Switches S2 .............................................................. 9
Boiler Connections ........................................................................... 11
LON Connections ............................................................................. 12
Power Supply .................................................................................. 13
Configuration
Configuring the Boilers ...................................................................... 14
Specifications
Specifications .................................................................................. 15
Troubleshooting
Troubleshooting ............................................................................... 16
4
6204788 - 02
Versatronik 503 NR2/Analog Bridge
Approvals
Viessmann boilers, burners and controls are
approved for sale in North America by CSA
International.
Codes
The installation of this unit shall be in accordance
with local codes. In the absence of local codes, use:
- CSA C22.1 Part 1 and/or local codes in Canada
- National Electrical Code ANSI/NFPA 70 in the U.S.
Always use latest editions of codes.
The heating contractor must comply with the
Standard for Controls and Safety Devices for
Automatically Fired Boilers, ANSI/ASME CSD-1
where required by the authority having jurisdiction.
Working on the equipment
The installation, adjustment, service, and
maintenance of this product must be done by a
licensed professional heating contractor who is
qualified and experienced in the installation, service,
and maintenance of hot water boilers. There are
no user serviceable parts on the boiler, burner, or
control.
Power supply
Install power supply in accordance with the
regulations of the authorities having jurisdiction or,
in absence of such requirements, in accordance
with National Codes. Viessmann recommends the
installation of a disconnect switch to the 120V
power supply outside of the boiler room.
Ensure main power supply to equipment, the
heating system, and all external controls have
been deactivated. Close main oil or gas supply
valve. Take precautions in both instances to avoid
accidental activation of power during service work.
fPlease carefully read this manual prior to
attempting installation. Any warranty is null and
void if these instructions are not followed.
For information regarding other Viessmann System
Technology componentry, please reference
documentation of the respective product.
We offer frequent installation and service seminars
to familiarize our partners with our products.
Please inquire.
fThe completeness and functionality of field
supplied electrical controls and components must
be verified by the heating contractor. These
include low water cut-offs, flow switches (if
used), staging controls, pumps, motorized valves,
air vents, thermostats, etc.
1 WARNING
Turn off electric power supply
before servicing. Contact with live
electric components can cause
shock or loss of life.
Important Regulatory and Installation Requirements
Important Precautions
1 CAUTION
HField modifications of this control panel
manufactured by Viessmann Manufacturing
Company Inc. will void factory CSA certification!
HIf modifications are performed, electrical safety
field inspection is required according to local
codes.
HViessmann Manufacturing Company Inc. is not
responsible for any damage, injury or loss of life
resulting from field modifications
5
6204788 - 02
Versatronik 503 NR2/Analog Bridge
Intended use of the Versatronik 503 NR2/Analog
Bridge is to integrate a boiler equipped with a One
Base control into a pre-existing NR2/LON cascade
system.
On the LON communication side, the Versatronik
503 behaves like any other boiler in the cascade. It
then communicates this information, in analog, to
the target boiler.
More specifically, the cascade control sends these
commands to a boiler: Temperature setpoint and on/
off command. This, in turn, is then communicated
with the target boiler as a 0-10V signal.
The Versatronik 503 equipped boiler is responsible
for relaying the following parameters back to the
cascade: Boiler Temperature, Modulation rate,
and fault status. This is achieved through analog
outputs from the boiler, and a strap-on sensor
(included) that must be mounted on the supply
side of the boiler being integrated into the cascade
system.
About these Installation Instructions
General Information
uThis symbol indicates that additional, pertinent
Information is to be found.
1 WARNING
Indicates an imminently hazardous situation
which, if not avoided, could result in death,
serious injury or substantial product/property
damage.
1 CAUTION
Indicates an imminently hazardous situation
which, if not avoided, may result in minor injury or
product/property damage.
IMPORTANT
1Take note of all symbols and notations intended to draw attention to potential hazards or important
product information. These include “WARNING”, “CAUTION”, and “IMPORTANT”. See below.
uWarnings draw your attention to the presence of
potential hazards or important product information.
uCautions draw your attention to the presence of
potential hazards or important product information.
uHelpful hints for installation, operation or
maintenance which pertain to the product.
u uThis symbol indicates that additional, pertinent
Information is to be found.
Intended Use
6
6204788 - 02
Versatronik 503 NR2/Analog Bridge
1. Mount Versatronik 503 in a convenient location
near the One Base boiler. Remove cover by
loosening the two screws on either side of the
base to release the cover.
2. Fasten base to wall, or back of boiler, using
field-supplied screws/fasteners.
3. Remove knockout and install wire strain relief or
box connector. Removal of remaining knockouts
is required to make further connections.
4. Once all of the 120VAC and low voltage
connections are complete and verified, reinstall
the cover from Step 1.
2.
1.
3.
Mounting the Communication Module
Installation
7
6204788 - 02
Versatronik 503 NR2/Analog Bridge
Legend
A Power Supply (120VAC) with preinstalled 6 ft (2
meter) convenience plug
B LON Connection (LON1)
C LON Connection (LON2)
D 0-10VDC Boiler Temperature Setpoint Output to
boiler (BLR CMD)
E Fault Message Input from Boiler (FAULT)
F Boiler Temperature Input from boiler (BLR TEMP)
G 0-10VDC Boiler Temperature Input from boiler
(BLR STS)
H Rotary Dial (S1)
I DIP Switches (S2)
Note:
Apply strain relief to on-site cables. Secure
individual wires directly to each plug using cable
ties. Seal any unnecessary apertures with cable
grommets (not cut open).
1 CAUTION
The electronic modules are static
sensitive. To avoid damage
caused by static discharge, follow
Electrostatic Discharge safety
procedures.
LON 1
LON 2
1212
H
LN1
R41
R17
1212
1 5
1234567
ON
12
3 4
1 2 345 6 7
C8
C9
IC4
R14
IC5
Q1
C15
C16
C10
C11
C12
C13
C14
R16
R15
IC6
R22
C17
C19
R20
R26
C21
R40
C25
D2 D1
S2
S1
R42
LED2
D10D11
D17
D18
D19
J1 J2
R1
C31
R2
R25
R3
C30
IC9
R4
R5
SV1
X1
F1
PE
R6
R12 LED3
R13 LED4
R18 LED5
R19 LED6
C4
OK2
R10
C7
C6
IC3
A
B
H
I
G F E D C
Installation
Overview of Electrical Connections
8
6204788 - 02
Versatronik 503 NR2/Analog Bridge
Setting the Rotary Switch
The rotary dial sets the LON participant address of the
device.
Position 1-8: Boiler LON participant address. The
Vitotronic Cascade control will recognize this boiler
as this address.
Note:
You must power cycle the device after an address
change.
Position 0: Test mode, this mode is used for factory
testing, the unit will not function as intended when
left in this position.
Position 9: Autobinding reset is used to change LON
participant # without power cycle. Or breaking
a tool binding configuration (this is not used in a
typical application).
Position LON Participant Number
0 Do not use
1 Boiler Address 1
2 Boiler Address 2
3 Boiler Address 3
4 Boiler Address 4
5 Boiler Address 5
6 Boiler Address 6
7 Boiler Address 7
8 Boiler Address 8
9 Autobinding reset
Adjust dial switch to position 9
Wait 10s
Press and hold service button for 2s
Wait 10s
Adjust dial switch to desired boiler #
New address is set after another 10s
LON 1
LON 2
1212
H
LN1
R41
R17
1212
1 5
1234567
ON
12
3 4
1 2 345 6 7
C8
C9
IC4
R14
IC5
Q1
C15
C16
C10
C11
C12
C13
C14
R16
R15
IC6
R22
C17
C19
R20
R26
C21
R40
C25
D2 D1
S2
S1
R42
LED2
D10D11
D17
D18
D19
J1 J2
R1
C31
R2
R25
R3
C30
IC9
R4
R5
SV1
X1
F1
PE
R6
R12 LED3
R13 LED4
R18 LED5
R19 LED6
C4
OK2
R10
C7
C6
IC3
S1
Connections
Setting the Rotary Switch S1
9
6204788 - 02
Versatronik 503 NR2/Analog Bridge
LON 1
LON 2
1212
H
LN1
R41
R17
1212
1 5
1234567
ON
12
3 4
1 2 345 6 7
C8
C9
IC4
R14
IC5
Q1
C15
C16
C10
C11
C12
C13
C14
R16
R15
IC6
R22
C17
C19
R20
R26
C21
R40
C25
D2 D1
S2
S1
R42
LED2
D10D11
D17
D18
D19
J1 J2
R1
C31
R2
R25
R3
C30
IC9
R4
R5
SV1
X1
F1
PE
R6
R12 LED3
R13 LED4
R18 LED5
R19 LED6
C4
OK2
R10
C7
C6
IC3
1234567
ON
1 2 345 6 7
S2
J1
Setting the Dip Switches
The DIP Switch settings are used to configure device
options and target boiler maximum power output.
DIP switches 1-6 are used for selecting the power
input of the connected boiler.
The calculation for power (in kW) is the binary value
squared, then divided by 5.
P = (x^2)/5
See table 1 below.
DIP switch #7 is used in case there is no 0-10V
feedback (Feedback disabled) In this case the
Versatronik 503 cannot provide accurate feedback
information to the cascade.
Position ON OFF
DIP 7 0-10V feedback
Disabled
0-10V feedback
Enabled
Boiler Input
MBH (kW)
Boiler
Model
Switch Setting
1 2 3 4 5 6
0 (0) OFF OFF OFF OFF OFF OFF
0.6 (0.2) ON OFF OFF OFF OFF OFF
2.7 (0.8) OFF ON OFF OFF OFF OFF
6.1 (1.8) ON ON OFF OFF OFF OFF
10.9 (3.2) OFF OFF ON OFF OFF OFF
17.0 (5.0) ON OFF ON OFF OFF OFF
24.6 (7.2) OFF ON ON OFF OFF OFF
33.4 (9.8) ON ON ON OFF OFF OFF
43.6 (12.8) OFF OFF OFF ON OFF OFF
55.3 (16.2) ON OFF OFF ON OFF OFF
68.2 (20.0) OFF ON OFF ON OFF OFF
82.6 (24.2) B2HE 85 ON ON OFF ON OFF OFF
98.3 (28.8) OFF OFF ON ON OFF OFF
115.3 (33.8) B2HE 120 ON OFF ON ON OFF OFF
133.8 (39.2) B2HE 150 OFF ON ON ON OFF OFF
153.8 (45.1) ON ON ON ON OFF OFF
174.7 (51.2) OFF OFF OFF OFF ON OFF
197.2 (57.8) B2HE 199 ON OFF OFF OFF ON OFF
221.1 (64.8) OFF ON OFF OFF ON OFF
246.4 (72.2) ON ON OFF OFF ON OFF
273.0 (80.0) OFF OFF ON OFF ON OFF
Connections
Setting the DIP Switches S2
10
6204788 - 02
Versatronik 503 NR2/Analog Bridge
Boiler Input MBH (kW) Boiler Model Switch Setting
1 2 3 4 5 6
301.0 (88.2) ON OFF ON OFF ON OFF
330.3 (96.8) OFF ON ON OFF ON OFF
361.0 (105.8) ON ON ON OFF ON OFF
393.1 (115.2) CI2 399 OFF OFF OFF ON ON OFF
426.5 (125.0) ON OFF OFF ON ON OFF
461.3 (135.2) OFF ON OFF ON ON OFF
497.5 (145.8) CI2 500 ON ON OFF ON ON OFF
535.0 (156.8) OFF OFF ON ON ON OFF
573.9 (168.2) ON OFF ON ON ON OFF
614.2 (180.0) OFF ON ON ON ON OFF
655.8 (192.2) ON ON ON ON ON OFF
698.8 (204.8) OFF OFF OFF OFF ON ON
743.2 (217.8) CI2 750 ON OFF OFF OFF OFF ON
788.9 (231.2) OFF ON OFF OFF OFF ON
836.0 (245.0) ON ON OFF OFF OFF ON
884.4 (259.2) OFF OFF ON OFF OFF ON
934.2 (273.8) ON OFF ON OFF OFF ON
985.4 (288.8) CI2 1000 OFF ON ON OFF OFF ON
1037.8 (304.1) ON ON ON OFF OFF ON
1091.9 (320.0) OFF OFF OFF ON OFF ON
1147.1 (336.2) ON OFF OFF ON OFF ON
1203.8 (352.8) OFF ON OFF ON OFF ON
1261.8 (369.8) ON ON OFF ON OFF ON
1321.2 (387.2) OFF OFF ON ON OFF ON
1381.9 (405.0) ON OFF ON ON OFF ON
1444.0 (423.2) CI2 1500 OFF ON ON ON OFF ON
1507.5 (441.8) ON ON ON ON OFF ON
1572.3 (460.8) OFF OFF OFF OFF OFF ON
1638.5 (480.2) ON OFF OFF OFF ON ON
1706.1 (500.0) OFF ON OFF OFF ON ON
1775.0 (520.2) ON ON OFF OFF ON ON
1845.3 (540.8) OFF OFF ON OFF ON ON
1917.0 (561.8) ON OFF ON OFF ON ON
1990.0 (583.2) CI2 2000 OFF ON ON OFF ON ON
2064.3 (605.0) ON ON ON OFF ON ON
2140.1 (627.2) OFF OFF OFF ON ON ON
2217.2 (649.8) ON OFF OFF ON ON ON
2295.7 (672.8) OFF ON OFF ON ON ON
2375.5 (696.2) ON ON OFF ON ON ON
2456.7 (720.0) OFF OFF ON ON ON ON
2539.3 (744.2) ON OFF ON ON ON ON
2623.3 (768.8) OFF ON ON ON ON ON
2708.6 (793.8) ON ON ON ON ON ON
Connections
Setting the DIP Switches S2
11
6204788 - 02
Versatronik 503 NR2/Analog Bridge
A
B
CD E
Terminal
Designation
Boiler Terminal Description
Blr Sts 0-10V Out Boiler Modulation
Feedback
Blr Temp N/A Boiler Temp
Sensor (10K)
Fault 66 (S and P) Boiler Fault Status
Blr Cmd 0-10V In (0-
100°C)
Boiler Setpoint
Demand Signal
Setting the Rotary Switch
The Versatronik 503 requires three analog
connections to be made to the boiler control board.
As well as a 10K boiler temp sensor (provided)
Legend
A Boiler MZIO
B Verstaronik 503
C NTC 10K Sensor (Supplied)
D LON Connection 2
E LON Connection 1
Connections
Boiler Connections
12
6204788 - 02
Versatronik 503 NR2/Analog Bridge
Setting the Rotary Switch
The Versatronik 503 is wired into a Vitotronic NR2
LON daisy chain. There are two RJ45 (8P8C) jacks
for this connection.
They are electrically connected internally, it does
not matter in which order they are connected. If
only one connection is required (end of bus) insert a
LON end resistor into the other port (not provided)
Consideration when using Vitogate 300
The Vitogate 300 will not recognise the Versatronik
503. It can therefore not directly communicate with
the target boiler. However, there are a few data
points that can be learned from the cascade control.
For example, in the case of a GW6B lead control.
The following useful points can be learned about
boiler 3 (via the Versatronik 503)
AI:1085 - 1.1 (Boiler 3) Boiler output - value
AI:1050 - 1.1 (Boiler 3) Boiler water temperature
AI:1059 - 1.1 (Boiler 3) Set boiler water
temperature
MI:1033 - 1.1 (Boiler 3) Boiler fault
MI:1013 - 1.1 (Boiler 3) Operating mode
Connections
LON Connections
13
6204788 - 02
Versatronik 503 NR2/Analog Bridge
Direct power supply
The Versatronik 503 comes complete with a 6 ft. (2
m) power cord with convenience plug for simplified
installation.
1 WARNING
Incorrectly executed electrical installations can result
in injuries from electrical current and in equipment
damage.
Connect the power supply and implement all
grounding measures (e.g. RCD circuit) in accordance
with the following regulations:
HIn Canada all electrical wiring is to be done in
accordance with the latest edition of CSA C22.1
Part 1 and/or local codes. In the U.S. use the
National Electrical Code ANSI/NFPA 70. The
heating contractor must also comply with both
the Standard for Controls and Safety Devices for
Automatically Fired Boilers, ANSI/ASME CSD-1,
and the Installation Code for Hydronic Heating
Systems, CSA B214-01, where required by the
authority having jurisdiction.
HConnection requirements specified by your local
power supply utility
HProtect the power cable with max. 15A
Connections
Power Supply
1 WARNING
The absence of component grounding in the system
can lead to serious injury from electrical current if
an electrical fault occurs. Connect the appliance and
pipework to the equipotential bonding of the building
in question.
1 WARNING
Incorrect core allocation can result in serious injury
and damage to the appliance.
Never interchange cores “L” and “N”.
1 WARNING
An incorrect phase sequence can cause damage
to the appliance. Check for phase equality with
the power supply connection of the control unit.
1 WARNING
When extending wire there is the possibility of
exposure to electromagnetic interference. Avoid
running wires beside or near high voltage 120/240
VAC conductors. If proximity to high voltage
conductors cannot be avoided, use stranded,
twisted pair of shield design wire. Ensure that only
one end of the shielding is grounded.
14
6204788 - 02
Versatronik 503 NR2/Analog Bridge
Application Boiler Configuration Settings
Operating Mode Not weather compensated
without room temperature
controller
Heating Circuit
1-4
Not available
DHW Not available
Low Loss Header/
Buffer Tank
Not available
Heating Zone 1-3 Not available
Function Plug 96 “No Function”
This is preferred so that only
the Versatronik 503 controls
the appliance. However other
options will work as well.
Setting the Rotary Switch
It is recommended that the E-series appliance
should be commissioned as a standalone unit with
no zones, heating circuits, DHW, or outdoor reset
enabled.
This can be configured during the Commissioning
process.
Note:
Basic configuration required for Versatronik 503
compatibility. The installation manual / startup
procedure for the boiler should still be followed
VDD 1706
Description Function Selection MZIO
Value 06
Description Fault Message Output and
Temperature Demand
Setting the Rotary Switch
The heating appliance should also be configured
with 0-10VDC setpoint controls, and fault output
(VDD 1706) This is done using the following steps:
Service -> Service Functions -> Boiler -> 1706.0
Configuring the Boilers
Configuration
15
6204788 - 02
Versatronik 503 NR2/Analog Bridge
Rated voltage 120VAC
Rated frequency 60 Hz
Rated current 63 mA
Power consumption 22 mA
Permissible ambient
temperature
HOperation 32 to 104°F
(0 to +40°C)
HStorage and transport -4 to 149°F
(–20°C to +65°C)
Specifications
Specifications
16
6204788 - 02
Versatronik 503 NR2/Analog Bridge
Function ON OFF BLINK
LED1 Power Power Supply is
Functioning
No Power Not Applicable
LED2 Service PIN LED may flash during
participant check from
the cascade
LED3 LON Communication
Status
Not Applicable No Communication 1/second indicates
communication with
the cascade is active
LED4 Cascade Demand Setpoint requested
from Cascade
Standby requested
from Cascade
Not Applicable
LED5 Boiler Fault Boiler Fault Output is
active
Boiler Fault is inactive 1/second temperature
sensor is missing
4/second LON module
communication fault
LED6 Boiler Status Boiler Status 100%
(10VDC)
Boiler Status is 0%
(0VDC)
Flashes faster as
modulation increases
(0-9.8VDC)
LED Indication
It is recommended that the E-series appliance should
be There are six LEDs on the PCB that can be used
for information feedback and troubleshooting.
LON 1
LON 2
1212
H
LN1
R41
R17
1212
1 5
1234567
ON
12
3 4
1 2 345 6 7
C8
C9
IC4
R14
IC5
Q1
C15
C16
C10
C11
C12
C13
C14
R16
R15
IC6
R22
C17
C19
R20
R26
C21
R40
C25
D2 D1
S2
S1
R42
LED2
D10D11
D17
D18
D19
J1 J2
R1
C31
R2
R25
R3
C30
IC9
R4
R5
SV1
X1
F1
PE
R6
R12 LED3
R13 LED4
R18 LED5
R19 LED6
C4
OK2
R10
C7
C6
IC3
LED3
LED4
LED5
LED6
LED2
Troubleshooting
Troubleshooting
17
6204788 - 02
Versatronik 503 NR2/Analog Bridge
18
6204788 - 02
Versatronik 503 NR2/Analog Bridge
19
6204788 - 02
Versatronik 503 NR2/Analog Bridge
6204788 - 02
Versatronik 503 NR2/Analog Bridge
Technical information subject to change without notice. Printed on environmentally friendly
(recycled and recyclable) paper.
F
Viessmann Manufacturing Company (U.S.) Inc.
45 Access Road
Warwick, Rhode Island · 02886 · USA
TechInfo Line 1-888-484-8643
1-800-288-0667 · Fax (401) 732-0590
www.viessmann-us.com · [email protected]
Viessmann Manufacturing Company Inc.
750 McMurray Road
Waterloo, Ontario · N2V 2G5 · Canada
TechInfo Line 1-888-484-8643
1-800-387-7373 · Fax (519) 885-0887
www.viessmann.ca · [email protected]
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20