10 DY
P. 1 / 2
EM-0826 Rev.5
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
COMPONENT IDENTIFICATION
n POWER SWITCH
Power supply can be turned off.
Right: ON, left: OFF
12
3
56
78
Power Switch*
ZERO
PWR
OFF ON
SPAN
*Only for option /S
INSTALLATION
Use Standard Rack (model: 10BXq).
TERMINAL CONNECTIONS
Connect the unit as in the diagram below or refer to the con-
nection diagram label on the unit side.
+
–
1
OUTPUT 1
7
8
+
–
OUTPUT 2
5
6
CONNECTOR
*1 output type has the output 1 connected to the
card-edge connector in parallel.
OUTPUT 2*
POWER
3
+
–
2
2-WIRE
TRANSMITTER
+
–
V
MONITOR
(1 – 5V DC)
+
–
BEFORE USE ....
Thank you for choosing M-System. Before use, check the
package you received as below.
If you have any problems or questions with the product,
please contact M-System's Sales Office or representatives.
n PACKAGE INCLUDES:
Signal conditioner ....................................................(1)
n MODEL NO.
Confirm that the model number described on the product is
exactly what you ordered.
n INSTRUCTION MANUAL
This manual describes necessary points of caution when you
use this product, installation, connection and basic mainte-
nance procedures.
POINTS OF CAUTION
n POWER INPUT RATINGS
• Power input ratings are specied by the model number
suffix code. Check the power input voltage for the unit on
the specification label.
24V DC ±10%, approx. 55mA with voltage output 1
approx. 80mA with current output 1
n GENERAL
• Before you remove the unit or mount it, turn off the power
supply and input signal for safety.
n ENVIRONMENT
• Indoor use
• When heavy dust or metal particles are present in the air,
install the unit inside proper housing and ventilate it.
• Do not install the unit where it is subjected to continuous
vibration. Do not apply physical impact to the unit.
• Environmental temperature must be within -5 to +55°C
(23 to 131°F) with relative humidity within 30 to 90% RH in
order to ensure adequate life span and operation.
n WIRING
• Do not install cables (power supply, input and output) close
to noise sources (relay drive cable, high frequency line, etc.).
• Do not bind these cables together with those in which noises
are present. Do not install them in the same duct.
n AND ....
• The unit is designed to function as soon as power is supplied,
however, a warm up for 10 minutes is required for satisfying
complete performance described in the data sheet.
CURRENT LOOP SUPPLY
(isolated)
MODEL
10DY
INSTRUCTION MANUAL
Zero Adj.
Span Adj.
Output 1
Body
Specifications
Connection Diagram
Label
(side)
Zero Adj.
Output 2*
Span Adj.
Terminal Cover
*Provided only when the second output is selected.