RTD TRANSMITTER
MODEL
RB/RBS
INSTRUCTION MANUAL
BEFORE USE ....
Thank you for choosing M-System. Before use, check the
contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System’s Sales Office or representatives.
PACKAGE INCLUDES:
Signal conditioner (body + base socket) .........................(1)
MODEL NO.
Confirm that the model number described on the product is
exactly what you ordered.
INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
POINTS OF CAUTION
WARNING
•RiskofElectricalShock:TheFrontCoveristobeOpened
Only by Qualified Service Personnel.
•BeforeYouRemovetheUnitfromitsBaseSocketorMount
it, Turn Off the Power Supply and Input Signal for Safety.
CONFORMITY WITH EU LVD DIRECTIVE OR UL
(CE/ULisunavailableforcertainmodelsufxoptions.)
•ThisequipmentissuitableforuseinaPollutionDegree2
environment and in Installation Category II.
Reinforcedinsulation(signalinputoroutputtopowerin-
put: 300V) andbasic insulation (signal input to output:
300V)aremaintained.(NoI/OisolationforRB).
Prior to installation, check that the insulation class of this
unit satisfies the system requirements.
•Altitudeupto2000meters.
•Theequipmentmustbemountedinsideapanel.
•The equipment mustbe installed such that appropriate
clearance and creepage distances are maintained to con-
formtoCE/ULrequirements.Failuretoobservethesere-
quirementsmayinvalidatetheCE/ULconformance.
CONFORMITY WITH EU EMC DIRECTIVE
•InsertnoiseltersforthesignalI/Oandthepowersource
connected to the unit. TDK Model ZCAT 3035-1330 or
equivalent is recommended.
•The actualinstallation environments such as panelcon-
figurations, connected devices, connected wires, may affect
the protection level of this unit when it is integrated in
apanelsystem.TheusermayhavetoreviewtheCEre-
quirements in regard to the whole system and employ ad-
ditionalprotectivemeasurestoensuretheCEconformity.
POWER INPUT RATING & OPERATIONAL RANGE
•Operationalrange&powerconsumption:Checkthepow-
er rating for the unit with the specifications.
ACratings:Rating±10%,50/60±2Hz,
approx.2VA(approx.3VAwithOption/E2)
DCratingsexcept110V:Rating±10%,approx.2W
(approx.3WwithOption/E2)
110VDCrating:85–150V,approx.2W
UNPLUGGING THE UNIT
•Beforeyouremovetheunitfromitsbasesocketormount
it, turn off the power supply and input signal for safety.
ENVIRONMENT
•Indooruse.
•Whenheavydustormetalparticlesarepresentintheair,
install the unit inside proper housing with sufficient ven-
tilation.
•Donotinstalltheunitwhereitissubjectedtocontinuous
vibration.Donotapplyphysicalimpacttotheunit.
•Environmentaltemperaturemust bewithin -5 to+60°C
(23to140°F)withrelativehumiditywithin30to90%RH
in order to ensure adequate life span and operation.
WIRING
•Do not install cables close to noise sources (relay drive
cable, high frequency line, etc.).
•Do not bind these cables together with those in which
noisesarepresent.Donotinstalltheminthesameduct.
AND ....
•Theunitisdesignedtofunctionassoonaspowerissup-
plied,however,awarmupfor10minutesisrequiredfor
satisfying complete performance described in the data
sheet.
COMPONENT IDENTIFICATION
Body Base Socket
Connection Diagram
Front Cover
LCD Meter
(optional)
Specifications
HOW TO OPEN THE FRONT COVER:
Position your finger on the hook at the top of the front cover
and pull.
The shape of base socket may be different
for some models.
RB/RBS
P.2/4
EM-1334 Rev.7
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
INSTALLATION
Detachtheyellowclampslocatedatthetopandbottomof
the unit for separating the body from the base socket.
DIN RAIL MOUNTING
Set the base socket such that its
DINrailadaptorisatthebottom.
Position the upper hook at the
rear side of base socket on the
DINrailandpushinthelower.
When removing the socket,
pushdowntheDINrailadap-
tor utilizing a screwdriver (–)
and pull.
WALL MOUNTING
Refertothedrawingsbelow.
FRONT PANEL CONFIGURATIONS
Span Adj.
Zero Adj.
Span Adj.
Zero Adj.
Loop Test Selector
To p
Middle
Bottom
: 0% fixed
: 100% fixed
: Cancel
(normal operating mode)
NEXT Key
ENTER Key
• Option /E
• Option /E2
Clamp
(top & bottom)
DIN Rail
35mm wide
Spring Loaded
DIN Rail Adaptor
Shape and size of the base socket
are slightly different with various
socket types.
TERMINAL CONNECTIONS
Connect the unit as in the diagram below or refer to the connection diagram on the top of the unit.
DIMENSIONS mm (inch)
3456
2187
80 (3.15)
50 (1.97) 107 (4.21)
127 (5) [3.3 (.13)]
80 (3.15)
20
(.79)
40 (1.57)
50 (1.97)
7.8 (.31)
CLAMP
(top & bottom)
DIN RAIL
35mm wide
2–4.5 (.18) dia.
MTG HOLE
15 (.59) deep
8–M3.5
SCREW
• When mounting, no extra space is needed between units.
CONNECTION DIAGRAM
+
OUTPUT
1
2
U(+)
V(–)
POWER
7
8
3
4
A
B
B
RTD
5
RB/RBS
P.3/4
EM-1334 Rev.7
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
DISPLAY SETTING PROCEDURE Option /E2
Value
Unit, Item
ENTER Key
NEXT Key
Backlight : Green (normal)
Red (simulated output)
Normal Operating
Mode
Display Configuration
Mode
ITEM : ‘CFG’
Select engineering
unit
ITEM : ‘UNIT’
NEXT
NEXT
NEXT
ENTER
Press NEXT one
or more times.
ENTER
Select decimal point
position
ITEM : ‘DOT P’
NEXT
Press NEXT one
or more times.
ENTER
Calibration Mode
Adjust the display 0% &
100% values
ITEM : ‘CAL
Set the present input value as 0%.
Display shows AD conversion value*
1
.
ITEM : ‘A DJ Z’
NEXT
ENTER
Press NEXT to read and show
the present input value
(AD conversion value)
Press NEXT to read and show
the present input value
(AD conversion value)
ENTER
Set the present input value as 100%.
Display shows AD conversion value*
1
.
ITEM : ‘A DJ S’
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
Select 0%
scaling value
ITEM : ‘SCL Z’
NEXT
Numeric Input
Mode
Exit
ENTER
Select 100%
scaling value
ITEM : ‘SCL S’
Numeric Input
Mode
Exit
ENTER
NEXT
NEXT NEXT
Display Initialization
Mode
ITEM : ‘INIT’
ITEM : ‘NO’
Exit Numeric
Input Mode
NEXT
ENTER
Press ENTER to reset
the display
configuration to the
initial state.
ITEM : ‘YES’
Press NEXT to
choose among
‘0’ –> ‘1’ –> ‘-0’ –>
‘-1’ –> ‘0’ ....
Most Significant Digit
(upper line)
Press NEXT to
choose among ‘0’
through ‘9.
Press ENTER to
move to the next
LS digit.
Less Significant Digits
(upper line)
NEXT
NEXT
The range is set to
10 000 or -10 000
and the numeric
input mode ends.
Select ‘1’ or ‘-1’
Select
‘0’ or ‘-0’
Numeric Input Mode
Press ENTER key in maintaining NEXT key
pressed to return to Normal Operating Mode
from any setting mode.
Selectable among %, µV, mV, V, mA, A,
°C, °F, Ω, DEG K, mHz, Hz, kHz, VAC, AAC,
mg, g, kg, t, rpm, rps and no engineering unit.
(Factory setting: %)
Selectable between 10
-1
10
-4
and no decimal point.
(Factory setting: 10
-2
)
Selectable within the range -10 000 to +10 000.
(Factory setting: 0000)
Selectable within the range -10 000 to +10 000.
(Factory setting: 10 000)
Apply the input signal for 0%.
Apply the input signal for 100%.
(Value Set)
(Value Set)
AD conversion valuemeans the internal digital data representing
the input signal, which is computed to a percentage.
It is not a % or engineering unit value.
*1.
RB/RBS
P. 4 / 4
EM-1334 Rev.7
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
SIMPLE LOOP TEST OUTPUT Option /E2
Simulated0%and100%outputisavailablewithOption/E2.
SwitchtheLoopTestSelectorpositions.
Topposition: 0%xed
Middleposition:100%xed
Bottomposition:Cancelthelooptestmode
(Back to the normal operating mode)
CHECKING
1) Terminalwiring:Checkthatallcablesarecorrectlycon-
nected according to the connection diagram.
2) Powerinputvoltage:Checkvoltageacrosstheterminal
7–8withamultimeter.
3) Input: Check voltage across the terminal 3 – 4 with a
sensitive voltmeter.
(With20°Cor68°F,approx.220mVwithPt100,approx.
110mVwithPt50Ω.)
IfRTDwiresarebroken,theoutputgoesover100%(be-
low0% withdownscale protection)due to burnoutpro-
tection function. Check leadwires in such a case.
4) Output: Check that the load resistance meets the de-
scribed specifications.
ADJUSTMENT PROCEDURE
This unit is calibrated at the factory to meet the ordered
specifications, therefore you usually do not need any cali-
bration.
Theoutputsignalcanbenelyadjustedtomatchittoare-
ceiving instrument, or to compensate input wire resistance
whentheunitiscombinedwithazenorbarrier.Followthe
regularcalibrationprocedureexplainedbelow:
HOW TO CALIBRATE THE OUTPUT SIGNAL
Useasignalsourceandmeasuringinstrumentsofsufcient
accuracy level. Turn the power supply on and warm up for
morethan10minutes.
1) ZERO:Apply0%inputandadjustoutputto0%.
2) SPAN:Apply100%inputandadjustoutputto100%.
3) CheckZEROadjustmentagainwith0%input.
4) When ZERO value is changed, repeat the above proce-
dure1)–3).
MAINTENANCE
Regularcalibrationprocedureisexplainedbelow:
CALIBRATION
Warmuptheunitforatleast10minutes.Apply0%,25%,
50%, 75%and 100%input signal. Check thatthe output
signal for the respective input signal remains within the
range of accuracy described in the datasheet.When the
output is out of tolerance, recalibrate the unit according to
theADJUSTMENTPROCEDURE”explainedearlier.
LIGHTNING SURGE PROTECTION
In order to protect the unit from lightning surges entering
through signal and power supply cables, use of appropriate
lightning surge protectors are recommended. Please con-
tact M-System.