Danfoss RET230 HCW1 Installation guide

Type
Installation guide
RET 230 HCW-1
GB
F
D
ES
DK
NL
GR
LT
PL
I
Installation Instructions
User Instructions
Instructions d’installation
Instructions d’utilisateur
Anweisungen für Installati
Benutzeranweisen
Instrucciones de instalación
Instrucciones del usuario
Instruktions vejledning
Brugervejleding
Electronic Heat / Cool thermostat with
auto-changeover based on water temperature
Installatie handleiding
Instructiesevoor Gebruik
Ïäçãßåò åãêáôÜóôáóçò
Ïäçãßåò ÷ñÞóçò
Instrukcja instalacji
Instrukcja Użytkownika
Montavimo instrukcijos
Informacija Vartotojui
Istruzioni per l’uso
Istruzioni per l’utente
2
Index
INDEX
Installation Instructions 3-9
User Instructions 10
Instructions d’installation 11-17
Instructions d’utilisateur 18
Anweisungen für Installati 19-25
Benutzeranweisen 26
Instrucciones de instalación 27-33
Instrucciones del usuario 34
Instruktions vejledning 35-41
Brugervejleding 42
Installatie handleiding 43-49
Instructiesevoor Gebruik 50
Ïäçãßåò åãêáôÜóôáóçò 51-57
Ïäçãßåò ÷ñÞóçò 58
Instrukcja instalacji 59-65
Instrukcja Użytkownika 66
Montavimo instrukcijos 67-73
Informacija Vartotojui 74
Istruzioni per l’uso 75-81
Istruzioni per l’utente 82
F
D
ES
DK
NL
GR
PL
LT
I
3
Please note
This product should only be installed by a
suitably qualied electrician or heating installer.
The installation must comply with local Building
Regulations and wiring Regulations, including any
competent person requirements that may exist
Installation
Instructions
GB
GB - Installation Instructions
Thermostat features
Temperature range, heating 5-30°C
Water changeover temp
- Cool to Heat
- Heat to Cool
> 30°C
< 16°C
Thermostat off/auto & fan on
selector
l
Power supply 230 Vac ± 15%, 50/60Hz
Relay outputs, heat/cool & fan 2 x SPST, 3(1)A, 10-230 Vac,
Type 1B
Dimensions (mm) 110 wide x 90 high x 40 high
Design standard EN60730-2-9
Rated impulse voltage 2.5Kv
Ball hardness test 75°C
Control pollution situation Degree 2
Temperature accuracy ±1°C
Specication
4
GB - Installation Instructions
Product overview
The thermostat is designed for use in systems equipped
with fan coils served by a 2-pipe central changeover system.
The thermostat controls the operation of a motorized valve
which, during heating periods, opens when heat is required
and which, during cooling periods, opens when cooling is
required.
The changeover from heating to cooling is achieved
automatically by measuring the temperature of the ow
pipe. If the ow temperature exceeds 30°C the thermostat
operates as a heating thermostat, if the ow temperature
is less than 16°C the thermostat operates as a cooling
thermostat
Important note: It is essential that the circuit in which
the pipe sensor is located is not closed off and that water
circulates past the sensor at all times. This may require
the tting of a bypass valve between system ow and
return at the end of each circuit.
Installation
o First remove the wallplate from the back of the unit.
o Ensure that there is a minimum of 50mm above the
unit and 100mm below the unit in order to mount the
plug-in module.
!
5
o Fix at a height of approximately 1.5m from the oor,
away from draughts or heat sources such a fan-coil
outlets, sunlight or ofce equipment.
Pipe sensor location
o Fix the pipe sensor to the ow pipe using the clamping
band supplied.
Important note: It is essential that the circuit in which
the pipe sensor is located is not closed off and that
water circulates past the sensor at all times when the
system is in operation. This may require the tting of a
bypass valve between system ow and return to ensure
circulation past the sensor.
!
BYPASS
PS1
PS1
BYPASS
PS1
PS1
GB - Installation Instructions
6
Wiring
2-pipe fan coil application
GB - Installation Instructions
X
SEN
X SEN
N
L
FAN
1
COM
O/P
1 SPEED
FAN
ELECTRONICS
OUTPUT
COMMON IN
(LIVE IN)
PS1 PIPE
SENSOR
230 VAC
FIXED 3A
N
Note:
If HEAT/COOL/FAN outputs are 230V, link terminals L-COM
7
GB - Installation Instructions
Commissioning
Prior to re-tting the thermostat to the wallplate, the DIL
switches on the rear of the unit must be set to the desired
setting.
DIL Switch options, shown in factory set position
(all switches in On position)
ON
ON/OFF
CHRONO
˚C
˚F
Sw On
4
3
2
1
CHRONO 3CHRONO 6
8
DIL Switch descriptions
Switch 4: If set to On/Off, both heating and cooling operates
in on/off mode. If set to Chrono, both heating and
cooling operates in chrono-proportional mode.
Switch 3: Active only if switch 4 is set to Chrono. This
switch determines the number of cycles per hour
that the thermostat will impose on the system,
the options are three 20 minute cycles or six 10
minute cycles.
Switch 2: Allows Celsius or Fahrenheit temperature scaling
to be selected.
Switch 1: Not used in this model.
GB - Installation Instructions
9
GB - Installation Instructions
Mounting thermostat to the wallplate
o To mount the thermostat to the wallplate, align the
tabs on the top of the thermostat with the apertures in
the wallplate and hinge the thermostat down, pressing
rmly to engage the securing clip in the wallplate.
Locking & limiting
o To lock or limit the setting range turn the setting dial to 3
and remove knob.
o Position the locking springs on the rear of the dial to the
desired position and re-mount the knob ensuring that
number 3 on the dial aligns with the reference mark
on the case.
10
Fan runs continuously
Fan runs with heat or
cool demand
Thermostat off
LED lit green when
thermostat is powered
LED lit orange when
fan running
LCD display shows actual room temperature unless knob is moved at which time a
ashing set temperature is momentarily displayed. During heating demand a ame
symbol is lit, during cooling demand a snowake symbol is lit
LED lit green during
heating or cooling demand
Temperature setting dial,
read setting off LCD display
Note: Should it be necessary to reset the microprocessor for any reason, a reset button is located beneath the setting dial. Use
a non-metallic point, for example a matchstick, to depress the recessed button.
GB - User Instructions
RESET
button
www.danfoss.com/BusinessAreas/Heating
Part No 39053 Issue 04 05/06 SW REV 2.1
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84

Danfoss RET230 HCW1 Installation guide

Type
Installation guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI