FM-200

Kidde Fire Systems FM-200 User manual

  • Hello! I am an AI chatbot trained to assist you with the Kidde Fire Systems FM-200 User manual. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
  • What is the maximum electrical load that the switch can handle?
    How many poles and throws does the switch have?
    What is the pressure inlet size?
    What is the maximum allowable system pressure?
    What are the recommended mounting orientations for the switch?
A UTC Fire & Security Company
This literature is provided for informational purposes only. KIDDE-FENWAL, INC. assumes
no responsibility for the product’s suitability for a particular application. The product must be
properly applied to work correctly.
If you need more information on this product, or if you have a particular problem or question,
contact KIDDE-FENWAL, INC., Ashland, MA 01721. Telephone: (508) 881-2000.
Kidde Fire Systems
A UTC Fire & Security Company
400 Main Street
Ashland, MA 01721
Ph: 508.881.2000
Fax: 508.881.8920
www.kiddefiresystems.com
K-90-5180 Rev AC © 2010 Kidde-Fenwal Inc. Printed in USA
Effective: September 2010
K-90-5180
FM-200
®
Component Description
Pressure Operated Switch
FEATURES
For Use with UL Listed, ULC Listed and
FM Approved Systems
See Kidde
®
Manual 90-FM200M-021 for
USCG Approval
P/N: 81-486536-000
OPERATED
SET
4.00"
WIRING
SCREW
TERMINALS
4.00"
SET
OPERATED
PRESSURE OPERATED SWITCH
3P.D.T.
U
L
TO RESET
PUSH STEM TO SET POSITION
15 AMP 125 VAC
10 AMP 250 VAC
3/4 HP 1-2-3 PH 125-480 VAC
8 COVER SCREWS
STEM SHOWN IN SET POSITION-
PULL UP ON STEM TO MANUALLY
OPERATE SWITCH
0.375"
1/2” SUPPLY PIPE WITH UNION
FRONT VIEW
FRONT VIEW
COVER REMOVED
SWITCH 3PDT
COVER
GASKET
BOX 3 EACH SIDE
1/2” CONDUIT
KNOCKOUTS
½” NPT FEMALE,
CONNECT TO SYSTEM
PIPING
SIDE SECTION
TO RESET
PUSH STEM TO SET POSITION
FM
15 AMP.— 125 V.AC 10 AMP.—250 V.AC
3/4HP—250 VAC
PT. NO. 486536
KIDDE-FENWAL, INC.
400 MAIN STREET
ASHLAND, MA 01721
WIRING DIAGRAM
SET
OPERATED
PRESSURE INLET
C
NC
NO
C
NC
NO
C
NC
NO
FM-200 is a registered trademark of the Great Lakes Chemical Corporation.
NOTES:
The switch may be mounted in any position; how-
ever, the preferred installation is upright, as shown.
Any load connection to the switch must not exceed
the switch rating, and shall utilize a suitable protec-
tion device (i.e., circuit breaker, fuse).
Contact Ratings (3 PDT):
15 Amp @125 Vac
10 Amp @ 250 Vac
3/4 HP @ 250 Vac
1, 2 or 3 Phase
/