Ochsner AQUA 54 Operating Instructions & Installation Instructions

Category
Heat pumps
Type
Operating Instructions & Installation Instructions

This manual is also suitable for

BA OCHSNER AQUA TERRA_EN_V01.1.docx Page 1 of 72
Operating Instructions/Installation Instructions
OCHSNER AQUA OCHSNER TERRA
Brine/Water Heat pump
Heating/Cooling/Hot Water
BA OCHSNER AQUA TERRA_EN_V01.1.docx Page 2 of 72
BA OCHSNER AQUA TERRA_EN_V01.1.docx Page 3 of 72
Contents
1 General .................................................... 4
1.1 Notes on the documentation .......................... 4
1.2 Safety instructions .......................................... 4
2 Description of the appliance ................... 5
2.1 Function ......................................................... 5
2.1.1 Refrigerant circuit ........................................... 5
2.2 Heat pump ...................................................... 5
2.2.1 Construction ................................................... 5
2.2.2 Compressor .................................................... 5
2.2.3 Housing .......................................................... 5
3 Installation .............................................. 6
3.1 Delivery .......................................................... 6
3.2 Transport ........................................................ 6
3.3 Tilting dimensions of indoor unit ..................... 6
3.4 Select the place of instillation ......................... 6
4 Electrical connection ............................... 7
4.1 Check list: ....................................................... 7
4.2 Guidelines ...................................................... 8
4.3 Details of power supply .................................. 8
4.4 Smart Grid ...................................................... 8
4.5 EVU signal contact ......................................... 9
4.6 Tariff without interruption ................................ 9
4.7 Switching off via tariff relay: ............................ 9
4.8 Off-peak tariff ................................................. 9
4.9 Sensor wiring ................................................. 9
4.10 Pumps, drives 230 VAC ............................... 10
4.11 Safety thermostat (STB) in heating circuit .... 10
4.12 Auxiliary heater hot water ............................. 10
4.13 Terra control panel ....................................... 11
5 Hydraulic connection: ........................... 12
5.1 Heating connection....................................... 12
5.2 Properties of the water ................................. 12
5.3 Pressure maintenance system ..................... 12
5.3.1 Cooling version ............................................ 12
5.3.2 Passive cooling version ................................ 13
5.4 Sizing fundamentals ..................................... 13
5.5 Heating system connection .......................... 14
5.5.1 Nominal flow rates in heating system ........... 14
5.5.2 Flow rate measurement heating system ....... 14
5.6 Setting the flow rate...................................... 14
5.7 Pump test ..................................................... 15
5.7.1 Reading flow rate ......................................... 15
5.8 Heat source water connection ...................... 16
5.8.1 Water quality ................................................ 16
5.8.2 Flow meter ground water .............................. 17
5.9 Heat source brine connection ....................... 18
5.10 Flow rate metering brine ............................... 18
5.10.1 Collection shaft ........................................ 18
6 Commissioning ...................................... 19
6.1 Before you switch on .................................... 19
6.2 Check list for commissioning ........................ 19
6.3 Required on-site personnel: ......................... 19
6.4 For the system installer ................................ 20
6.5 Commissioning OCHSNER .......................... 20
7 System operation .................................. 21
7.1 Menus: ......................................................... 21
7.2 Safety functions ............................................ 22
7.3 Appliance function ........................................ 22
7.3.1 Heating circuit .............................................. 22
7.3.2 Hot water ...................................................... 22
7.3.3 Anti-Legionella switching .............................. 22
7.4 System operation ......................................... 22
7.4.1 Running costs ............................................... 22
7.4.2 Flow temperatures ........................................ 22
7.5 Ventilation ..................................................... 22
7.6 Screed flooring drying ................................... 22
8 Maintenance ......................................... 23
8.1 Service work ................................................. 23
9 Trouble shooting .................................. 24
9.1 Error Codes OTE .......................................... 24
9.2 Procedure for malfunctions ........................... 26
9.3 Remedy small faults yourself ........................ 26
9.4 Repairing your heat pump ............................ 26
9.5 Customer Service ......................................... 27
9.6 Cleaning ....................................................... 27
10 Environment and recycling .................. 27
10.1 Disposing of the packaging .......................... 27
10.2 Decommissioning ......................................... 27
10.3 Disposal of the appliance ............................. 27
11 Warranty ............................................... 28
11.1 Working hours and travel costs. ................... 30
12 Annex .................................................... 31
12.1 Technical Data AQUA .................................. 31
12.2 Technical Data TERRA ................................ 33
12.3 Performance curves TERRA 40 C ................ 35
12.4 Performance curves TERRA 61 C ................ 35
12.5 Performance curves TERRA 76 C ................ 36
12.6 Performance curves AQUA 54 C .................. 36
12.7 Performance curves AQUA 83 C .................. 37
12.8 Performance curves AQUA 97 C .................. 37
12.9 Pump characteristics .................................... 38
12.10 Pump characteristic curves well pumps ........ 39
12.11 Dimensions sheet SP 14-4 ........................... 40
12.12 System diagram heat source water .............. 41
12.13 System diagram heat source brine ............... 42
12.14 Flow rates ..................................................... 43
12.15 Ground collector heat source brine............... 43
12.16 Electrical circuit diagrams ............................. 44
13 Disassembly, assembly panel .............. 48
13.1 Dismantling the top cover ............................. 49
13.2 Disassembly of the upper cladding parts ...... 50
13.3 Remove the back panel parts ....................... 52
13.4 Dismantling of the wooden parts .................. 54
13.5 Mounting the feet .......................................... 57
14 Declaration of Conformity .................... 58
15 ERP-Data .............................................. 62
15.1 ERP-Data AQUA .......................................... 62
15.2 ERP-Data TERRA ........................................ 65
16 Directory of Illustrations ..................... 68
16.1 Directory of Tables ....................................... 68
BA OCHSNER AQUA TERRA_EN_V01.1.docx Page 4 of 72
1 General
1.1 Notes on the documentation
The following pointers are a guideline for the com-
plete documentation
Please read your heat pump's operating instruc-
tions carefully from front to back. This will help
you to operate your heat pump better. This man-
ual is to be stored in the vicinity of the heat pump
and must be easily accessible. The precautionary
pointers below will be used in this document.
WARNING
Pointers which, if not heeded, can mean
danger to life and limb, and can also lead to
material damage. These pointers must
be heeded without fail.
ATTENTION
Pointers which, if not heeded, can lead to an
appliance malfunction and to material dam-
age. These pointers must be heeded
without fail.
NOTE
Attention
Pointers for work on electrical equip-
ment. These pointers must be heeded
without fail.
Attention - danger to life and limb
1.2 Safety instructions
Read this manual carefully before you begin to
commission/adjust the heat pump!
Converting or altering the appliance is not
allowed. Work on the appliance (repairs,
alterations) may only be carried out by
a
specialist authorised by the manufacturer.
All circuit breakers in the heating sys-
tem are to be turned off before any
work is carried out on terminal strips or
electrical connections (wiring).
The commissioning as well as the ser-
vicing of the appliances may only be
carried out by personnel which are au-
thorised by OCHSNER.
The installation of the appliances and
their electrical wiring may only be car-
ried out by a specialist according to lo-
cal regulations and codes of practice.
Protective functions for the heat pump
can be activated by the control. How-
ever, as the control is not certified as a
safety appliance, the protection against
failure or damage to the heat pump must be
adapted to the local instructions (for instance, by
additional external switching of the safety appli-
ances used.
BA OCHSNER AQUA TERRA_EN_V01.1.docx Page 5 of 72
2 Description of the appliance
2.1 Function
The heat pump converts low temperature heat
(e.g. heat from the ground) into heat of higher
temperatures (heating water). The heat pump ex-
tracts from the ambience the stored solar energy
and returns this, plus drive energy (electricity for
the compressor) in the form of heat to the heating
and hot water circuits. The system consists of sep-
arate circuits, which are coupled by means of a
heat exchanger.
Heat source system extraction of heat from
the environment
Heat pump refrigerant circuit.
Heat use circuit emission of heat to the
heating system.
2.1.1 Refrigerant circuit
The refrigerant circuit consists of:
plate heat exchanger as evaporator
compressor, mounted on a noise and vibration
dampening thick metal plate
plate heat exchanger as condenser
dryer, refrigerant sump, expansion valve,
safety equipment
chlorine-free, non-flammable safety refriger-
ant and bio-degradable special compressor oil
WQA Heat pump WNA
Fig. 1: Refrigerant circuit
WQA Heat source pump
WNA Heat use system
2.2 Heat pump
The heat pumps models AQUA and TERRA are
compact appliances for indoor installation.
The heat pump is suitable for
inside installation and NOT for outside
installation
The heat extraction (heat source circuit) takes
place, depending on the type) via its own brine cir-
cuit, for instance ground heat systems: from flat-
plate collectors, deep trench (Künette) collectors,
ground probes or a well as the heat source)
The heat pump of the AQUA and TERRA series
function usually in a monovalent heating opera-
tion. The heat pumps can, however, be combined
at any time with a further heat generator.
2.2.1 Construction
2.2.2 Compressor
The fully hermetic SCROLL compressors are spe-
cially designed for heat pump use, i.e. for the high-
est loading. Various important constructive
measures protect the compressor, both under
normal operative conditions as well as overload-
ing. The compressors used by OCHSNER have the
highest performance and are the most durable.
The SCROLL compressors have only a few moving
parts and have no dynamic suction or pressure
valves. Furthermore, they are distinguished by a
very low vibration and noise level.
2.2.3 Housing
A profile frame, corrosion protected and with
elegant cladding plates. The complete cladding is
fitted with noise-dampening mats. A special load-
bearing noise-reducing underlay is supplied with
the heat pump.
BA OCHSNER AQUA TERRA_EN_V01.1.docx Page 6 of 72
3 Installation
3.1 Delivery
The heat pump is delivered ready to install, i.e.
electrically pre-wired, on a one-way palette and
packed in foil. The cladding is packaged extra.
Report any transport damage immedi-
ately on receiving the heat pump!
3.2 Transport
The heat pump is to be stored and transported
packaged up. Careful transport at an angle up to
45° is permitted over short distances. Ambient
temperatures from 20°C to +45°C are permitted
both for transport and storage. The standard pack-
aging offers no weather or seawater protection.
Transport damage can only be recognised if this is
made known to the driver of the delivery vehicle
during, or immediately after unloading.
3.3 Tilting dimensions of indoor unit
The tilting dimension of the heat pump is 209cm:
Fig. 2: Titling dimension of the heat pump
3.4 Select the place of instillation
The heat pump TERRA can be installed in any dry
and frost free room. Installation must take place
on an even, horizontal surface.
Placement of the unit should be such that servic-
ing and maintenance are possible.
Fig. 3: Minimum clearances
The heat pump must be acoustically de-coupled
from the floor. Reverberant rooms can lead to in-
creased noise sensitivity A possible transfer of
noise to adjacent rooms cannot be ruled out and
should be considered when planning the system.
2090 mm
BA OCHSNER AQUA TERRA_EN_V01.1.docx Page 7 of 72
4 Electrical connection
Attention!
Before wiring up the unit make sure
that the heating system carries no line
voltage.
DANGER of electrocution
Install all electrical connections ac-
cording to national and local Standards
Connecting work may only be carried
out by a certified specialist according
to this instruction!
The values indicated for fuse protection are given
solely for reference. The correct sizing of the
safety measures is the sole responsibility of the
electrician connecting the heat pump. The choice
of cable size is to be made by the electrician tak-
ing into account the ratings and cable lengths.
4.1 Check list:
The stated voltage must be the same as the
house circuit voltage. Observe the specifica-
tions on the rating label!
The heat pump connection must have been
approved by the competent utility before it is
carried out.
The circuit breaker for the main power supply
circuit 230V/ 400VAC is to be a fuse that
switches off all poles in the event of a mal-
function.
Should a leakage current switch (FI) be used,
this must be sensitive to universal current.
The control circuit voltage 230VAC is to be
protected by a C13A circuit breaker.
The supply cable must be protected against
overload and short circuiting.
The regulations of the responsible energy
utility and the relevant EN-standards are to
be strictly adhered to.
BA OCHSNER AQUA TERRA_EN_V01.1.docx Page 8 of 72
4.2 Guidelines
Position
min. cross-
section
Connecting cables 230VAC
are always to be sized ac-
cording to on-site condi-
tions
1.5 mm².
Control cable 230VAC
Pumps, valve motors
min. 1.0 mm²
Sensor cables:
(outside sensors, etc.) are
sensitive to EMC and must
always be run separately
(min. 20 cm) from
230V/400V cables. If sepa-
ration is not possible,
sheathed cables are to be
used. The sheath connec-
tion to the heat pump is on
Terminal PE
max. cable length 50 m!
2x 1.0 mm²
Bus cables
eBus from OTE control to
room remote control,
auxiliary modules, between
units (when cascading).
These cables must always
be laid as sheathed cables.
The sheath connection to
the heat pump is on Termi-
nal PE OCHSNER recom-
mends the following con-
ventional cables: Y(ST)Y)
2x2x0.8
ATTENTION: always use a
twisted two-wire cable!
Example. eBUS =
SIGNAL/GND
Do not connect GND to the
sheath!
2x2x0,8 mm²
Table 1: Cable selection
4.3 Details of power supply
The voltage supplies 400V~ and 230V~ are to be
run separately according to the circuit diagram.
The following power supplies are necessary:
Fig. 4: Power supply
400VAC for the compressor
Utility (EVU) Signal contact *
230V control voltage (inside switching box)
The power supply 230VAC to the control is on the
terminal strip X3 in the distribution box on the
switching box (L N PE).
Should the minimum clearances be-
tween sensor wiring and 230V/400V
(100mm) not be able to be adhered to,
sheathed wiring is to be used.
The values indicated for fuse protection are given
solely for reference. The correct sizing of the
safety measures is the sole responsibility of the
electrician connecting the heat pump.
OCHNSER provides no guarantee in cases of sys-
tem damage occurring due to incorrectly sized
safety devices!
4.4 Smart Grid
Special descriptions for the Smart Grid are availa-
ble on request.
*EVU (Utility)
BA OCHSNER AQUA TERRA_EN_V01.1.docx Page 9 of 72
4.5 EVU signal contact
Attention!
230VAC control voltage is present on
the EVU contact!
Fig. 5: EVU signal contact
Remover the jumper and apply the wiring as
shown in the drawing If the EVU contact is inter-
rupted, the compressor and also, if applicable;
the auxiliary heater switch off.
4.6 Tariff without interruption
In the case of tariff switching without interrupted
power supply the heat pump will be temporarily
switched off by the utility. The control input EVU
on the inside unit is to be used for this. Terminal
strip X3 for activating the function, remove jumper
and connect cable.
4.7 Switching off via tariff relay:
For switching by means of a tariff relay (sealed by
the Utility on site) the power supply to the heat
pump compressor is switched off. In this case, the
EVU input is to be switched without fail via an
auxiliary contact on the tariff relay (NC contact).
(…otherwise ERROR)
4.8 Off-peak tariff
If the tariff switching takes place in the meter
(Off-peak Tariff), the EVU contact must not be ac-
tivated.
4.9 Sensor wiring
Do not place line voltage on the sensor
terminals! The control will otherwise
be destroyed.
The Type NTC5K temperature sensors of the OTE
control are supplied with 4.0m cable lengths.
Should these lengths not suffice, the cables can be
lengthened as required. Please use 2x 1.0mm²
flexible cable.
When installing the sensor cable, ensure that the
cables do not run parallel to alternate current
>230VAC cables.
Outside sensor TA
The outside sensor (TA) is to be mounted at ca. 2.5
m height on the outside wall of the building
(north-west side). It is to be ensured that the out-
side sensor is not directly affected by sun's radia-
tion or by wind, as this will adversely affect the
control behaviour. Do not place the sensor in the
direct vicinity of the evaporator either. Possible
danger of adverse influence on the control.
Mixing valve sensor TMK
If a mixing circuit is installed in addition to the di-
rect heating circuit, a mixing valve sensor must
also be installed. The mixing valve sensor is sup-
plied as a contact sensor with band clamp and con-
ductive paste. The mixing valve sensor is to be
mounted directly after the mixer pump. If multi-
layer or plastic pipework is being used, a suitable
metal bridge must be provided.
Hot water sensor TB
The hot water sensor is packed in the heat pump
on delivery. The sensor should be placed in the
bottom third of the tank, maximum in the middle.
Ochsner hot water tanks are fitted with corre-
sponding sleeves for the installation.
The current electro-magnetic compatibility regu-
lations are to be adhered to when installing the
wiring.
230V~
BA OCHSNER AQUA TERRA_EN_V01.1.docx Page 10 of 72
Buffer sensors (TPO, TPM)
If a hydraulic separating buffer is used, 2 sensors
must be installed in the buffer. Differing sensor
placements are to be considered for:
Heating buffer
Heating or cooling buffer and
Unifresh
The placement takes place as specified in the hy-
draulic plans.
4.10 Pumps, drives 230 VAC
Pumps, (heating circuit pumps, hot water charge
pumps) as well as drives (mixing valves, etc.) are
connected directly to the control.
A test-run may only be undertaken on a fully-pre-
pared system that is ready for commissioning! A
relay test can be carried out on the OTE control in
order to test the appropriate outputs (actuators).
4.11 Safety thermostat (STB) in heating
circuit
If a non-self-resetting safety thermostat (STB) is
installed on site, this STB is to be installed directly
in the power supply to the heating circuit pump
(not supplied).
4.12 Auxiliary heater hot water
A separate circuit breaker is to be provided in the
distribution box for the optional electrical auxiliary
heater in the hot water tank (Legionella protec-
tion). See El.-diagram in Annex. This function is op-
tional and thus not in the heat pump's scope of de-
livery.
BA OCHSNER AQUA TERRA_EN_V01.1.docx Page 11 of 72
4.13 Terra control panel
Fig. 6: Control panel wiring TERRA basic wiring
Sizing of the connecting cable cross sections
must be according to local regulations.
ATTENTION Danger to life
and limb! Switch off all system power
supplies before starting electrical work!
Power Supply
3x 380-400VAC
(compressor)
Power Supply
220-240VAC
(Control voltage)
Heating circuit
mixing valve
Open - close
Pin.15/16/N/PE
WQP and WEP
pump
Temperature sensor
TMK (Mixing circuit)
Pin.43/GND
Temperature sensor
TA (outside tempera-
ture) Pin.44/GND
Temperature sensor
TPM (buffer middle)
Pin4/GND
Temperature sensor
TPO (buffer top)
Pin.45/GND
Temperature sensor
TB (hot-water sensor)
Pin46/GND
OTE control with
Climate control
manager
Cascade manager
Heat manager
Heating circuit
pump 1
Pin.7/N/PE
Heating circuit
pump 2
Pin.8/N/PE
Auxiliary heater
hot water
Pin.10
Hot water
Active
Pin.13/14/N/PE
BA OCHSNER AQUA TERRA_EN_V01.1.docx Page 12 of 72
5 Hydraulic connection:
5.1 Heating connection
The water and pressure in the system is to be reg-
ularly monitored by the system operator and ad-
justed if the pressure is too high or too low. The
flow rates in the heat system are monitored by the
integrated flow sensor. Furthermore, the specified
system service intervals as well as the system
checks must be adhered to.
If, during larger reconstruction work or after burst
piping the majority of the water in the heating sys-
tem has to be drained off and refilled, this must be
carried out in the presence of the OCHSNER works
customer service / OCHSNER authorised partner
(see Logbook) If exceptional refilling work is to be
carried out (e.g. reconstruction work or after burst
piping), a current water test report is to be made
and, if necessary, using this report, additives must
be used when refilling the heating system.
5.2 Properties of the water
The VDI 2035 resp. ÖNORM H5195-1 and 2 are to
be observed with respect to the properties and
quantities of heating system water, incl. filling and
topping up water.
In order to prevent damage due to scaling, the
hardness of the water must be tested before filling
the heating system. The total hardness of the wa-
ter must be:
4.0…8.5° dH at a pH-value from 7 to 9
The water must be softened if this value is ex-
ceeded. Desalinated water or rainwater must not
be used as this leads to increased corrosion.
Please observe!
Unsuitable filling or topping up water
gives rise to sedimentation and corro-
sion and can lead to system damage.
5.3 Pressure maintenance system
The primary pressure in the expansion vessel must
be checked before filling the system. This must be
adjusted to the height of the building. Static
height: Difference between the highest and lowest
points of the system.
Bench-mark value:
Primary pressure = static pressure + 0.3 bar.
Max. permissible operating pressure: 2.6 bar. Se-
lect a safety valve of 3.0 bar.
See ENISO 4126-1:2013-10-15 Part 1: Safety valves
A sufficient sizing of the hydraulic
safety and pressure maintenance
equipment is necessary for the opera-
tional safety of the system. An annual
control according to the Standards
must take place.
The installation of the appliances may
only be carried out by a specialist ac-
cording to
local regulations and codes of practice.
All heat pump connections are to be
mounted in a flexible fashion. Avoid vi-
bration transmission bridges when in-
stalling pipework. The pipework sizing
as well as the choice of circulation
pump is dependent on the relevant
heating system.
5.3.1 Cooling version
All cooling system components (pipework, fittings)
must be insulated against condensed water using
suitable non-permeable insulation material. This is
to be taken into consideration even more for flow
pipework from the heat pump to the buffer tank.
BA OCHSNER AQUA TERRA_EN_V01.1.docx Page 13 of 72
5.3.2 Passive cooling version
In water/water heat pumps with passive
cooling applications,
it is essential that each cooling circuit has its
own mixing valve as well as
a room remote control to limit the dew point.
The diverting valve in the passive cooling
mode MUST be installed in the heat
pump's evaporator outlet. Corresponding
circuit diagrams are part of the scope of sup-
ply of every heat pump.
5.4 Sizing fundamentals
Please observe the following sizing fundamentals.
The flow rate in the pipe-network must not
exceed 0.8 m/s. (noise/resistance).
In order to ensure a comfortable and disturbance-
free operation, a temperature difference of 5K be-
tween the heating system flow and return is to be
maintained.
Fig. 7: Hydraulic heat pump connection
When sizing the heating system
pump/buffer charge pump, the internal
pressure differential of the heat pump
condenser is to be taken into consider-
ation (see technical data Pet seq)!
If this is not done, there is a danger that the heat
pump will not reach the specified catalogue rating
and under certain conditions will be shut off by
means of the high-pressure switch, ERROR re-
port (see operation instructions OTE).
Integrated heating system circulation pumps are
sized as buffer charge pumps (technical data see
annex).
It is recommended to install a decoupling tank
(separation tank, buffer tank) or a header tank
with the heat pump. A bleeder valve (manual
bleeding) must be fitted at the highest point in the
pipework system.
It must be ensured that no foreign bodies can en-
ter the pipework (dust, dirt, etc.). A filter sieve can
be mounted in the return pipework to the heat
pump in order to collect any dirt. Make sure that
the dirt collector is easy to clean for maintenance
purposes.
A clogged sieve affects the heat transfer consider-
ably and can lead to a switch off via the high-pres-
sure safety switch! Valves and thermometers are
to be fitted to the flow and return pipework so
that the water flow and the running condition of
the heat pump can be monitored at all times. A
drain pipe is to be installed at the lowest point in
the pipework so that the system can be drained.
The heating system pipework is to be sized ac-
cording to the technical data of the heat pump.
BA OCHSNER AQUA TERRA_EN_V01.1.docx Page 14 of 72
5.5 Heating system connection
5.5.1 Nominal flow rates in heating system
The nominal flow rates in the heating system are
to be ensured. Deviating flow rates can lead to a
heat pump safety switch off.
5.5.2 Flow rate measurement heating sys-
tem
The flow rate meter is part of the heat pump and
must be installed by the system installer according
to the OCHSNER installation guidelines. Please ob-
serve the instructions in the installation manual
for flow rate measuring meters.
If the flow rate meter is either not installed, or in-
correctly installed, OCHSNER will not undertake
the commissioning of the system.
OCHSNER accepts no liability for possible damage
which may occur if the flow rate meter is either
not installed, incorrectly installed, sized or wired
up.
Fig. 8: Flow rate measurement heating system
5.6 Setting the flow rate
The nominal flow rate (see /) is to be ensured in all
types of operation /hot water charging, heating,
cooling via a separate buffer tank etc.). The flow
rates are measured by the installed flow meter
and displayed on the OTE control. The flow rate is
adjusted by means of the adjustment screw on the
circulation pump supplied. For a hydraulic regula-
tion corresponding to the standards, especially by
combined heating rsp. heating/cooling operation
with hot water heating, appropriate pipe-run reg-
ulating valves are to be fitted and the system cali-
brated as required.
Fig. 9: Setting the flow rate of the EC pump
-c
Set the flow rate by
turning the red adjustment screw.
BA OCHSNER AQUA TERRA_EN_V01.1.docx Page 15 of 72
5.7 Pump test
Switch on the buffer charge pump / heat source pump via the relay test.
Fig. 10: Switch on heat generator pump
5.7.1 Reading flow rate
The measured flow rate is displayed; this must correspond to the nominal flow.
Fig. 11: Reading flow rate
HEAT PUMP
ESC
ENTER
OCHSNER OTE
MENU
Sa 25.06.2016
08:10
Switched off
5
Main menue
HEATING CIRCUIT 1
HEATING CIRCUIT 2
HOT WATER
HEAT PUMP
ESC
ENTER
1
HEAT PUMP
Operation mode
Operational data
ESC
ENTER
Settings
Relay test
01-076
Compressor
100
01-077
HEAT PUMP
01-022
Pump heat gener
20
Heat source pum
45
ESC
ENTER
20%
ESC
01-022
HEAT PUMP
Pump heat generator
ESC
01-077
HEAT PUMP
Heat source pump
/ fan
45%
HEAT PUMP
ESC
ENTER
OCHSNER OTE
MENU
Sa 25.06.2016
08:10
Switched off
5
Main menue
HEATING CIRCUIT 1
HEATING CIRCUIT 2
HOT WATER
HEAT PUMP
ESC
ENTER
1
HEAT PUMP
Operation mode
Operational data
Settings
Relais test
ESC
ENTER
HEAT PUMP
21-002
Flow rate heat
50
21-090
Flow rate heat
55
23-001
Thermal energy
ESC
ENTER
99
23-010
Thermal energy
12
21-002
HEAT PUMP
Flow rate heat sink
50.1 l/min
ESC
ESC
21-002
HEAT PUMP
Flow rate heat source
55.4 l/min
BA OCHSNER AQUA TERRA_EN_V01.1.docx Page 16 of 72
5.8 Heat source water connection
If ground water is to be used as heat carrier me-
dium, only clean drinking-quality water with no
clouding particles must be used. When using
ground water, a cleanable large surface filter with
a mesh size of 500 Microns is to be installed. For
increased safety, we recommend the use of our
centrifugal filter.
Before installing the system, a water
analysis, which gives information on the
water properties, must be carried out.
- The removal of water for analysis must
take place shortly before the end of a con-
tinuous pumping operation and immedi-
ately analysed (otherwise, incorrect water
values will be used for analysis). We fur-
thermore recommend an annual in testing
of the water quality.
- The flow rate in the pipe-network must
not exceed 0.8 m/s.
- In order to ensure a comfortable and dis-
turbance-free operation, a temperature
difference of 3K between the heating sys-
tem flow and return is to be maintained.
- The temperature range limits for the heat
source are between +8°C and +22°C
OCHSNER accepts no liability for the correctness
of the analyses resp. changes in water quality.
5.8.1 Water quality
Aggressive and coking materials can lead to corro-
sion and clogging of the evaporator, the feed
pump and the pipework (heat pump malfunction).
Adhere to the values in
ATTENTION:
A water analysis can only be a momen-
tary value. The values can fluctuate
considerably in the course of a year.
The evaluation of a meaningful use can, however,
only be carried out with the measured values!
Table 1: Water quality
Legend:
+ = the material has normally good resistance
- = not recommended for use
0 = corrosion can occur if several
factors are evaluated with 0
Notes:
1.) If these limiting values cannot be ensured, a
stainless steel soldered stainless steel heat ex-
changer must be installed in place of the cop-
per soldered stainless steel heat exchanger.
This information must be made know when or-
dering!
2.) Due to probable clogging, we do not recom-
mend installing a water/water heat pump.
3.) Besides iron and manganese, the chloride con-
centration is essentially decisive for the deploy-
ment of a stainless steel soldered heat ex-
changer.
Copper
braized
Stainless
steel
braized
1.)
 > 500 -- +
< 6 0 0
6 - 8 + +
> 8 -- 0
< 10 + +
 +
+
 0
+
> 200 --
-- 3.)
< 50 +
+
 0
+
> 100 --
0
< 5 +
+
 0
+
> 20 --
0
< 1 +
+
 0
+
> 8 --
+
< 2 +
+
 0
+
> 20 --
+
2.) [mg(l] > 0,2 - -- 3.)
2.) [mg(l] > 0,05 - -- 3.)
1.) [mg(l] < 5 + +
1.) [mg(l] < 0,5 + +
Iron with Manganese
Mangan - Manganese
Sulphide
Chlorine (free)
Oxygen
1.)
[mg/l]
Ammonium
1.)
[mg/l]
Chloride
1.)
[mg/l]
Sulphate
1.)
[mg/l]
Carbon dioxide (aggressive
free)
1.)
[mg/l]
Plate heat exchanger
Electric conductivity
pH-Value
1.)
BA OCHSNER AQUA TERRA_EN_V01.1.docx Page 17 of 72
5.8.2 Flow meter ground water
The flow rate meter is part of the heat pump and
must be installed by the system installer according
to the OCHSNER installation guidelines. Please ob-
serve the instructions in the installation manual
for flow rate measuring meters.
If the flow rate meter is either not installed, or in-
correctly installed, OCHSNER will not undertake
the commissioning of the system.
OCHSNER accepts no liability for possi-
ble damage which may occur if the flow
rate meter is either not installed, incor-
rectly installed, sized or wired up.
Fig. 12: Installation of flow rate sensor heat source ground waterand heating system
Fig. 13: Wall ducting
BA OCHSNER AQUA TERRA_EN_V01.1.docx Page 18 of 72
5.9 Heat source brine connection
The sizing and installation of the brine collector is
the responsibility of the installer and is to be car-
ried out according to OCHSNER guidelines. The
heat source connection is to be executed in such a
way that the brine circuit can be flushed and/or
bled at any time. The amount of heat carrier fluid
required is to be calculated beforehand. This is a
product of the pipework length and pipe dimen-
sion as well as the heat pump water content The
heat carrier fluid is to be poured into a clean con-
tainer in one pour and well stirred.
Ethylene glycol in a mixture of 25%-30% by volume
is to be used as anti-freeze, this providing protec-
tion down to 12 to 15°C.
The anti-freeze fluid must not be mixed with ag-
gressive raw water (pH-value below 7.0), distilled
water
or rain water.
NOTE:
As the protection against corrosion de-
creases in the course of time, a two-
yearly water quality check is recom-
mended
The frost protection, the pH-value, as well as the
rest alkalinity are to be checked. This check is to
be carried out with a representative quantity (for
instance. 3x 1/4l). The correct mix relationship is
to be tested with a refractometer. The filling is to
be carried out in such a way as to ensure the
proper bleeding of the system
In order to ensure a reliable operation,
a temperature difference of 3K
between the evaporator (heat source)
flow and return
is to be maintained.
The flow rate in the pipe-network must
not exceed 0.8 m/s. (noise/resistance).
5.10 Flow rate metering brine
The flow rate meter is part of the heat pump and
must be installed by the system installer according
to the OCHSNER installation guidelines. Please ob-
serve the instructions in the installation manual
for flow rate measuring meters. If the flow rate
meter is either not installed, or incorrectly in-
stalled, OCHSNER will not undertake the commis-
sioning of the system.
OCHSNER accepts no liability for possi-
ble damage which may occur if the flow
rate meter is either not installed, incor-
rectly installed, sized or wired up.
Fig. 14: Flow meter installation in heat source brine system
5.10.1 Collection shaft
If a collection shaft is to be installed, a
lined conduit with a slope towards the collecting
shaft
is to be used.
Fig. 15: Collection shaft
BA OCHSNER AQUA TERRA_EN_V01.1.docx Page 19 of 72
6 Commissioning
6.1 Before you switch on
The heat pump has no separate main switch. In
emergencies, the system must be switched off by
means of the specified circuit breakers. The circuit
breakers must be so reachable as to ensure a
switching off at any time.
Attention - danger to life and limb
The initial switching on of the electrical
systems may only take place in the pres-
ence of a suitably trained and certified electrician.
Switch the power supply to the system ON (or
OFF) only when:
Nobody can be endangered
All heat pump installation work is com-
plete
All wiring is completely connected
The voltages correspond to the documen-
tation
The hydraulic system is filled with water
and
the system has been completely bled
The power supply to the compressor may not be
switched on before the refrigerant circuit and the
hydraulics have been filled with the appropriate
medium.
Once all the above conditions have been met, the
control voltage 230V~ (F1 fuse) can be switched
on in order to check the individual functions.
Check carefully all sensors and their values for
plausibility and all hydraulic outlets for correct
function.
Attention:
Operating the heat pump with no, or
too little refrigerant leads to damage to
the appliance. Operating the circulation pumps
with no water in the system leads to destruction
of the pump.
Commissioning must be carried out by Ochsner
Customer Service or a service partner authorised
by Ochsner. The Ochsner commissioning guide-
lines must be adhered to. Operating the system
without a correct commissioning will lead to a for-
feiture of the guarantee and warranty rights.
6.2 Check list for commissioning
Adhere to the following sequence:
1. Check heating system circuit: System-
pressure, expansion vessel function,
bleeding valves, quantity adjustment.
The system installer is to ensure that, at
the start of
commissioning, the system tempera-
ture/buffer temperature does not exceed
30°C.
2. Check the flow rates! The flow rates at
heat source and heat use systems are
measured by the integrated flow sensors
and monitored. These can be read off
from the display of the OTE-control.
3. for brine/water heat pumps
4. System pressure, frost protection mix-
ture (-12°C), bleeding
5. Check whether all non-return valves are
open
6. Check power supplies and circuit break-
ers
7. Check the electrical connections to the
system components, including all re-
quired safety equipment, according to
the wiring diagram.
8. Switch on 3-phase supply to the heat
pump.
9. Control 3-phase supply and right-hand
rotary field
10. Switch on control voltage supply
11. Relay test on the output terminals
12. Adjust the system according to user re-
quirements and document these
13. Hand over system to operator
6.3 Required on-site personnel:
Electrician, installer and future system supervisor
MUST be present for the system orientation dur-
ing commissioning.
BA OCHSNER AQUA TERRA_EN_V01.1.docx Page 20 of 72
6.4 For the system installer
The OCHSNER Customer Service engineer / Cus-
tomer Service partner will execute the user-spe-
cific settings according to the specifications in the
system data sheet. Should the system installer not
be present during commissioning, or if there is no
fully completed system data sheet present, the
system will be commissioned using the control's
factory settings.
1. OCHSNER accepts no liability for possible
malfunctioning (heating curve too low, bi-
valent point too high, etc.). Any claims re-
sulting from this will be invoiced to the
system installer.
2. In order to run the system economically, it
is absolutely necessary that the system be
balanced hydraulically and that the con-
trol settings are coordinated to the system
requirements.
3. Other necessary work performed, such as
bleeding the system, electrical wiring, ad-
ditional instruction etc., that do not fall
within the realm of the OCHSNER firm’s
duties will be invoiced separately
6.5 Commissioning OCHSNER
Commissioning requests are to be made to
OCHSNER Customer Service. A date for commis-
sioning can only be made when the completed and
signed commissioning form is handed in.
Please make appointments for fixed commission-
ing dates at least 2 weeks in advance.
To undergo the commissioning process, the fol-
lowing work should be complete:
The heating and hot-water systems must be
completely installed, filled, bled, and hydrau-
lically adjusted.
The electric connection from the main circuit
3x400V/50Hz, (control and main voltage cir-
cuit VX, machine drives 230V/50Hz) and other
electrical installations on the building site are
complete. Confirmation of proper field rota-
tion, no provisional modifications!
The brine system must be filled and bled of air.
Work that needs to be carried out by OCHSNER:
Check the refrigerant circuit
Check minimum flow rate
Calibrating the safety equipment
Controlling the switching sequence
Creating a commissioning protocol
Basic control settings
Explanation of the heat pump and control to
the end user (assuming he/she is present at
commissioning).
Optional: Configure the system by means of
the commissioning (IBN) assistant
Store the sensor configuration
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72

Ochsner AQUA 54 Operating Instructions & Installation Instructions

Category
Heat pumps
Type
Operating Instructions & Installation Instructions
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI