Vaillant geoTHERM VWS Installation guide

Category
Heat pumps
Type
Installation guide

This manual is also suitable for

For the heating engineer
Installation instructions
geoTHERM
Heat pump
VWS
GB
Installation instructions geoTHERM VWS 0020046310_012
Contents
1 Notes on the documentation ........................... 3
1.1 Storage of the documents ...................................... 3
1.2 Symbols used ............................................................. 3
1.3 Applicability of the manual ..................................... 4
1.4 CE label ........................................................................ 4
1.5 Intended use ............................................................... 4
2 Description of the appliance ........................... 5
2.1 Data badge .................................................................. 5
2.2 Functional principle .................................................. 6
2.3 Design of the heat pump ......................................... 7
2.4 General notes on operating modes and
functions ...................................................................... 9
3 Safety instructions and regulations .............. 10
3.1 Safety instructions ................................................... 10
3.2 Regulations, rules, guidelines ............................... 10
3.3 Coolants ....................................................................... 11
4 Assembly and installation ............................... 12
4.1 Accessories ................................................................. 12
4.2 Requirements of the installation site .................. 12
4.3 Dimensions and clearances .................................... 13
4.4 Assembly/Installation at a glance ........................ 14
4.5 Preparatory work in the installation area .......... 14
4.6 Requirements of the heating circuit .................... 15
4.7 Scope of delivery ...................................................... 15
4.8 Unpacking the unit and checking the delivery .. 16
4.9 Transporting the heat pump .................................. 16
4.10 Installing the heat pump ......................................... 17
4.11 Removing the cladding ............................................ 18
4.12 On-site installation .................................................... 19
4.12.1 Assembly of the heating system ........................... 20
4.12.2 Assembly, brine circuit ............................................ 20
4.13 Fitting the VRC DCF outside temperature
sensor ........................................................................... 21
4.14 Fitting the VR 90 remote control unit................. 21
4.15 Installing the VR 60 mixer module ....................... 21
5 Filling the heating and heat source systems 21
5.1 Filling the heating circuit ........................................ 21
5.2 Filling the brine circuit ............................................. 21
6 Electrical installation ....................................... 24
6.1 Safety and installation information...................... 24
6.2 Regulations pertaining to electrical
installations ................................................................ 24
6.3 Electronic box ............................................................ 25
6.4 Connecting the power supply ................................ 25
6.4.1 Unblocked mains supply (Electroplan 1) .............. 26
6.4.2 Dual circuit feed, heat pump tariff
(Electroplan 2) ........................................................... 27
6.4.3 Dual circuit feed, special tariff
(Electroplan 3) ........................................................... 28
6.4.4 Connecting external components ......................... 29
6.4.5 Simultaneous operation of the compressor
and auxiliary heating ................................................ 30
6.5 Controller PCB at a glance ..................................... 31
6.6 Wiring the controller PCB ....................................... 32
6.6.1 Connecting the VR 10 standard sensor ............... 32
6.6.2 Direct heating operation (Hydraulic plan 1) ....... 33
6.6.3 Mixer circuit with buffer cylinder
(Hydraulic plan 2) ...................................................... 34
6.6.4 Direct heating operation and domestic
hot water cylinder (Hydraulic plan 3) .................. 35
6.6.5 Mixer circuit with buffer cylinder and domestic
hot water cylinder (Hydraulic plan 4) .................. 36
6.7 Connecting the DCF receiver ................................. 37
6.8 Connecting accessories ........................................... 37
6.8.1 Installing the VR 90 remote control unit ............ 37
6.8.2 Connecting further mixer circuits ........................ 38
6.8.3 Connecting vrnetDIALOG ........................................ 38
6.9 Connecting an external boiler ............................... 39
6.10 Fitting the cladding and the control panel ......... 39
7 Start-up .............................................................. 41
7.1 General points regarding start-up ........................ 41
7.2 Operating the controller ......................................... 42
7.2.1 Finding your way around the controller ............. 42
7.2.2 Calling up the screens ............................................. 42
7.3 Carrying out the initial commissioning ............... 43
7.4 Bleeding the brine circuit. ....................................... 44
7.5 Bleeding the heating circuit ................................... 44
7.6 Handing the system over to the operator .......... 44
8 Controller ........................................................... 45
8.1 Operating modes and functions ............................ 45
8.2 Automatic auxiliary functions ................................ 45
8.3 Settable auxiliary functions.................................... 46
8.3.1 Auxiliary functions in the Operator Level: ......... 46
8.3.2 Auxiliary functions in the Code Level: ................. 46
8.3.3 Auxiliary functions via vrDIALOG: ........................ 47
8.4 Description of the controller .................................. 47
8.4.1 Possible system circuits .......................................... 47
8.4.2 Energy balance controller ...................................... 47
8.4.3 Charging principle buffer cylinder ........................ 48
8.4.4 Resetting to factory settings ................................. 48
8.4.5 Controller structure ................................................. 48
8.5 Operator level sequence diagram ........................ 49
8.6 Code level sequence diagram ................................ 50
8.7 Displays in the operator level ................................ 52
8.8 Displays in the code layer ....................................... 57
8.9 Installer Menu ............................................................ 65
8.10 Parameters that can be set with
vrDIALOG 810/2 67
9 Inspection and maintenance ........................... 69
9.1 Notes for maintenance ............................................ 69
9.2 Carrying out maintenance work ............................ 69
9.4 Test operation and restarting................................ 69
10 Troubleshooting and diagnosis ....................... 70
10.1 Error messages on the controller ......................... 70
10.2 Malfunctions of eBUS components ...................... 71
Contents
3Installation instructions geoTHERM VWS 0020046310_01
1 Notes on the documentation
The following notes are intended as guidance throug-
hout the entire documentation.
Further documents apply in combination with this instal-
lation manual.
We accept no liability for any damage caused by fai-
lure to observe these instructions.
Other applicable documents
For the owner of the system:
Operating manual No. 0020045200
For the heating engineer:
Installation instructions,
VPS buffer cylinder No. 0020070601
Installation Manual for vrnetDIALOG No. 839189
Installation manual for vrDIALOG No. 0020023003
The manuals for any accessories and controllers used
also apply.
1.1 Storage of the documents
Please pass this installation manual and all other valid
documents on to the owner of the installation in order
for him or her to store it so that it is available whenever
it is required.
1.2 Symbols used
Please observe the safety instructions in this installation
manual for the installation of the appliance.
d
Danger!
Immediate risk of serious injury or
death!
e
Danger!
Danger of death by electric shock!
H
Danger!
Danger of burning and scalding!
a
Caution!
Potentially dangerous situation for the
product and environment.
h
Note!
Useful information and instructions
• Symbol for a necessary task
Contents
Notes on the documentation 1
10.3 Displays in the error memory and under
"Warning message" .................................................. 71
10.4 Temporary shut-down ............................................. 72
10.5 Blocking error ............................................................ 74
10.6 Other errors/malfunctions ..................................... 76
11.2 Packaging .................................................................... 77
11.3 Coolants ....................................................................... 77
12 Warranty and customer service ..................... 77
12.1 Vaillant warranty....................................................... 77
12.2 Vaillant Service .......................................................... 77
13 Technical data .................................................. 78
14 Start-up checklist ............................................. 80
15 Reference ........................................................... 82
Appendix ....................................................................... 85
Sensor characteristics.......................................................... 85
VRC-DCF outside temperature sensor ............................. 86
Heat pump schematic ........................................................... 87
Electrical circuit diagram .................................................... 88
Installation instructions geoTHERM VWS 0020046310_014
1.3 Applicability of the manual
These installation instructions apply exclusively to appli-
ances with the following part numbers:
Type name Article number
VWS 61/2 230 V 0010005501
VWS 81/2 230 V 0010005502
VWS 101/2 230 V 0010005503
Table 1.1 Type designations and article numbers
The part number of the equipment can be taken from
the identification plate.
1.4 CE label
With the CE mark, we confirm as equipment manufactu-
rers that the appliances in the geoTHERM range satisfy
the basic requirements of the following Directives:
– Electromagnetic Compatibility Directive (Council Di-
rective 89/336/EEC)
– Low voltage directive (73/23/EEC)
– EN 14511 (heat pumps with electrically-driven compres-
sors for heating, specifications for appliances for
space heating and for warming drinking water)
– EN 378 (safety and environmentally related specifica-
tions for refrigerating systems and heat pumps)
1.5 Intended use
The Vaillant geoTHERM heat pumps are state-of-the-art
appliances which have been constructed in accordance
with recognised safety regulations. Nevertheless, there
is still a risk of death or serious injury to the user or
others or of damage to the device and other property in
the event of improper use or use for which it is not in-
tended.
This unit is not intended for use by persons (including
children) having limited physical, sensory or mental ca-
pacities or who have inadequate experience and/or
knowledge, unless they are supervised by a person re-
sponsible for their safety or have been given instruc-
tions by him regarding the operation of the unit.
Children must be supervised to ensure that they do not
play with the unit.
The units are intended as heaters for closed hot-water
central heating installations and for hot water generati-
on. Any other use or extended use is considered to be
improper. The manufacturer or supplier is not liable for
any resulting damage. The user alone bears the risk.
The appliances are intended for operation on a power
supply network with a system impedance Z
max
at the
transfer point (house connection) of 0.16 ohms maxi-
mum.
Intended use includes the observance of the installation
manual.
a
Caution!
Any improper use is forbidden.
The appliances must be installed by a heating engineer,
who is responsible for adhering to the existing regulati-
ons, rules and guidelines.
1 Notes on the documentation
5Installation instructions geoTHERM VWS 0020046310_01
2 Description of the appliance
2.1 Data badge
An identification plate is attached to the baseplate on
the inside of the geoTHERM heat pump. The type desi-
gnation is located at the top on the grey frame of the
pillar (also see Fig. 2.4, Item 1).
R407 C
COP B0/W35
4,2
COP B5/W55
3,0
B0/W35
B5/W55
1/N/PE 230V 50Hz
IP 20
Vaillant GmbH Remscheid / Germany
1/N/PE 230V 50Hz
1/N/PE 230V 50Hz
6,8 kW
2,8 kW
2 / 4 kW
58 A
<16 A
1,9 kg
2,9 (29) MPa (bar)
6,0 kW
6,3 kW
VWS 61/2 230 V
IT FR NO LV LT EE ES UK
Serial-No. 21054500100028300006000001N1
21054500100028300006000001N4
16 A
-- I
-- MPa (bar)
Fig. 2.1 Example of an identification plate
Explanation of the symbols on the identification plate
Rated voltage - compressor
Rated voltage - pumps + controller
Rated voltage - auxiliary heating
Rated maximum power
Rated power - compressor, pumps
and controller
Rated power - auxiliary heating
Start-up current without start-up
current limiter
16 A
Start-up current with start-up
current limiter
Service water tank capacity
Permissible rated overpressure
Coolant type
Filling quantity
Permissible rated overpressure
COP B0/W35
Performance figure at a brine
temperature of 0 °C and a heating
flow temperature of 35 °C
COP B5/W55
Performance figure at a brine
temperature of 5 °C and a heating
flow temperature of 55 °C
B0/W35
Heating output at a brine
temperature of 0 °C and a heating
flow temperature of 35 °C
B5/W55
Heating output at a brine
temperature of 5 °C and a heating
flow temperature of 55 °C
CE mark
VDE/GS mark
Read the Operating and Installation
Manual!
Humidity protection class
Ensure proper disposal at the end
of its useful life (not household
waste)
21054500100028300006000001N4
Serial Number
Table 2.1 Explanation of symbols
Description of the appliance 2
Installation instructions geoTHERM VWS 0020046310_016
2.2 Functional principle
Heat pump systems consist of separate circuits in which
liquids or gases transport the heat from the heat source
to the heating system. As these circuits operate with
differing media (brine/water, coolant and heating
water), they are coupled to one another by means of
heat exchangers. In these heat exchangers the heat
passes from a medium at a high temperature to a medi-
um at a lower temperature.
The Vaillant geoTHERM heat pump uses geothermal en-
ergy as its heat source.
3/4 Environmental energy 4/4 Heating energy
1/4 Electrical energy
Fig. 2.2 Utilisation of heat sources such as geothermal energy
or ground water
Additional
heating
Domestic
hot water cylinder
Heating water circuit
Heat source circuit
Coolant circuit
Hot water
Cold water
Switching valve
Heating water pump
Condenser
Heat source
Brine pump
Evaporator
Compressor
Expansion valve
2
1
3
4
Heating system
Fig. 2.3 Mode of operation of the heat pump
The system consists of separate circuits which are coup-
led to one another by means of heat exchangers. These
circuits are:
- The heat source circuit, by means of which the energy
from the heat source is transported to the coolant cir-
cuit.
- The coolant circuit, which releases its heat to the hea-
ting water circuit by means of evaporation, compressi-
on, liquefaction and expansion.
- The heating water circuit, which supplies the heating
and the hot water generation for the domestic hot
water cylinder.
The coolant circuit is connected by means of the evapo-
rator (1) to the environmental heat source, from which it
extracts thermal energy. At the same time, the physical
state of the coolant changes; it evaporates. The coolant
circuit is connected by means of the condenser (3) to
the heating system, to which it releases the heat again.
In so doing, the coolant becomes liquid again; it con-
denses.
As thermal energy can only pass from a body at a high-
er temperature to a body at a lower temperature, the
coolant in the evaporator must have a lower tempera-
ture than the environmental heat source. On the other
hand, the temperature of the coolant in the condenser
must be higher than that of the heating water in order
to be able to release the heat to it.
2 Description of the appliance
7Installation instructions geoTHERM VWS 0020046310_01
These different temperatures are produced in the coo-
lant circuit by means of a compressor (2) and an expan-
sion valve (4), which are situated between the evapora-
tor and the condenser. The coolant flows in vapour form
from the evaporator into the compressor, where it is
compressed. This causes the pressure and temperature
of the coolant vapour to rise sharply. The coolant then
flows through the condenser, where it releases its heat
to the heating water by means of condensation. It flows
as a liquid to the expansion valve, where it expands sig-
nificantly and in so doing loses much of its pressure and
temperature. This temperature is now lower than the
brine/water flowing through the evaporator. The coo-
lant can thus take up more heat in the evaporator, tur-
ning into vapour in the process and flowing to the com-
pressor. The cycle starts again.
If required, the electric auxiliary heating can be swit-
ched in by means of the integrated controller.
To prevent the formation of condensate in the interior
of the unit, the pipes of the heat source circuit and the
coolant circuit are insulated. If condensate forms, this
collects in a pan (see Fig. 2.6, Item 11) and is led away
under the unit. Drop formation under the unit is thus
possible.
2.3 Design of the heat pump
The Vaillant geoTHERM heat pump is available in the
following models. The heat pump are, above all, diffe-
rent from each other in their output.
Type name Heating output (kW)
Brine water heat pumps (S0/W35)
VWS 61/2 230 V 6.0
VWS 81/2 230 V 8,1
VWS 101/2 230 V 10.5
Table 2.2 Type summary
You can read the type designation of the heat pump
from the sticker (see Fig. 2.4, Item 1) on the pillar frame.
The heat pump is designed to implement all current
electrical supply tariffs.
2
3
1
Fig. 2.4 Front view
Key to Fig. 2.4
1 Label with heat pump type designation
2 Operating panel
3 vrnetDIALOG mounting plate (behind the pillar cladding)
Description of the appliance 2
Installation instructions geoTHERM VWS 0020046310_018
3
2
1
5
4
6
7
Fig. 2.5 Rear view
Key to Fig. 2.5
1 Return to domestic hot water cylinder
2 Heat source to the heat pump
3 Heat source from the heat pump
4 Transportation handles
5 Cable feedthrough for electrical connections
6 Heating return
7 Heating feed
Assemblies
15
16
14
13
12
11
1
9
3
2
5
4
6
7
8
10
Fig. 2.6 Front view, covers removed
Key to Fig. 2.6
1 Electrical connections
2 Controller PCB (under cover plate)
3 Contactor for electric auxiliary heating
4 Safety thermostat STL for the auxiliary heating
5 Electric auxiliary heating
6 Condenser
7 CH pump
8 Fill/drain valve for heating circuit
9 Data badge
10 Compressor
11 Condensate pan
12 Expansion Valve
13 Fill/drain valve for brine circuit
14 Brine pump
15 Evaporator
16 3-way valve
2 Description of the appliance
9Installation instructions geoTHERM VWS 0020046310_01
2.4 General notes on operating modes and func-
tions
There are five operating modes available for the heating
circuit and these can be used for time and temperature
control of the heat pump (see Chap. 8 "Control sys-
tem").
Three additional operating modes are available for the
connected domestic hot water cylinder and circulation
circuit.
During start-up, you will tell the heat pump which of the
connection configurations listed in the appendix cor-
responds to your installation by entering the number of
the corresponding hydraulic plan into the controller.
Thus all the operating parameters will be set to prede-
termined values, so that the heat pump can work opti-
mally. However, you can individually set and adapt the
operating modes and functions afterwards.
You will find all the information on operating modes, au-
xiliary and special functions in Chapter 8, "Control sys-
tem".
The heat pump is equipped with numerous automatic
auxiliary functions to ensure trouble-free operation
(see also Chap. 8.2 "Automatic auxiliary functions"):
– Frost protection
Prevents the heating system from freezing
– Tank frost protection
Prevents the connected tanks from freezing
– Checking the external sensors
Checking the connected sensors during initial commis-
sioning using the basic hydraulic circuit that was
entered previously
– Protection against loss of heating water
Shuts down when there is a loss of heating water and
switches on again when there is sufficient water pres-
sure
- Protection against loss of brine
Shuts down if the brine pressure is too low and swit-
ches on again when the pressure is sufficient
– Floor protection circuit
Overheating protection for the floor (important for
wooden floors)
– Pump blocking protection
Prevents seizing of pumps in the system
- Freeze protection function
Shuts down the compressor if the temperature of the
heat source falls below a predetermined value
Additionally, there are further settable auxiliary func-
tions available (see also Chap. 8.3 "Settable auxiliary
functions"):
– Timer programmes
To set the heating times for each heating circuit
– Holiday programming
Programming of two holiday periods with date entry
and set-back temperature
– Party function
Carries the heating and hot water times forward to
the next shut-off point
– Energy saving function
Lowers the flow setpoint temperature for a presettab-
le period
– Screed floor drying
For drying out screed floors
– Fixed value controlling
Sets a fixed flow temperature
– Anti-legionella function
Kills germs in the tank and in the pipes
– Quick test
Test function for maintenance
– Remote maintenance
Diagnostics and setting via vrDIALOG or
vrnetDIALOG
Description of the appliance 2
Installation instructions geoTHERM VWS 0020046310_0110
3 Safety instructions and regulations
3.1 Safety instructions
The heat pump must be installed by an approved techni-
cian, who will be responsible for adhering to the existing
standards and regulations. We accept no liability for any
damage caused by failure to observe these instructions.
When full, the heat pump weighs roughly 140 -195 kg.
Take this into consideration when transporting and set-
ting up the unit. Pay particular attention to Chap. 4.2,
"Requirements of the installation site", before assembly.
d
Danger!
The coolant circuit is pressurised. Fur-
thermore, high temperatures can arise.
The appliance may only be opened and
serviced by Vaillant factory customer
service or by a qualified specialist tech-
nician. Work on the coolant circuit may
only be carried out by a qualified refrige-
ration engineer.
e
Danger!
Risk of electric shock!
Always switch off all power supplies be-
fore carrying out electrical installation
work. Make sure that they are secured
against inadvertent switching on again.
a
Caution!
Risk of damage!
Do not add any antifreeze or corrosion
protection agents to the heating water,
as seals and other components can be
damaged as a result and this can lead to
water leaks.
If the heating water hardness is more than 3.0 mmol/l
(21.05 °e) it should be softened. You can use the Vail-
lant ion exchanger (Art. No. 990 349) for this purpose.
Observe the enclosed instructions for use.
3.2 Regulations, rules, guidelines
Pay particular attention to the local specifications, pro-
visions, regulations and guidelines on/by the following
when setting up, installing and operating the heat pump:
– electrical connection
– supply system operator
– water distribution company
– geothermal energy utilisation
– integration of heat sources and heating installations
– energy conservation
– hygiene
3 Safety instructions and regulations
11Installation instructions geoTHERM VWS 0020046310_01
3.3 Coolants
The heat pump is delivered with an operational filling of
R 407 C coolant. This is a chlorine-free coolant which
does not affect the Earth's ozone layer. R 407 C is neit-
her a fire hazard nor an explosion risk.
However, maintenance work and interventions into the
coolant circuit may only be undertaken by an expert
technician with appropriate protective equipment.
d
Danger!
R 407 C coolant!
Do not inhale gases or vapours emana-
ting from leaks in the coolant circuit.
Risk to health! Avoid contact with the
skin and eyes. Escaping coolant can
cause frostbite if the exit point is
touched! R 407 C coolant presents no
danger in normal use and under normal
conditions. With improper use, however,
it can cause injury and damage.
a
Caution!
This appliance contains R 407 C coolant.
The coolant must not be allowed to es-
cape into the atmosphere. R 407 C is a
fluorinated greenhouse gas covered by
the Kyoto Protocol, with a GWP of 1653
(GWP = Global Warming Potential).
Before the appliance is disposed of, the
coolant it contains must be completely
drained into a suitable vessel so that it
can then be recycled or disposed of in
accordance with the regulations.
The relevant work in connection with the
coolant may only be carried out by offi-
cially certified specialists.
Coolant (see identification plate for
quantity) may only be drained off and
fresh coolant may only be added via the
service valves. All warranties become
void if any approved replacement coolant
other than the R 407 C recommended by
Vaillant is used.
Safety instructions and regulations 3
Installation instructions geoTHERM VWS 0020046310_0112
4 Assembly and installation
4.1 Accessories
You can fit the following accessories to expand the heat
pump system. You can find more detailed information
on the installation of accessories in Chap. 5.8.
Mixer module VR 60
With the mixer module, you can expand the control sys-
tem of the heating installation by two mixer circuits.
You can connect a maximum of six mixer modules.
VR 90 remote control unit
You can connect a separate remote control unit for the
first six heating circuits (HC 1 - HC 6).
VR 10 standard sensor
Additional sensors may be required, e.g. as flow, return,
collector or cylinder sensors, depending on the configu-
ration of the system.
vrDIALOG 810/2
vrDialog is a communications unit with software and
connecting cable which enables you to carry out diagno-
sis, monitoring and parametrisation of the heat pump
from a computer.
vrnetDIALOG 840/2, 860/2
The vrnetDIALOG communications unit enables you to
carry out remote diagnosis, monitoring and parameter
setting on the heat pump from a computer over a tele-
phone connection or via an integrated GSM modem.
VPS heating water buffer cylinder
The VPS buffer cylinder provides an intermediate sto-
rage facility for heating water and can be installed
between the heat pump and heating circuit. It provides
the necessary energy to bridge over the power compa-
ny blocking periods.
Other accessories
- Heat transfer fluid
- Filling pump
- Safety assembly and tundish
- Expansion vessel for the heating circuit
4.2 Requirements of the installation site
– Choose a dry room that is generally frost-proof.
– The floor must be level and sufficiently stable to be
able to bear the weight of the heat pump, together
with a DHW and possibly a buffer tank.
– It must be possible to install suitable pipe conduits
(for heat source, DHW and heating).
– When choosing the installation site, bear in mind that
when operating, the heat pump can transmit vibra-
tions to the floor or nearby walls.
- In accordance with DIN EN 378 T1, the minimum instal-
lation space for heat pumps, (V
min
), is calculated as
follows:
V
min
= G/c
G = coolant fill quantity in kg
c = practical limit in kg/m
3
(c = 0.31 kg/m
3
applies for R 407C).
This yields the following minimum installation space:
Heat pump type Coolant fill quantity
[kg]
Minimum
installation space
VWS 61/2 230 V 1.9 6.1
VWS 81/2 230 V 2.2 7.1
VWS 101/2 230 V 2.05 6.6
Table 4.1 Minimum installation space
4 Assembly and installation
13Installation instructions geoTHERM VWS 0020046310_01
4.3 Dimensions and clearances
600
100
140140
75 75
1200
0-10
1)
600
835
650
Fig. 4.1 Dimensions and clearances
1)
Adjustable feet adjustable in height by 10 mm
Assembly and installation 4
Installation instructions geoTHERM VWS 0020046310_0114
300 mm
10 mm
600 mm
300 mm
300 mm
Fig. 4.2 Minimum clearances for installing the heat pump
4.4 Assembly/Installation at a glance
– Remove packing material.
– Remove transportation safety devices.
– Transport the heat pump to the installation area.
– Position and align the heat pump in the intended as-
sembly location.
– Remove the upper cladding.
– Remove the front cladding.
– Connect the on-site piping.
– Carry out the electrical installation.
– Fill the heating circuit.
– Fill the heat source circuit.
– Fit the cladding.
– Fit the operating console.
– Carry out the initial commissioning.
– Fill out the start-up checklist.
– Hand over system to the user and familiarise him with
it.
4.5 Preparatory work in the installation area
1
1
2
3
3
Fig. 4.3 Preparatory work in the installation area
• Make sure that the substrate is sufficiently stable (see
Chap. 4.2 "Requirements for the installation site“).
• Drill at least two bore holes, bearing in mind the di-
mensions of the unit and its connections (1).
• A separate bore hole is required for each heat source
pipe.
• Special pipe lead-throughs must be used if there is a
risk of ground water penetration (follow the
manufacturer's details).
• Take account of the distances to the core barrels for
the rest of the installation.
• Pass the heat source pipes (2) from the outside into
the installation area.
• Lay the heat source pipes (2) centrally in the bore
holes (1) to facilitate all-round thermal insulation.
• Seal the annular gap (1) as shown with foam insulation
(e.g. PE foam) (3).
• Install diffusion-tight insulation pipes from heat sour-
ces in cellar areas, as condensation will otherwise
form (pipe temperature may be as low as -15 °C).
4 Assembly and installation
15Installation instructions geoTHERM VWS 0020046310_01
4.6 Requirements of the heating circuit
The heat pump is only suitable for connection to a
closed central heating installation. To ensure trouble-
free operation, the central heating installation must
have been installed by authorised technical personnel in
compliance with the applicable regulations.
A heat pump is suited to low temperature heating sys-
tems. The system must therefore be designed for low
flow temperatures (ideally around 30 to 35 °C). Further-
more, it must be ensured that power company outages
are bridged over.
EN 12828 requires the following the heating system in-
stallation:
– a filling valve, in order to fill the heating system with
water or be able to drain the water,
– a diaphragm expansion vessel in the return line of the
heating circuit,
– an overpressure safety valve (opening pressure 3 bar)
with pressure gauge (safety group) in the flow line of
the heating circuit, immediately after the appliance,
– an air/dirt separator in the return line of the heating
circuit.
To avoid energy losses and protect against freezing,
thermal insulation must be installed on all supply lines.
The lines must be dirt free - so flush these through tho-
roughly before filling, if necessary.
a
Caution!
Risk of damage!
Do not add any antifreeze or corrosion
protection agents to the heating water,
as seals and other components can be
damaged as a result and this can lead to
water leaks.
In hydraulic installations that are predominantly equip-
ped with thermostatically or electrically controlled val-
ves, it is necessary to ensure a constant, adequate flow
through the heat pump. Regardless of the choice of hea-
ting system, the nominal flow rate of heating water
must be ensured. This is guaranteed by using a professi-
onally installed buffer cylinder.
4.7 Scope of delivery
3
2
1
6
5
4
7
8
12
9
13
14
10
11
Fig. 4.4 Checking the supplied material
For key, see Table 4.2.
The heat pump is delivered on a pallet in two packing
units.
• Check the heat pump and the separately packaged
operating console for any transport damage.
Assembly and installation 4
Installation instructions geoTHERM VWS 0020046310_0116
Pos. Description
1 1 Heat pump
2 1 Operating console, pillar cover
33
2
3
2
Gaskets (yellow/green) for heating circuit elbow
unions
M6 flat-headed screws for fitting the operating
console to the frame (plus one spare screw)
Self-tapping screws for the operating console
frame (incl. one spare screw)
Self-tapping screws for fastening the
vrnetDIALOG unit
4 1 6 Litre brine expansion tank incl. brass adapter,
max. 3 bar
5 1 VRC-DCF outside temperature sensor
6 4 VR 10 sensors
7 1 Control cable for vrnetDIALOG
8 5 45° connection elbow with cap nuts
9 1 Expansion relief valve for brine circuit, 1/2", 3 bar
10 1 Bag of small parts for fastening the brine
expansion tank
11 1 Clamp for fastening the brine expansion tank
12 1 Insulation matting for heat source connection on
the rear wall
13 5 Installation instructions, operating manual
14 2 Seals with metal support rings for heat source
circuit connection elbows
Table 4.2 Scope of delivery
The frame for the operating console is already fastened
to the heat pump casing on delivery.
4.8 Unpacking the unit and checking the delivery
2 x
Fig. 4.5 Removing the transport securing device
• Carefully remove the packaging and padding, taking
care not to damage any parts of the unit.
• Unfasten the transport securing devices (brackets)
with which the heat pump is fixed to the pallet.
The brackets are no longer required.
4.9 Transporting the heat pump
We recommend that the heat pump be transported with
the aid of a suitable barrow. The handles on the rear
side of the unit are provided as transportation aids (see
Fig. 2.5, Item. 4).
d
Danger!
Risk of injury!
Depending on type, the heat pump
weighs 140 - 195 kg in the unfilled state.
To avoid injury, use several people to lift
it.
a
Caution!
Risk of damage!
Regardless of the mode of transport, the
heat pump must never be tilted by more
than 45°. Otherwise it can cause mal-
functions in the coolant circuit during
later operation, which in the worst case
can lead to a failure of the whole sy-
stem.
max. 45°
Fig. 4.6 Transporting the heat pump (carrying)
4 Assembly and installation
17Installation instructions geoTHERM VWS 0020046310_01
We recommend that the heat pump be transported with
the aid of a suitable barrow.
max. 45°
Fig. 4.7 Transporting the heat pump (pushcart)
a
Caution!
Risk of damage!
Find out the weight of your heat pump
from the Technical Data and make sure
that the transport equipment you select
is appropriately designed.
When using a barrow, take note:
• Only use the barrow on the rear side of the heat
pump, as the weight distribution is then the most fa-
vourable.
• Fasten the heat pump with a restraining strap.
• Use a ramp when pushing the barrow from the pallet,
e.g. a batten and a sturdy board.
4.10 Installing the heat pump
0-10 mm
Fig. 4.8 Adjusting the feet
• Pay attention to the minimum wall clearances when
installing the heat pump (see Fig. 4.2).
• Align the heat pump horizontally by adjusting the feet.
Assembly and installation 4
Installation instructions geoTHERM VWS 0020046310_0118
4.11 Removing the cladding
The cladding panels are screwed on and additionally
provided with retaining clips.
Fig. 4.9 Removing the upper cover
• Remove the pipe access cover, which is fastened with
retaining clips, by pulling it gently upwards.
• Unfasten the screws for the upper cover which are
concealed beneath it.
• Remove the upper cover in an upwards direction.
Fig. 4.10 Removing the front lower cladding
• Unfasten the two screws on the console frame and
pull it, together with the front lower cladding, away
from the casing.
Fig. 4.11 Removing the front upper cladding
• Unfasten the two screws on the front of the front
upper cladding and remove the cladding.
4 Assembly and installation
19Installation instructions geoTHERM VWS 0020046310_01
4.12 On-site installation
a
Caution!
Flush the heating system thoroughly be-
fore connecting the appliance!
By doing that, residue such as welds,
cinder, hemp, putty, rust, rough dust and
similar substances are removed from the
pipes. Otherwise such substances can be
deposited in the appliance and cause da-
mage.
a
Caution!
To prevent leaks, take care that no me-
chanical stresses are created on the
connection lines!
- The pipework installation must be carried out in ac-
cordance with the dimensional and connection dra-
wings in Fig. 4.1.
- The installation must be performed by a specialist fit-
ter.
- The applicable regulations must be observed during
the installation.
h
Note!
Air in the heating system leads to im-
paired operation and reduces the heating
output. Fit bleed valves as required.
3
4
5
6
7
2
1
Fig. 4.12 Fitting the connection elbows
Key to Fig. 4.12
1 Heating feed
2 Heating return
3 Return to domestic hot water cylinder
4 Heat source to the heat pump
5 Heat source from the heat pump
6 Insulating pad
7 Blanking plugs
a
Caution!
To avoid leaks, take care that the cor-
rect seals are used on the connecting el-
bows!
Leaks can result if the seals with the
metal support ring are not used in the
heat source circuit!
• Remove the blanking plugs from the appliance con-
nections (7). They are no longer needed and can be
disposed of.
• Fit the three connecting elbows (1 to 3) with the yel-
low/green gaskets supplied with the accessories.
• Fit the two connecting elbows (4 and 5) with the seals
with the metal support ring supplied with the accesso-
ries.
• The accessory kit contains an insulating pad for insu-
lating the connection plate. Fit this insulating pad to
the two right hand screwed connections (6).
Assembly and installation 4
Installation instructions geoTHERM VWS 0020046310_0120
4.12.1 Assembly of the heating system
a
Caution!
Risk of damage!
In order to be able to clear any possible
overpressure, the heat pump must be
connected to an expansion vessel and an
expansion relief valve, at least DN 20
with a maximum opening pressure of
3 bar (not supplied).
H
Danger!
Risk of scalding!
The blow-off line on the expansion relief
valve must be the size of the valve's
outlet aperture and be installed in a
frost-free environment. It must remain
constantly open. It must be fitted in
such a way that persons are not endan-
gered by hot water or steam when it
blows off.
We recommend the installation of a
Vaillant safety group and a tundish.
• Fit the heating flow and return lines with all compo-
nents.
• Insulate all the pipes.
4.12.2 Assembly, brine circuit
• Install the heat source pipes and all their associated
components.
49
61
49
61
58
57
65
42a
5858
K
33
Fig. 4.13 VWS heat source circuit
Key to Fig. 4.13
33 Air separator/Dirt filter
42a Expansion relief valve
49 Flow rate adjuster
57 Brine expansion tank
58 Filling and drainage tap
61 Brine circuit
65 Brine collecting tank
K Collector
42a
57
65
1
Fig. 4.14 Fitting the brine expansion tank
h
Note!
The brine expansion tank has a capacity
of approx. 6 litres and is thus adequate
for brine circuits up to a maximum of
1900 litres.
a
Caution!
Material damage resulting from escaping
brine!
The screw couplings on the brine expan-
sion tank must be sealed with hemp.
Sealing with, e.g., teflon tape can lead to
leaks in the brine circuit.
• Fit the bracket for the brine expansion tank to the
wall using the wall plug and the screw.
• Unfasten the pre-assembled connection pieces from
the brine expansion tank (57).
• Wind hemp into the outer threads of the connection
pieces.
• Fit the first connection piece to the 3 bar expansion
relief valve (42a) enclosed with the heat pump.
• Using the second connection piece, fit the brine ex-
pansion tank (57) from the accessory kit to the pipe
(1) running from the heat source to the heat pump.
• Fix the brine expansion tank with the bracket.
• Fit the connection piece with the expansion relief
valve to the brine expansion tank.
• Fit the brine collecting tank (65) to the expansion reli-
ef valve (42a) at zero pressure.
The brine collecting tank must not be completely
closed, as otherwise the functioning of the expansion
relief valve is not guaranteed.
• Provide all the pipes with vapour-proof thermal insula-
tion. The accessory kit contains the insulating mat
provided for the thermal insulation of the connection
plate.
4 Assembly and installation
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92

Vaillant geoTHERM VWS Installation guide

Category
Heat pumps
Type
Installation guide
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI