Emerson EMC-240B Installation guide

  • Hello! I am an AI chatbot trained to assist you with the Emerson EMC-240B Installation guide. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
Features
Fast■Response■Time
40,000■Amps■per■phase■capacity
Failsafe■and■fused
Operational■Status■Indicators
ANSI/UL■1449■Third■Edition
5■year■warranty
EDCO EMC-240B
120/240VAC■Surge■Protection
The■ Edco■ EMC-240B■ surge■ suppressor■ is■ designed■ to■ protect■ AC■ distribution■
panel■ circuits■ or■ 120■ V■ power■ supplies■ feeding■ sensitive■ electronic■ equipment.■
Electrically,■the■unit■incorporates■MOV■fusing■technology.■The■Edco■EMC-240B■is■
designed■to■be■installed■in■parallel■on■standard■split■phase■120/240■VAC■(3W+G)■or
single■phase■120■VAC■(2W+G)■circuits.
General Technical Specifications
Models
Operating■Voltage 120/240■VAC
Total■Peak■Surge■Current 80■kA■(8x20■μs)
Short■Circuit■Current■Rating 42■kAIC
UL1449■Location■Type Type■2
UL1449■Nominal■Discharge■Current■(I
n
) 3■kA
Operating■Current NA,■Parallel■Connection
Operating■Frequency 47-63■Hz
EMI■Attenuation■■
(100■kHz■to■100■MHz)
>■40■db
SPD■Technology Metal■Oxide■Varistors■(MOVs)
Modes■of■Protection Line-to-Line■(L-L)
Line-to-Neutral■(L-N)
Status■Indication Power■On■&■MOV’s■Functional
Connection■Type Wire■Leads
Operating■Temperature -40°C■to■+85°C
Dimensions■(in■/■mm) 4.6˝■H■x■2.2˝■W■x■2.8˝■L■
[116.84■x■55.88■x■71.12■mm]
Weight■(oz■/■kg) 13.5■oz■[0.38■kg]
Certifications ANSI/UL1449■Third■Edition
EMC-240B with■1/2˝■[12.7■mm]■Chase■Nipple
EMC-240BK with■1/2˝■[12.7■mm]■Conduit■Offset,■
2.5˝■[63.5■mm]■Long
EMC-240BK90 with■1/2˝■[12.7■mm]■Conduit■90°,■
3.25˝■[82.55■mm]■Long
Installation Instructions
Emerson Network Power Contact information
Surge■Protection
100■Emerson■Parkway
Binghamton,■NY■13905
T:■(607)■721-8840
T:■(800)■288-6169
F:■(607)■722-8713
E:■SurgeTech@Emerson.com
IO-50101■5-14■Rev.■7■Printed■in■USA
www.EmersonNetworkPower.com/Surge
120 V applications use a single pole 30 Amp breaker 120/240 V applications use a 2 pole 30 Amp breaker
While■every■ precaution■has■been■taken■to■ensure■accuracy■ and■completeness■herein,■Emerson■Network■ Power■Surge■Protection■assumes■no■responsibility,■and■disclaims■all■liability,■for■damages■
resulting■from■use■of■this■information■or■for■any■errors■or■omissions.■Specifications■are■subject■to■change■without■notice.
Emerson■Network■Power,■the■Emerson■Network■Power■logo■and■Edco■are■trademarks■
and■service■marks■of■Emerson■Electric■Co.■©2014■Emerson■Electric■Co.
Dimensions
Connect on load side of main breakers
Keep wires short and straight as possible for best
suppression performance.
2.160”
[54.86]
4.600”
[116.84]
1/2”
[12.7]
CHA
SE
NIPPL
E
2.800”
[71.12]
EMC-240B
Black
Black
White
Green
120 V
120 V
Ground
L1
240
V
L2
N
L2 NL1
L
N
120 V
Ground
EMC-240B
Black
Black
White
Green
NL
Seulement■le■personnel■qualifié■doit■installer■
ou■ maintenir■ ce■ systéme.■ Des■ précautions■
de■sécurité■en■électricité■doivent■être■sui vis■
lors■ de■ l’installation■ ou■ de■ la■ maintenance■
de■ cet■ equipement.■ Pour■ eviter■ tout■ risque■
de■choc■électrique,■débranchez■et■verouiller■
toutes■ les■ sources■ d’alimentation■ de■ cet■
equipement■avant■de.
Only■ qualified■ personnel■ should■ install■ or■
service■ this■ system.■ Electrical■ safety■ pre-
cautions■ must■ be■ followed■ when■ installing■
or■ servicing■ this■ equipment.■To■ prevent■ risk■
of■ electrical■ shock,■ turn■ off■ and■ lock■ out■ all■
power■ sources■ to■ the■ unit■ before■ making■
electrical■connections■or■servicing.
V
DANGER!
/