Emerson Transient Detection System Installation guide

Type
Installation guide

Emerson Transient Detection System offers real-time power quality monitoring, event logging, and protection against damaging voltage surges. It measures and displays RMS voltages, frequency, crest factor, VTHD, voltage unbalance, and MOV health. It also logs power quality events, system events, and surge/transient, sag, swell, phase loss/outage, voltage interruption/dropout, voltage harmonics, neutral bond, overvoltage, temporary overvoltage, over/under frequency, and protection failure.

Emerson Transient Detection System offers real-time power quality monitoring, event logging, and protection against damaging voltage surges. It measures and displays RMS voltages, frequency, crest factor, VTHD, voltage unbalance, and MOV health. It also logs power quality events, system events, and surge/transient, sag, swell, phase loss/outage, voltage interruption/dropout, voltage harmonics, neutral bond, overvoltage, temporary overvoltage, over/under frequency, and protection failure.

Applicable to Emerson Network Power
SPD’s with “T” in the monitoring
position (10
th
digit) of the model number.
Example: (SPD Model Number) 560 _ _ _ _ _ _ T _ _ _
A
dvanced Transient Detection System
Quick Start Guide
Scan this QR code to learn
more about Emerson Network
Power Surge Protection.
Installation, Operation and Maintenance Manual QS-70100 Rev 0, 1/2015
Page | 1
Thank You for choosing the Emerson Network Power advanced Transient Detection System
package with your Surge Protective Device. Emerson Network Power Surge Protective
Devices(SPDs) are high quality, high energy surge current diversion system designed to
protect sensitive equipment from damaging transient voltage surges resulting from load
switching, lightning strikes and other sources.
Emerson Network Power makes it easy to monitor your electrical system by integrating its
advanced Transient Detection and monitoring package within its SPDs. The web-based device
allows the end-user real time power quality measurements, logged events, statistical
summaries and premium power protection.
Please read all instructions before starting the installation of this product. These instructions
do not replace national or local electrical codes — check applicable codes to ensure
compliance.
This Quick-Start Guide provides general information pertaining to the installation &
operation of the SPD monitoring system. For detailed Installation & Operation instructions,
refer to the full manual (document # IO-70109).
For general SPD installation instructions, reference the installation manual provided with your SPD.
DANGER! ONLY QUALIFIED PERSONNEL SHOULD INSTALL
OR SERVICE THIS SYSTEM. ELECTRICAL SAFETY PRE-
CAUTIONS MUST BE FOLLOWED WHEN INSTALLING OR
SERVICING THIS EQUIPMENT. TO PREVENT RISK OF ELECTRICAL SHOCK, TURN OFF AND
LOCK OUT ALL POWER SOURCES TO THE UNIT BEFORE MAKING ELECTRICAL
CONNECTIONS OR SERVICING.
DANGER! SEULEMENT LE PERSONNEL QUALIFIÉ DOIT INSTALLER OU MAINTENIR CE
SYSTÈME. DES PRÉCAUTIONS DE SÉCURITÉ EN ÉLECTRICITÉ DOIVENT ÊTRE SUIVIS LORS
DE L'INSTALLATION OU DE LA MAINTENANCE DE CET EQUIPEMENT. POUR EVITER TOUT
RISQUE DE CHOC ÉLECTRIQUE, DÉBRANCHEZ ET VEROUILLER TOUTES LES SOURCES D’
ALIMENTATION DE CET EQUIPEMENT AVANT DE LE BRANCHER OU LE MAINTENIR.
Summary
The Emerson Network Power advanced Transient Detection System measures, displays, &
logs the following parameters/events:
Measured & Displayed
RMS Voltages
Frequency
Crest Factor
VTHD
Voltage Unbalance
MOV Health
Logged Power Quality Events
Surge/Transient
Sag
Swell
Phase Loss/Outage
Voltage Interruption/Dropout
Voltage Harmonics (VTHD)
Neutral Bond
Overvoltage
Temporary Overvoltage (TOV)
Over/Under Frequency
Protection Failure
Logged System Events
Power On
Settings change
Firmware Upgrade
Communication Error
Software Reset
Installation, Operation and Maintenance Manual QS-70100 Rev 0, 1/2015
Page | 2
Communication Connections
Connect all applicable communication wiring to the monitoring system.
2 sets of Form C relay contacts;
250VAC, 5A max. (J10 & J11)
RS-485 for MODBUS RTU
Connection (J13 & J15)
RJ-45 Ethernet Port (J20)
Status LEDs
Red, Green, & Orange
LED indication is provided for each phase, neutral, and
service. If all LEDs are not solid green at power-up,
verify source voltages & mechanical connections. If
the alarm condition persists, call Emerson Network
Power Surge Protection, Inc at 607-721-8840.
Display Screens
The advanced Transient Detection System provides
25+ Display Screens. Each screen provides real-time
information concerning the existing power quality,
past recorded events, & networking.
Capacitive touch buttons are utilized to maneuver
from screen to screen.
Network Connection - System Ethernet Port > to Hub > to PC
Connecting the system to a
network may be the simplest
method of connection.
The monitoring system will
automatically attempt to locate
an available network IP address
when connected/powered up.
The IP address is required to
remotely access the monitoring
system Web Server & web pages.
Pressing BACK and ENTER at the same time will jump directly to the systems Networking
Display Screen.
PC
Network Hub/Switch
SPD
Monitoring
System
J
20
Line & Neutral LEDs
Green = Normal Operation
Orange = Reduced Protection
Red (steady) = Protection Failure
Red (flashing) = Active Event
Service LED
Green = Normal Operation
Orange = Active Event
Red = Protection Failure
Installation, Operation and Maintenance Manual QS-70100 Rev 0, 1/2015
Page | 4
100%
100%
100%
Web Server
The advanced Transient Detection System
webpage contains all of the information
available on the LCD display as well as some
additional features. Various settings,
thresholds, & functions can be modified,
enabled, disabled, etc. using the systems
webpage/Ethernet function.
To open system webpage
Open a web browser and enter the systems IP
address (located on Display Screen) into the
address bar and press Enter. This will launch
the SPDs advanced Transient Detection
System webpage.
Emerson Network Power
Surge Protection
100 Emerson Parkway
Binghamton, NY 13905
800 288 6169 Phone (U.S. & Canada Only)
607 721 8840 (Outside U.S.)
607 722 8713 FAX
United States of America
Emerson Network Power
European Headquarters
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD)
Italy
39 049 9719 111 Phone
39 049 5841 257 FAX
Emerson Network Power Asia Pacific
29/F, The Orient Square Building
F. Ortigas Jr. Road, Ortigas Center
Pasig City 1605
Philippines
+63 2 687 6615
+63 2 730 9572 FAX
Technical Support
800 288 6169 Toll-Free
607 721 8840 Phone
607 722 8713 FAX
EmersonNetworkPower.com/Surge
While every precaution has been taken to ensure accuracy and
completeness in this literature, Emerson Network Power assumes
no responsibility, and disclaims all liability for damages resulting
from use of this information or for any errors or omissions.
© 2014 Emerson Network Power. All rights reserved throughout
the world. Specifications subject to change without notice.
All names referred to are trademarks or registered trademarks
of their respective owners.
QS-70100 (Rev03 1/15) Printed in USA
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4

Emerson Transient Detection System Installation guide

Type
Installation guide

Emerson Transient Detection System offers real-time power quality monitoring, event logging, and protection against damaging voltage surges. It measures and displays RMS voltages, frequency, crest factor, VTHD, voltage unbalance, and MOV health. It also logs power quality events, system events, and surge/transient, sag, swell, phase loss/outage, voltage interruption/dropout, voltage harmonics, neutral bond, overvoltage, temporary overvoltage, over/under frequency, and protection failure.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI