Reznor XBWS Installation guide

Category
Air filters
Type
Installation guide
INSTALLATION INSTRUCTIONS
EN ERGY RE COV ERY VEN TI LA TOR
Applies To Model XBWS When Used With Option AQ20
Side By Side Design
INSTALLATION INSTRUCTIONS FOR ROOFTOP STAND ALONE
ENERGY RECOVERY UNIT IN SIDE BY SIDE DESIGN
FORM RZ-NA-I-XBWS-AQ20
MAY 29, 2014
SUPERCEDES 09-27-13
SXX-2ZERV
PAGE 1
I - Ship ping and Pack ing List
Package contains:
1 — Energy Recovery Ventilator Assembly
I I - Ship ping Dam age
Check unit for shipping damage. Receiving party should
contact last carrier immediately if shipping damage is
found.
III - Gen eral
These instructions are intended as a general guide and do
not supersede local codes in any way. Authorities having
jurisdiction should be consulted before installation.
IV - Re quire ments
When installed, the unit must be electrically wired and
grounded in accordance with local codes or, in absence of
local codes, with the current National Electric Code,
ANSI/NFPA No. 70.
V - Ap pli ca tion
These Energy Recovery Ventilators (ERV) are used in a
down discharge manner equipped with field provided
balancing damper assembly through the roof. A roof
curb must be provided to Rooftop Systems specifications.
These wheels conserve energy by mixing warmer air with
cooler air in the following manner:
Re cov ery Wheel Mode
The Recovery Wheel mode is accomplished by two
blowers providing continuous exhaust of stale indoor air
and replacement by equal amount of outdoor air. Energy
recovery is achieved by slowly rotating the energy
recovery wheel within the cassette frame work. In winter,
the ERV adsorbs heat and moisture from the exhaust air
stream during one half of a complete rotation and gives
them back to the cold, drier intake air supply during the
other half rotation. In summer, the process is automatically
reversed. Heat and moisture are absorbed from incoming
fresh air supply and transferred to the exhaust air stream.
This process allows outdoor air ventilation rates to be
increased by factors of three or more without additional
energy penalty or increase in size of heating or air
conditioning systems.
VI - Rig ging Unit For Lift ing
1. Maximum weight of unit is — Varies per Series
{300-1200 Lbs.} (Crated)
2. Remove crating.
3. All panels must be in place for rigging.
4. Remove hood assemblies from door marked filter
access.
5. Place 2" filter in filter rack and replace filter access
door.
6. Roof curb gasket must be applied to all top surfaces of
the curb. (Refer to roof curb installation instruction.)
7. Forklift channels must be removed from the base of
ERV before setting unit on curb. See Figure 1.
8. Position unit on roof curb and provide service access
to ERV control access door and wheel.
CAUTION
Danger of sharp metallic edges. Can cause injury.
Take care when servicing unit to avoid accidental
contact with sharp edges.
WARNING
Electric shock hazard. Can cause injury
or death. Before attempting to perform
any service or maintenance, turn the
electrical power to unit OFF at
disconnect switch(es). Unit may have
multiple power supplies.
FIGURE 1
FORKLIFT CHANNELS
Energy recovery COMPONENT certified
to the AHRI Air-to-Air Energy Recovery
Ventilation Equipment Certification
Program in accordance with AHRI
Standard 1060-2000. Actual performance
in packaged equipment may vary.
ETL Certified per UL 1995
and CSA 22.2
VII - In stal la tion
Fresh Air Hood As sem bly (See Fig ure 2)
1. Secure hood sides (A and C) to Hood top (B) using the
supplied #10 x ½ screws.
2. Secure filter channels (F and D) to hood sides using
the supplied #10 x ½ screws.
3. Secure hood bottom (E) to the inside of the hood sides
using the supplied #10 x ½ screws.
4. Slide the fresh air filter (H) into the tracks created by
the front of the hood sides and the filter channels.
5. Secure the filter panel (G) to the hood sides. Slide the
filter panel under the front flange of the hood top.
6. Install fresh air hood on ERV.
7. Install barometric exhaust hood over exhaust blower
outlet.
8. Connect field duct connections to duct flanges on back
of ERV. Seal duct connections.
9. Remove ERV control access panel to connect field
wiring.
10. Route class II low voltage wire (3 conductor) from
thermostat or energy management through small
bushing in end panel of ERV. See wiring diagram.
a. Thermostat (dependent) - connect in parallel at
rooftop unit with “G”, “C” and “W”. Then connect
matching color at terminal 1, 2, and 3 respectively
on ERV circuit board.
b. Energy Management - provide +24 VAC to “1” and
common, 24 VAC to “2’ terminals on ERV circuit
board.
c. Thermostat (dedicated) - splice into +24 vac (blue
wire) at (control circuit board) transformer
connection run wire to "R" terminal. Then run
another wire from "G" terminal to ERV (control
circuit board) terminal block #1.
11. All electrical connections must conform to any local
codes and current National Electric Codes (NEC) and
Canadian Electric Codes (CEC). Refer closely to unit
wiring diagram in unit and/or in these instructions for
proper wiring connections.
12. Refer to the unit nameplate for minimum circuit
ampacity (MCA) and maximum overcurrent protection
size (fuse).
13. Electrical data is listed on unit rating plate and motor
name plates.
14. Connect line voltage power supply to ERV fuse block
in control box of unit from disconnect switch. See
wiring diagram.
15. Ground unit with a suitable ground connection either
through unit supply wiring or an earth ground.
Note: Unit voltage entries must be sealed weather
tight after wiring is complete.
16. Remove motor access panels. Locate belts fastened
to blower assembly. Install belt onto motor and blower
pulley. Adjust motor sheave to correct blower RPM for
CFM and external static pressure requirements. See
charts in this instruction. Multiple pulley arrangements
are available to meet the entire range.
PAGE 2
Caution: Blower speed must be adjusted for the given
external static pressure and airflow (CFM)
requirements. If blower speed is not adjusted
for conditions, possible motor over loading can
occur.
17. Replace access panel onto the ERV unit and secure.
18. Restore power to unit.
19. Cleanup once unit is operating properly, caulk any
open joints, holes or seams to make the units
completely air and water tight.
20-Leave this instruction manual with owner or in an
envelope to be kept near unit.
VIII - Op er a tion
How It Works
The unit contains an Energy Recovery Wheel (ERW) that
is a new concept in rotary air-to-air heat exchangers.
Designed as a packaged unit for ease of installation and
maintenance, only the connection of electrical power is
required to make the system operational.
When slowly rotating through counter flowing exhaust and
fresh air streams the ERW adsorbs sensible heat and
latent heat from the warmer air stream and transfer this
total energy to the cooler air stream during the second half
of its rotating cycle. Rotating at 50-60 revolutions per
minute, the wheel provides constant flow of energy from
warmer to cooler air stream. The large energy transfer
surface and laminar flow through the wheel causes this
constant flow of recovered energy to represent up to 85%
of the difference in total energy contained within the two air
streams.
Sensible and latent heat are the two components of total
heat. Sensible heat is energy contained in dry air and latent
heat is the energy contained within the moisture of the air.
The latent heat load from the outdoor fresh air on an air
conditioning system can often be two to three times that of
the sensible heat load and in the winter it is a significant
part of a humidification heat load.
During both the summer and winter, the ERW transfers
moisture entirely in the vapor phase. This eliminates wet
surfaces that retain dust and promote fungal growth as well
as the need for a condensate pan and drain to carry water.
(E)
(B)
(C)
(A)
(F)
(D)
(G)
(H)
FIGURE 2
ASSEMBLED FRESH AIR HOOD
PAGE 3
Because it is constantly rotating when in the air stream, the
ERV is always being cleaned by air, first in one direction
then the other. Because it is always dry, dust or other
particles impinging on the surface during one half cycle,
are readily removed during the next half cycle.
During the heating season, when outdoor air temperatures
are below 15
o
F, it is recommended to use the (optional)
low ambient kit (field installed).
Low Ambient Kit is appropriate for climates with limited
HVAC system operation when outdoor temperatures are
below 10
o
F.
The frost threshold is the outdoor temperature at which
frost will begin to form on the ERV wheel. For Energy
Recovery Ventilators, the frost threshold is typically below
10
o
F. Frost threshold is dependent on indoor temperature
and humidify. The table shows how the frost threshold
temperatures vary depending on indoor conditions
FROST THRESH OLD TEM PER A TURE
IN DOOR RH AT 70
o
F
FROST THRESH OLD
TEM PER A TURE
20% 0
o
F
30% 5
o
F
40% 10
o
F
Because Energy Recovery Ventilators have a low frost
threshold, frost control options are not necessary in many
climates. Where outdoor temperatures may drop below
the frost threshold during the ERV operational hours,
exhaust only frost control option is available.
Low Am bi ent Kit (Op tional)
Low Ambient Kit turns off the supply blower when outdoor
temperatures fall below the frost threshold. The exhaust
only thermostat set points are field adjustable. Supply fan
operation is automatically restored when the exhaust air
temperature rises above the thermostat set point.
Provisions for introducing make-up air into the building
when the supply blower is off to avoid depressurization
should be considered.
Re cov ery Wheel Mode
On a thermostat call for blower operation in heating,
cooling or continuous blower, the ERW will rotate between
fresh air and exhaust air streams. Both the fresh air and
exhaust air blowers will also be operating to overcome the
air resistance of the ERV.
IX - Sys tem Check
1. Disconnect main power.
2. Turn to “Cont” for blower operation on thermostat
controlled models.
3. Restore power to unit. Observe ERV wheel rotation
and both fresh air and exhaust air blowers will
operating.
Note: If Low ambient kit is used the jumper between
TB37-5 & TB37-6 should be removed. Also if
system check out is being conducted at low
ambient temperatures, technician should be
aware that this kit can cause system not to
operate.
4. Verify that the ERV (3) three phase blower motors are
phased sequentially ensuring correct rotation and
operation.
a. Disconnect power.
b. Reverse any two field power leads to the ERV.
c. Reapply power.
5. Verify that both blower motors are operating under
their full load AMP rating (FLA). The FLA can be found
on each motor and the unit nameplate
A - Re turn Damper Set tings
Manually adjust position of field installed dampers to
balance air flow.
B - Air Flow / Blower Speed Ad just ment
Blower speed selection is accomplished by changing the
sheave setting on both fresh air and exhaust air blowers.
To set ERV for the required air flow (CFM), the external
static pressure applied to the ERV (duct static) must be
known. See the CFM vs External Static Pressure chart for
the appropriate unit to determine the correct blower RPM
for the specified CFM and External Static Pressure.
After blower speed adjustments have been made. Ensure
that when the belt is replaced it is tensioned correctly. The
motor mounting plate can be adjusted to tension the belt. If
using a belt tension checker, adjust the span to the
appropriate setting and check the belt defection force. The
belt deflection force should be between 5-8 lbs or the
lowest tension at which the belt will not slip under peak load
conditions.
5. Disconnect main power to unit before making
adjustment to economizer and/or ERV unit.
6. Replace ERV control access cover.
7. Set thermostat to normal operating position.
8. Restore power to unit.
X - Main te nance
1. All motors use prelubricated sealed bearings; no
further lubrication is necessary.
2. Make visual inspection of motors, belts and wheel
rotating bearings during routine maintenance.
3. Eight pie-shaped segments, are seated on stops
between the segment retainer which pivots on the
wheel rim and secured to the hub and rim of wheel.
Annual inspection of the self cleaning wheel is
recommended. With power disconnected, remove
ERV access panels (rear) and unplug [J150 & P150]
(Refer to wiring diagram in this instruction
manual). Remove segment and wash with water
and/or mild detergent.
4. To install wheel segments follow steps A through E .
See Figure 3. Reverse procedure for segment
removal.
a. Unlock two segment retainers (one on each side of
the selected segment opening.
b. With the embedded stiffener facing the motor side,
insert the nose of the segment between the hub
plates.
c. Holding segment by the two outer corners, press
the segment towards the center of the wheel and
inwards against the spoke flanges. If hand
pressure does not fully seat the segment, insert
the flat tip of a screw driver between the wheel rim
and outer corners of the segment and apply
downward force while guiding the segment into
place.
PAGE 4
d. Close and latch each segment retainer under
segment retaining catch.
e. Slowly rotate the wheel 180
o
. Install the second
segment opposite the first for counterbalance.
Rotate the two installed segments 90
o
to balance
the wheel while the third segment is installed.
Rotate the wheel 180
o
again to install the fourth
segment opposite the third. Repeat this sequence
with the remaining four segments.
XI - Pul ley Kit In stal la tion
The units are shipped from the factory at the low static
setting. Pulley kits are available for the medium and high
static settings. To install a pulley kit.
1. Check content of pulley kit, if pulley kit contains:
a. An adjustable sheave and a fixed pitch pulley then
remove belt and both motor and blower pulley
b. An adjustable sheave then remove the motor
pulley.
c. A fixed pitch pulley then remove the blower pulley.
2. Replace pulley(s) with the pulley(s) from pulley kit.
Make sure each pulley is installed with a key. Tighten
the set screw on the pulley(s) to 100 in.lb.
3. Install the belt that came with the pulley kit. Tension
belt as explained in the blower speed adjustment
section.
4. Check the speed of the blower. Adjust the motor
sheave to increase or decrease the speed of the
blower. See blower adjustment section.
B
C
A
D
E
D
HUB
SEGMENT
FIGURE 3
SPOKE
SEGMENT RETAINER CATCH
WHEEL RIM
SEGMENT RETAINER
PAGE 5
Stand Alone ERV’S For Side by Side Duct Arrangements
A
B
C
D
D
E
I
G
J
F
Fea tures and Notes
1. Stand alone design allows higher levels of outdoor
air to be introduced into the a/c space.
2. Static test ports provided to verify intake and
exhaust CFM.
3. Balancing damper(s) is field provided when connected
to ductwork. System will not operate properly without
balancing damper.
4. Roof curbs are available for the ERV’s.
5. See blower performance charts for airflow at various
E.S.P..
6. Filter rack with 2” pleated filters included.
K
H
H
SUPPLY DUCT FLANGE OPENING
EXHAUST DUCT FLANGE OPENING
ERV Data Di men sional Data
Size CFM Range A B C D E F G H I J K
11 300-1100 44.75 32.13 33.50 11.00 27.00 4.00 4.25 2.88 2.50 20.75 14.38
20 1200-2000 54.38 37.25 37.50 12.00 30.00 1.63 5.13 4.06 1.63 20.75 17.50
28 1200-2800 52.25 42.62 43.56 14.00 32.00 8.69 5.25 4.25 2.88 20.75 25.50
36 2000-3600 60.00 46.69 57.37 16.50 39.50 12.00 5.50 4.05 5.88 20.75 25.50
46 3000-4600 60.00 52.69 57.37 16.50 39.50 12.00 8.69 5.50 5.88 20.75 28.06
62 4600-6200 72.00 70.88 63.63 19.50 39.50 17.53 14.50 8.70 6.60 20.75 37.75
Roof Curbs (Op tion Codes)
Size 14" 24"
11 CJ51-11 CJ52-11
20 CJ51-20 CJ52-20
28 CJ51-28 CJ52-28
36 CJ51-36 CJ52-36
46 CJ51-46 CJ52-46
62 CJ51-62 CJ52-62
PAGE 6
Notes:
1. Re move jumper to in stall field op tional low am bi ent switch.
2. Se lec tive volt age ter mi nal for proper unit volt age
3. Op tional low am bi ent switch.
4. Op tional mo tor ized in take damper.
5. Op tional Stop, Start and Jog Con trol (Cli mate Smart).
6. For en ergy man age ment sys tems con nect +24v to "G"
and com mon 24v to "C".
7. Op tional mo tor ized ex haust damper.
8. Op tional wheel ro ta tion sen sor.
9. Op tional smoke de tec tor.
S11-21-2ZERV
COMPONENT CODE
A131 Fixed Re lay Board
B26 Mo tor, Ex haust Air
B27 Mo tor, In take Air
B28 Mo tor, Desiccant Wheel
B30 Mo tor, Damper In take (Op tional)
B31 Mo tor, Damper Ex haust (Op tional)
C23 Ca pac i tor, Wheel Mo tor
C25 Ca pac i tor, Ex haust Air
C26 Ca pac i tor, In take Air
F29 Fuse
J48 Jack, Con trol Box (In take Air)
J50 Jack, Con trol Box (Wheel)
J51 Jack, Con trol Box (Ex haust Air)
J56 Jack, Con trol Box (Damper)
J148 Jack, In take Air Mo tor Har ness
P161 Plug, Damper Ex haust Mo tor Har ness
RS-1 Ro ta tion Sen sor (Op tional)
S26 Switch, Low Am bi ent (Op tional)
S51 Switch, Door
S52 Switch, Damper In take
S53 Switch, Damper Ex haust
SD Smoke De tec tor (Op tional)
SSJ Cli mate Smart Board (Op tional)
T27 Trans former, Con trol
T28 Trans former, Step-down (Op tional)
TB37 Ter mi nal Block (Low Volt age)
TB39 Ter mi nal Block (Mon i tor ing)
WHL Re lay, Wheel Mo tor
J150 Jack, Wheel Mo tor Har ness
J151 Jack, Ex haust Air Mo tor Har ness
J160 Jack, Damper In take Mo tor Har ness
J161 Jack, Damper Ex haust Mo tor Har ness
K163 Contactor, Ex haust Air Mo tor
K164 Contactor, In take Air Mo tor
MPD-1 Miss ing Pulse De tec tor Board (Op tional)
P48 Plug, In take Air Mo tor Har ness
P50 Plug, Wheel Mo tor Har ness
P51 Plug, Ex haust Air Mo tor Har ness
P56 Plug, Damper Mo tor Har ness
P148 Plug, In take Air Mo tor
P150 Plug, Wheel Mo tor
P151 Plug, Ex haust Air Mo tor
P160 Plug, Damper In take Mo tor Har ness
WIRE COLOR
CODE
BK Black
BL Blue
GR Green
GY Gray
OR Orange
PK Pink
RD Red
WT White
YL Yel low
PAGE 7
Unit#: 01-S11-02XX-21
Des ic cant Wheel for Roof top Unit
208- 230V (1 PH)
ERV UNIT WIR ING DIAGRAM
:setoN
.1 .hctiws tn ei bma wol lanoi tpo dleif llat sni ot repmuj evo meR
.2 eg atlov tinu reporp rof la ni mret eg atlov evi tce leS
.3 .hctiws tn ei bma wol lanoi tpO
.4 .repmad eka tni dez iro tom lanoi tpO
.5 .)tramS eta milC( lor tnoC goJ dna tratS ,potS lanoi tpO
.6 "G" ot v42+ tce nnoc sme tsys tne meg anam ygr ene roF
."C" ot v42 no mmoc dna
.7 .repmad tsua hxe dez iro tom lanoi tpO
.8 .ro snes noi ta tor leehw lanoi tpO
.9 .ro tce ted ekoms lanoi tpO
PAGE 8
Notes:
1. Re move jumper to in stall field op tional low am bi ent switch.
2. Step-down trans former as sem bly for 460/575 volt units.
3. Se lec tive volt age ter mi nal for proper unit volt age
4. Op tional low am bi ent switch.
5. Op tional mo tor ized in take damper.
6. Op tional Stop, Start and Jog Con trol (Cli mate Smart).
7. For en ergy man age ment sys tems con nect +24v to "G" and com mon 24v to "C".
8. Op tional mo tor ized ex haust damper.
9. Op tional wheel ro ta tion sen sor.
10. Op tional smoke de tec tor.
S11-S62-2ZERV
COMPONENT CODE
A131 Fixed Re lay Board
B26 Mo tor, Ex haust Air
B27 Mo tor, In take Air
B28 Mo tor, Des ic cant Wheel
B30 Mo tor, Damper In take (Op tional)
B31 Mo tor, Damper Ex haust (Op tional)
C23 Ca paci tor, Wheel Mo tor
F29 Fuse
J48 Jack, Con trol Box (In take Air)
J50 Jack, Con trol Box (Wheel)
J51 Jack, Con trol Box (Ex haust Air)
J56 Jack, Con trol Box (Damper)
J148 Jack, In take Air Mo tor Har ness
J150 Jack, Wheel Mo tor Har ness
J151 Jack, Ex haust Air Mo tor Har ness
P161 Plug, Damper Ex haust Mo tor Harness
RS-1 Ro ta tion Sen sor (Op tional)
S26 Switch, Low Am bi ent (Op tional)
S51 Switch, Door
S52 Switch, Damper Intake
S53 Switch, Damper Exhaust
SD Smoke De tec tor (Op tional)
SSJ Cli mate Smart Board (Op tional)
T27 Trans former, Con trol
T28 Trans former, Step- down (Op tional)
TB37 Ter mi nal Block (Low Volt age)
TB39 Ter mi nal Block (Mon i tor ing)
WHL Re lay, Wheel Motor
J152 Jack, Trans former (High Volt age)
J160 Jack, Damper In take Mo tor Har ness
J161 Jack, Damper Ex haust Mo tor Har ness
K163 Contactor, Ex haust Air Mo tor
K164 Contactor, In take Air Mo tor
MPD-1 Miss ing Pulse De tec tor Board (Op tional)
P48
Plug, In take Air Mo tor Har ness
P50
Plug, Wheel Mo tor Har ness
P51 Plug, Ex haust Air Mo tor Har ness
P56 Plug, Damper Mo tor Har ness
P148 Plug, In take Air Mo tor
P150 Plug, Wheel Mo tor
P151 Plug, Ex haust Air Mo tor
P152 Plug, Trans former (High Volt age)
P160 Plug, Damper In take Mo tor Harness
WIRE COLOR
CODE
BK Black
BL Blue
GR Green
GY Gray
OR Orange
PK Pink
RD Red
WT White
YL Yel low
PAGE 9
Unit#: 01-S11-S62-02XX-23 thru -43
Des ic cant Wheel for Roof top Unit
208- 230/460/575V (3 PH)
ERV UNIT WIR ING DIAGRAM
:setoN
.1 .hctiws tn ei bma wol lanoi tpo dleif llat sni ot repmuj evo meR
.2 .stinu tlov 575/064 rof yl bme ssa remro fsnart nwod-petS
.3 eg atlov tinu reporp rof la ni mret eg atlov evi tce leS
.4 .hctiws tn ei bma wol lanoi tpO
.5 .repmad eka tni dez iro tom lanoi tpO
.6 .)tramS eta milC( lor tnoC goJ dna tratS ,potS lanoi tpO
.7 ."C" ot v42 no mmoc dna "G" ot v42+ tce nnoc sme tsys tne meg anam ygr ene roF
.8 .repmad tsua hxe dez iro tom lanoi tpO
.9 .ro snes noi ta tor leehw lanoi tpO
.01 .ro tce ted ekoms lanoi tpO
PAGE 10
Mist Elimi na tor Fil ter in In take Hood (2HP)
Ex ter nal Static Pres sure (in wa ter)
0 0.25 0.5 0.75 1 1.25 1.5
CFM
1200 1065 1285 1375 1415 1495 1580 1685
1400 1140 1330 1410 1440 1555 1660 1760
1600 1290 1400 1480 1545 1670 1745 1835
1800 1395 1470 1540 1665 1735 1800 1880
2000 1460 1530 1650 1725 1795 1870 1960
Ba ro met ric Hood, 2" Pleated Fil ters (2HP)
Ex ter nal Static Pres sure (in wa ter)
0 0.25 0.5 0.75 1 1.25 1.5
CFM
1200 1175 1290 1430 1520 1680 1765 1850
1400 1245 1425 1515 1675 1755 1830 1920
1600 1400 1505 1670 1750 1825 1910 1980
1800 1495 1660 1740 1820 1900 1975 2090
2000 1645 1730 1815 1895 1965 2080 2170
SUP PLY
Blower RPM for XBWS20-AQ20
EXHAUST
Notes:
1. Drive losses included in the above tables.
2. Performance can vary depending on ambient conditions
3. Blower RPMs are for reference only
RPM Range
Low 1000- 1300 Stan dard Unit
Me dium 1300- 1750 Op tional Kit
High 1750- 2200 Op tional Kit
SUP PLY
Blower RPM for XBWS11-AQ20
EXHAUST
Notes:
1. Drive losses included in the above tables.
2. Performance can vary depending on ambient conditions
3. Blower RPMs are for reference only
RPM Range
Low 1000- 1300 Stan dard Unit
Me dium 1300- 1700 Op tional Kit
High 1750-2200 Op tional Kit
Ba ro met ric Hood, 2" Pleated Fil ters (1.5HP)
Ex ter nal Static Pres sure (in wa ter)
0 0.25 0.5 0.75 1 1.25 1.5
CFM
300 N/A N/A 1150 1285 1415 1515 1640
500 N/A 1145 1275 1410 1510 1545 1720
700 1140 1270 1405 1505 1590 1715 1815
900 1320 1435 1585 1665 1705 1810 1930
1100 1495 1580 1660 1755 1880 N/A N/A
Mist Elimi na tor Fil ter in In take Hood (1.5HP)
Ex ter nal Static Pres sure (in wa ter)
0 0.25 0.5 0.75 1 1.25 1.5
CFM
300 N/A N/A 1020 1205 1365 1480 1590
500 N/A 1015 1200 1320 1460 1565 1670
700 990 1190 1315 1455 1560 1665 1715
900 1150 1310 1450 1555 1660 1680 1795
1100 1305 1440 1550 1655 1740 1815 1895
PAGE 11
Mist Elimi na tor Fil ter in In take Hood (3HP)
Ex ter nal Static Pres sure (in wa ter)
0 0.25 0.5 0.75 1 1.25 1.5
CFM
2000 815 925 1020 1105 1155 1255 1325
2400 920 1060 1130 1215 1250 1355 1385
2800 1010 1140 1240 1285 1370 1425 1470
3200 1125 1235 1340 1385 1455 1465 N/A
3600 1225 1375 1440 1460 1500 N/A N/A
Ba ro met ric Hood, 2" Pleated Fil ters (3HP)
Ex ter nal Static Pres sure (in wa ter)
0 0.25 0.5 0.75 1 1.25 1.5
CFM
2000 755 890 970 1060 1125 1215 1280
2400 985 1035 1085 1140 1240 1275 1325
2800 1020 1115 1175 1230 1270 1335 1370
3200 1105 1200 1225 1285 1300 1390 1430
3600 1155 1265 1295 1335 1385 N/A N/A
SUP PLY
Blower RPM for XBWS36-AQ20
EXHAUST
RPM Range
Low 700-1025 Stan dard Unit
Me dium 1030-1305 Op tional Kit
High 1325-1575 Op tional Kit
SUP PLY
Blower RPM for XBWS28-AQ20
EXHAUST
RPM Range
Low 950-1320 Stan dard Unit
Me dium 1325-1565 Op tional Kit
High 1570-1880 Op tional Kit
Mist Elimi na tor Fil ter in In take Hood (3HP)
Ex ter nal Static Pres sure (in wa ter)
0 0.25 0.5 0.75 1 1.25 1.5
CFM
1200 N/A 955 1070 1210 1370 1465 1550
1600 N/A 1065 1205 1305 1460 1540 1595
2000 1060 1200 1290 1445 1530 1585 1680
2400 1190 1335 1440 1490 1575 1670 1755
2800 1300 1460 1550 1645 1705 1750 1800
Notes:
1. Drive losses included in the above tables.
2. Performance can vary depending on ambient conditions
3. Blower RPMs are for reference only
Notes:
1. Drive losses included in the above tables.
2. Performance can vary depending on ambient conditions
3. Blower RPMs are for reference only
Ba ro met ric Hood, 2" Pleated Fil ters (3HP)
Ex ter nal Static Pres sure (in wa ter)
0 0.25 0.5 0.75 1 1.25 1.5
CFM
1200 N/A N/A 1025 1170 1270 1355 1400
1600 N/A 1020 1155 1240 1330 1390 1490
2000 1015 1150 1235 1325 1380 1475 1590
2400 1140 1285 1365 1420 1510 1595 1640
2800 1280 1345 1455 1540 1575 1670 1745
PAGE 12
Mist Elimi na tor Fil ter in In take Hood (5HP)
Ex ter nal Static Pres sure (in wa ter)
0 0.25 0.5 0.75 1 1.25 1.5
CFM
4600 795 900 1030 1075 1160 1220 1255
5000 855 920 1070 1130 1190 1250 1275
5400 880 950 1095 1155 1245 1270 1290
5800 915 1035 1115 1175 1255 1280 N/A
6200 985 1080 1135 1225 1265 N/A N/A
Ba ro met ric Hood, 2" Pleated Fil ters (5HP)
Ex ter nal Static Pres sure (in wa ter)
0 0.25 0.5 0.75 1 1.25 1.5
CFM
4600 705 885 985 1045 1100 1155 1215
5000 825 950 1025 1095 1150 1210 1245
5400 875 980 1080 1140 1190 1240 1275
5800 935 995 1130 1180 1230 N/A N/A
6200 985 1095 1165 N/A N/A N/A N/A
SUP PLY
Blower RPM for XBW62S-AQ20
EXHAUST
Notes:
1. Drive losses included in the above tables.
2. Performance can vary depending on ambient conditions
3. Blower RPMs are for reference only
RPM Range
Low 700-900 Stan dard Unit
Me dium 900-1100 Op tional Kit
High 1100-1300 Op tional Kit
SUP PLY
Blower RPM for XBWS46-AQ20
EXHAUST
Notes:
1. Drive losses included in the above tables.
2. Performance can vary depending on ambient conditions
3. Blower RPMs are for reference only
RPM Range
Low 780- 1020 Stan dard Unit
Me dium 1000- 1315 Op tional Kit
High 1315- 1700 Op tional Kit
Mist Elimi na tor Fil ter in In take Hood (5HP)
Ex ter nal Static Pres sure (in wa ter)
0 0.25 0.5 0.75 1 1.25 1.5
CFM
3000 965 1085 1150 1230 1295 1345 1420
3400 1035 1145 1250 1290 1335 1415 1475
3800 1120 1245 1285 1315 1440 1470 1535
4200 1215 1305 1355 1430 1465 1530 1595
4600 1300 1375 1450 1460 1540 1590 1650
Ba ro met ric Hood, 2" Pleated Fil ters (5HP)
Ex ter nal Static Pres sure (in wa ter)
0 0.25 0.5 0.75 1 1.25 1.5
CFM
3000 1010 1105 1195 1255 1300 1375 1415
3400 1100 1190 1250 1320 1370 1410 1480
3800 1185 1245 1360 1410 1440 1475 1540
4200 1240 1355 1425 1465 1530 1590 1630
4600 1345 1410 1485 1520 1585 1650 1700
PAGE 13
Notes
PAGE 14
Notes
PAGE 15
Notes
START UP INFORMATION SHEET
VOLTAGE - ERV UNIT
In com ing Volt age L1-L2 L1-L3 L2-L3
Run ning Volt age L1-L2 L 1-L3 L2-L3
Sec ond ary Volt age C (black) to G (green) Volts*
C (black) to W (white) Volts*
* With ther mo stat call ing.
AM PER AGE - ERV MO TORS
In take Mo tor: Nom i nal HP Rated Amps Run ning Amps
Ex haust Mo tor: Nom i nal HP Rated Amps Run ning Amps
Wheel Mo tor: Nom i nal HP Rated Amps Run ning Amps
AIR FLOW
In take De sign CFM Pres sure Drop Cal cu lated CFM
Ex haust De sign CFM Pres sure Drop Cal cu lated CFM
Amb. db Temp Re turn Air db Temp* Tem pered Air db Temp*
Amb. wb Temp Re turn Air wb Temp* Tem pered Air wbTemp*
* Mea sure af ter 15 min utes of run time
IN STAL LA TION CHECK LIST
ERV Model # Se rial #
Owner Owner Phone #
Owner Ad dress
In stall ing Con trac tor Start Up Me chanic
q Inspect the unit for transit damage and report any damage on the carrier’s freight bill.
q Check model number to insure it matches the job requirements.
q Install field accessories and unit adapter panels as required. Follow accessory and unit installation manuals.
q Verify field wiring, including the wiring to any accessories.
q Check all multi-tap transformers, to insure they are set to the proper incoming voltage.
q Verify correct belt tension, as well as the belt/pulley alignment. Tighten if needed.
q Prior to energizing the unit, inspect all the electrical connections.
q Power the unit. Bump the motor contactor to check rotation. Three phase motors are synchronized at the
factory. If blower motor fans are running backwards, de-energize power to the unit, then swap two of the three
incoming electrical lines to obtain proper phasing. Re-check.
q Perform all start up procedures outlined in the installation manual shipped with the unit.
q Fill in the Start Up Information as outlined on the opposite side of this sheet.
q Provide owner with information packet. Explain the thermostat and unit operation.
1-800-695-1901; www.ReznorHVAC.com
©2014 Reznor, LLC. All rights reserved. Printed in U.S.A.
Reznor® is registered in at least the United States.
All other marks are the property of their respective organizations.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16

Reznor XBWS Installation guide

Category
Air filters
Type
Installation guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI