Ensy AHU-200 KV SLIM User Manual And Installation Manual

Type
User Manual And Installation Manual

This manual is also suitable for

User manual and
Installation Guide
AHU-200 KV SLIM
AHU-200 KH SLIM
3938292Rev1:19.04.2017.KJK
Wereservetherighttochangetechnicaldatawithoutnotice.http://www.ensy.no Side1
3938292Rev1:19.04.2017.KJK
Wereservetherighttochangetechnicaldatawithoutnotice.http://www.ensy.no Side2
Usermanual.Pages2til15
(Onpages,2‐6thepicturesshowsAHU200KVSLIM)
Becarefulthatthedoorcan"bestuck"inthesealingonthehatch.
Foreasierlooseningofthehatch,releaseitfirstinonecorneratthetop.
Tooperatethisproductpeopleshouldhave
necessaryskills,orunderthesupervision
ofaqualifiedperson.
Tellchildrennottoplaywiththeappliance.
Ifyouaregoingintotheunitthenyoufirsthavetoremove
anykitchenfurniturefrontdoor,ifsoismountedonfront
ofunit.
Onthesepictures,youcan
seetheventilationunitwith
whitecoatedcookerhood.
Therearealsovariantswithhoodsinbrushedstainless
steel.
Toopenthefronthatchyoufirsthavetountightenthose
fourscrewsyoufindineachcorneroftheunit.
Whenhatchis
tobemountedbackontheunittrytousealmostsametorqueonallfourscrews.
Thenputthekitchenfurniturefrontdoorbackonplace.
3938292Rev1:19.04.2017.KJK
Wereservetherighttochangetechnicaldatawithoutnotice.http://www.ensy.no Side3
Beforeanyaccessintotheelectrical
connectionsboxes,power
mustbedisconnectedby
pullingouttheplugfromthe
socket.
Onlyauthorizedpersonsisallowedtoenter
intotheelectricalconnectionboxes.
Ifanyelectricalcomponentsaredamaged,
theymustbereplacedbythemanufacturer,
dealeroraqualifiedpersonin
ordertoavoid
dangeroussituations.
Adjustmentoftheunit.
Ahumiditysensoris,fromfactory,mountedinsidetheunit.Itis
setto“0”thatmeansitissettonotactive.
Afterstartup,wheretheunitisplacedintoanewbuildingwithhighhumidity,
youcanletthishumiditysensorbeturnedoffforaperiodto
avoidthefullspeed
ofthefanatnight.Togetthehumiditysensortooperateasintended,youneedatonetimetoputit
active.Thanyouneedtosettheswitchinposition"1".
Iftheventilationunitisplacedinahousewithouthighhumidity,you
shouldswitchtoposition"1"
afteryouputtingventilationunitintooperation.Thisswitchwillalsoaffectanyextraexternal
humiditysensorthatispluggedintothedevice.
Adjustingthehumiditysensor.
Ifitisnecessarytoadjustthesensitivityofthehumiditysensorthenyoujustcanremovetheblack
plugandyouthencanseetheadjustingknobandtheRH%scale.
Ifaneedforbetter
insightordonotsee
theadjustmentscale
sufficientsoone
shouldremove
the
entirecoverofthis
controlboard.
3938292Rev1:19.04.2017.KJK
Wereservetherighttochangetechnicaldatawithoutnotice.http://www.ensy.no Side4
Thesensorissetto80%RHfromfactory.
Ifyoudoadjustments,thisonlyaffectthesensorintegated
insidetheunit.
Thesensitivityfortheintegratedsensoryoucanadjustfrom
50%(low)to90%(high)inaccordancetowhataretheneed.
Thearrowpointsthevaluechosen.
Ifyouhaveasecondexternalsensorthatmeansyouneedto
adjustthatonefromitssettings.
Replacethecoverand/orplugafterfinishadjusting.
Replacingthefilter.
Thefiltersshouldbereplacedevery6.9.
or12.months.
Shouldbeextractedwithoutuseofany
tools.
Remembertoenterthecontrolpanel
menu(4.3Filter)andpressFilterOK
afterthefiltershasbeenreplaced.
Toguaranteeoptimalpropertiesofthe
ventilationunit,usetheoriginalfilters
fromEnSy.Theuseofspuriousfilterswill
limitthewarrantyontheproduct.
Ensyartnumberforfiltersetis:
0114608502
SETFILTREENSYAHU200+300B.F7:120x280x94
3938292Rev1:19.04.2017.KJK
Wereservetherighttochangetechnicaldatawithoutnotice.http://www.ensy.no Side5
Cleaningthefans.
Thismustbedonebyaqualified
person.
Beforeremovingfansthemainpower
mustbedisconnectedbypullingout
themainsupplyplugfromthesocket,
orfanstobeprogrammedtoposition
AVorOFF
Disconnectthe3poleand5pole
plugs.
Thefanscanbe
pulledoutofthe
ventilationunitwithouttheneedfor
anytools.
Cleanwithmildsoapandwater
Maintenanceandcleaningof
rotaryheatexchanger
.
Thismustbedonebyaqualified
person.
Disconnectthe3poleplug.
Canbepulledoutoftheventilation
unitwithouttheneedforanytools.
Tonotscratchthecookerhoodsoyou
shouldcoverthisbeforeyoupullout
therotaryheatexchanger.
3938292Rev1:19.04.2017.KJK
Wereservetherighttochangetechnicaldatawithoutnotice.http://www.ensy.no Side6
Rotorexchangercaneasilybe
removedforcleaningbydissolving
the12screwsthatholdit
together.
Cleanpartswithmildsoapand
water
Donotexposethe
rotormotoror
connectorfor
moisture.
Theexchangeryoualsocancleanwithmildsoapandwater.Donotuseammonia
containingdetergent,asthiswillpreyonanddiscoloraluminuminrotaryheatexchanger.
Flushedwithhandshowerandblowgentlycleanwithcompressedair.
Ensurethatthescrewsaretightenedsufficientlysothattheydonotcomelooseduringoperation.
Preferablyuseascrewdrivertotightthescrews.If
useofelectricalscrewdriver,makesurethatyou
uselowtorquetopreventdestroyingthethreadsinthesheetmetalparts.
Tomakesurethatthedrivebeltcanadjustitselfintocorrectpositionyoumustrotatetheexchanger
somefewturns.
Theninsertbackintotheventilationunit.Besure
thatrotorexchangerisproperlyinsertedinallthe
guidesinsidetheunit.Ifnot,thiscanleadtovibrationinthesystemandinternalairleakintheunit.
3938292Rev1:19.04.2017.KJK
Wereservetherighttochangetechnicaldatawithoutnotice.http://www.ensy.no Side7
Operation of kitchen hood
ON/OFFswitchfordownlights.
Usingthedamperinakitchenhood.

Nofunction Opensdamper. Maxtimeontimer
Timeractivated 60min
Replacingthelampandtransformeronthecookerhood
Turnoffthepowerbefore
replacingthedownlight.
Ifthelightisnotworkingthenyou
mustreplacetheentirelight
socketandtransformer.To
replacetheusermustfirstremove
thefourblankingplugsandthen
loosenfourscrewstoreleasethe
entirecover.
Compressthespringwithfingers
tomoreeasilyslidinglightsocket
outthrough
cover.
Theplugsthatisbetweenlight
andtransformercanbepulled
apart.
Theswitchhasa
springretraction
andwillnotwork
untilithaspassed
"Min"
3938292Rev1:19.04.2017.KJK
Wereservetherighttochangetechnicaldatawithoutnotice.http://www.ensy.no Side8
Iffaultylightthenbothdownlightandtransformerreplacedwithnewparts.
OriginalLEDlightthatisinsertedfromfactory
Ensyartno:
2604552DownLightLED5Wwithwhitesocket
andtransformer
2604562DownlightLED5Wwithblacksocketand
transformer
Replacementorwashingthefilterinthekitchenhood.
Releasefromtheframebypushingthelocktothe
middleofthefilterandtilteddown.Thefiltercanbe
washedinsoapywater.Mustbecompletelydrybefore
itismountedinplaceagain.Ifthefiltermaterialis
damageditmustbeorderedneworiginal.
(Ensyart
no:2700812)
3938292Rev1:19.04.2017.KJK
Wereservetherighttochangetechnicaldatawithoutnotice.http://www.ensy.no Side9
Mainmenu
1.ControlButtonindicatorforfan.
2.ControlButtonindicatorsetpoint.
3.ControlButtonindicatorinformation.
4.ControlButtonindicatorsettings.
Overviewofcontrolpanel
Themainscreenconsistsof,fromtop,left:
TimeIndication,hour,minute
Timer,Weeklyschedule(ifprogrammed)
Reheatingcoil(ifconnected)
Temperaturereadings,Outdoor/Indoor
Statusairflowfanspeedsetting
OFFMINNORMorMAX
Temperaturesetpoint,15‐21°C
Reheatingcoil(hererefersactiveelement)
RotaryexchangerIndicator‐(hererefers
activerotarywheel)
Indicatorsinthemenuscreen:
"Sun"indicatesthattherotorhas
stopped,theairhandlingunitisin
thesummeroperationmode.
"Snowflake"lowtemperature
indicatesthattheairhandlingunit
isindefrostingmode.
"Steamingpot"andblinkingfan
bladesindicatesthatthekitchen
exhaustisactivated.
"Timer"andthecountdownofthe
fansymbolindicatethattheforced
ventilationisenabled.
From10upto240minutes
"Away"indicateswhen
thefeature
isenabled,thisfeaturewilloverride
timer.
"Clockoverthefansymbol"
indicatesthatthetimerisactivated.
Co2overthefansymbol"indicates
thatthecarbonsensorisactivated.
"Exclamationpoint"indicatesthat
moisturerecordedoverthesensor
ishigherthanthesetvalue.
Mayalsoindicatethatthemotion
sensorisactivatedifconnectedon
D2signaloutput.
Thissymbolindicatesthatthe
rotaryheatexchangerisactivated
andwillberotated.
ControlButton1. 2. 3. 4.
3938292Rev1:19.04.2017.KJK
Wereservetherighttochangetechnicaldatawithoutnotice.http://www.ensy.no Side10
1.Fanspeed
Ventilationunithasthreeoptionsforchoiceof
airflow.
Min,NormalandMax.
Forprogrammingofvalueswithineachstep,
see4.5.1.3Usingthecontrolbutton1,and‐/
+buttonscanchangebetweenthepre
programmedselections.
1.1Fanboost
Forcedventilation,fanspeedincreasestomax
speed.(Meanstothespeedthatissetin
menu4.5.1.3.)Thefunctionisforuseifhigh
humidityinbathroomsandlaundryroom.
Forcedventilationcanbeactivatedwith
button
then
Intervaladjustablefrom10‐240minwith+
and
Thispictureshows10minforcingtime,but
notactivated.
Toactivatethefanboostuse
controlbutton4.
YoucanseethatthefanarerunningwithMax
speedandtheclockwillstartcountdown.
Youcaneasydeactivatethefanboostagain
beforethecountdownautomaticallystopsit.
Firstcontrolbuttom1
andthen4.
Thisfeaturecanalsobeoperatedwithan
externalpulseswitch.Theswitchisplacedin
thebathroomoradjacentrooms.Connected
tocontactD1intopoftheventilationunit.
(Lookatpage23inthismanual.)
IfthisoptionviaD1isintendedforuseagainst
woodstoveor
fireplacethenitis
recommendedthatMaxspeedunderFan
controlinmenu4.5.1.3.issettoSupply100%
andadjustExtracttobe80to85%.(Lookat
page10inthismanual)
2.Temperature
Choosefrompreprogrammedtemperature
settingssetpointbetween15‐21°C.Setting
ischangedbyoperatingtheswitchbuttons
below‐/+symbols.
HeatingelementcanherebesetONorOFF
byoperatingtheswitchbutton4inthis
screen,butonlyifheaterisconnected.
(Toseeifheatingcoilisconnectedor
disconnected,see4.5.1.1Heater)
Indicatorforactivatedheatingcoil.
Smallpictureshownotactivated.
3938292Rev1:19.04.2017.KJK
Wereservetherighttochangetechnicaldatawithoutnotice.http://www.ensy.no Side11
3.Information.
3.Information/3.1.Alarms
Whenalarmyoucanfindasourceoferror
here,aswellasinfoonhowthealarmisreset.
(Seepages29and30inthismanual)
3.Information/3.2Programversion
Informationaboutthesoftware
version.Thisinformationmustbeprovidedto
servicepersonnelatthefailureoftheunit.
3.Information/3.3.Generalinfo
Hereyoucanseedefrostmodethathas
beenchosen.
(See4.5.1.9ifyouwanttochangemode.)
4.Preferences
Tonavigatewithinthevarioussubmenus
whenusingthecontrolbuttonsbelowtheup/
downcursorkeythatdisplaysonthedisplay.
4.Preferences/4.1Time/date
SettingmenuforTime/date.Thissettingis
importantsincetheinformationformingthe
basisfortheweeklyschedulefunctionifthisis
tobeactivated.Alsoforthefilteralarm
functionitisneeded.
3938292Rev1:19.04.2017.KJK
Wereservetherighttochangetechnicaldatawithoutnotice.http://www.ensy.no Side12
4.Preferences/4.2Weeklyschedule
ProgrammingoftheWeeklyschedule,fan
speedandtemperaturesetpoint.Hereitcan
beprogrammedfortwoperiodseachday.Ex.
day‐night.
Everydaymustbeprogrammedindividually.
Monday‐aperiodoftime,selectthestart
time.Toactivatetheperiod,X‐overperiod
numberisremoved,usethe/+keys.
Useentertomovebetweenthedifferent
fields.
Chooseairflow(fanspeed)Speeddialing‐
MINwhenonefanbladeontheindicatoris
black.NORM=twoblackfanbladesonthe
indicator.MAXspeed=threeblackfanblades
ontheindicator.
Selectthedesiredsupplyairtemperatureyou
wantduringtheperiod.Settingsbetween15‐
21°C.
Ifweeklyschedulelookssomethinglike
thiswithoutanyreasonthenyoumust
punchinallthedataagain.
Itdonothelptoupdatesoftware.
4.Preferences/4.3Filter
Settingthetimeintervalforfilterchange,
currentchoicesare6,9or12months.Make
yourchoicesbyusingthecursorkeys+/.
Alarmresetelapsedperiodbypressingthe
menubutton4,under"FilterOK"
4.Preferences/4.4AdjustScreen
Adjustingthecontrastandcoloronthe
display.
Youcanalsoadjusthowlongitshouldbelight
inthedisplayaftertheoperation.
4.Preferences/4.5Setup
Toproceed,usePINcode1000
Press
+oncetillitshows1000in
display.Thenpress4timeson
Thenpressbutton3forOK4.5.1
Starttime Stoptime
Fanspeed
Activationoftheperiod.Herenotactive
3938292Rev1:19.04.2017.KJK
Wereservetherighttochangetechnicaldatawithoutnotice.http://www.ensy.no Side13
4.5.1Setup
4.5.1.1Heater
Turningon/offthereheatingcoil,usethe
minusorplusbuttontochangesettings.
4.5.1.2Coolingrecovery
Activationofthecoolingrecovery:
Itispreprogrammedtwooptionsforuse
whentheoutsidetemperatureishigherthan
theindoortemperature,heatrecoverysystem
willactivatethefunctionstartandsupplyair
willbecooledbyexhaustair.Engagement
whentheoutdoortemperatureis2°Cor3°C
higherthanroomtemperature.Use
button4
tochangesettingforOff.Press+toactivate
(On).Usebutton4tochangesettingfor2°C.
Press+tochangetoto3°C,ifwanted.
4.5.1.3Fancontrol
FactorysettingsforAHU200KVandKHSLIM
youcanseeinnextpicture.
Theinstallercanadjustthesesettingssothat
itisadequatelybalancedventilation.
4.5.1.4Co2control
IftheunitshallbeconnectedCO²controlthen
connectittoC0²connectorontopoftheunit.
(Seepage24inthismanual).
Menuforenabling/disablingofCO²control.
ScrolltoOffandpress+toactivate.On
Hereyoupreprogrammedwantedppmvalue
andtheboostspeedforthefans.
Note:Togetbalancedventilationisa
prerequisitethatSupplyandExtractairfan
hasthesamevalueastheMAXvalueunder
4.5.1.3
3938292Rev1:19.04.2017.KJK
Wereservetherighttochangetechnicaldatawithoutnotice.http://www.ensy.no Side14
4.5.1.5Cookerhood
Menuforprogrammingoffanspeedsby
activationofthekitchenhood.
SupplyandExtractairshouldhavethesame
valueastheMAXvalueunder4.5.1.3(Setto
100%fromfactory.)
4.5.1.6Externalarm
Iftheunithasbeenconnectedtoanexternal
humiditysensorormotionsensor.UsetheD2
connectorontopoftheunit.(Seepage24in
thismanual).
Note!Inorderforthisfeaturetowork,you
needtheonepoleswitchmarkedRH%ON/
OFFinsidethe
unittobesetinposition1.(See
page3inthismanualforthelocationofthis
switch).
SupplyandExtractairshouldhavethesame
valueastheMAXvalueunder4.5.1.3(Setto
100%fromfactory.)
4.5.1.7Absent
Menuforsettingthedesiredvaluesby
activatingaway/homefunction.
UsetheD3connectorontopoftheunit.(See
page24inthismanual)Functionisoperated
viaanexternalswitch.
Setvalueofthedesiredtemperaturewill
showinthedisplayafteractivatingthe
function.
4.5.1.8Calibration
Menureadingofembeddedtemperature
sensors.
Thesetemperaturesensorsare
deliveredcalibratedfromthe
manufacturerandshouldnotbeattempted
changeinhere.
The«Outsideair»sensornormally
shows36°Chightertemperaature
thenthereeloutsidetemperature.Thisisdue
toheatingoftheairintheductnetworkfrom
theintakegrilleto
theintakeoftheunit
wherethesensorareplaced.
3938292Rev1:19.04.2017.KJK
Wereservetherighttochangetechnicaldatawithoutnotice.http://www.ensy.no Side15
4.5.1.9Defrost
Menuforhowtochangedefrostmodeif
temperatureislowandhumidityisheight.
Fromthestartupmenuyoucanseewhich
defrostmodetheunitissetin.
TheunitissetinmodeOFFfromfactory.
Ifitisneededtochangethedefrost
modetoanothermodethenpress
button4andscrolldowntoConfiguration
withbutton3.
Pressenterbuttonandfollowprocedure
asinMenu4.5Setuptocontinue.
Pressenterbutton
DefrostmodeOFFfromfactory.
Modus1:atlowhumidity.
Defrostingfunctionstartat‐20°C.
Modus2:atnormalhumidity.
Defrostingfunctionstartat‐15°C.
Modus3:athighhumidity.
Defrostingfunctionstartat‐10°C.
Thefunctionwhendefrostingstartsisthat
eachhourthesupplyairfanstopsfor6
minutes.TheheaterEVturnsoff.Extractair
fanreducesspeedto30%andtherotary
exchangerwillrunasnormal.
Toavoidthattherotaryexchangerwillstop
whenthecyclegoesbacktonormalfunction,
thesupplyairfanwillstartupthelastminute
ofthedefrostingmodecycle.
(Supplyairfanreactsdelayedrelativetothe
controlsignalsandrotaryexchangersothat
theheaterwillnotengage untilthespeedof
thesupplyairfanhaspassed250r/min,in
normaloperation).
3938292Rev1:19.04.2017.KJK
Wereservetherighttochangetechnicaldatawithoutnotice.http://www.ensy.no Side16
4.5.1.10Displaynumber
Onthisunititisonlypossibletoconnectone
display.
Fromthismenuithastobespecifiedthatthe
controlpanelsis«Display
3938292Rev1:19.04.2017.KJK
Wereservetherighttochangetechnicaldatawithoutnotice.http://www.ensy.no Side17
Mountinginstructions.Pages17to28.
TableofContents
1.General
2.Mountingoftheunit
2.1Bracketsandgasketstoavoidvibration
2.3Ductcover
2.4Dimensionsandtechnicaldata
3.Connections
3.1Electricalconnections
3.2Ductconnections
4.Settingtheairflow
5.Alarms
1.General
Thisguideismadetoprovideinstallationanduserinstructionsregardingthecorrectinstallationof
AHU200KVSLIMandAHU200KHSLIM.
AHU200KVandKHSLIMisdesignedforheatrecoverywithairvolumesofupto200/h.The
energy
fromtheexhaustairistransferredtosupplyairthroughtherotaryheatexchangerwherethe
airstreamspasseachotherwithoutmakingcontact.
Theunithasabuiltinheaterforsupplementaryheatingofsupplyair.Humiditysensorforforced
ventilationisintegratedintoventilationunit
Theunitcan
alsoconnectadditionalequipment.Pulseswitchforcontrollingtheforcedventilation,for
example,wetroomsorbathrooms,sensorforcarbonmanagementandswitchmanagementaway/
homefunction.ControloftheseoptionsareintegratedintoAHU200KVandKH.
AHU200KVandKHSLIMissuppliedinpaintedfinish,testedandreadyforoperation.Installation,
commissioningandtuningmustbeperformedbyauthorizedpersonnelTherearealsovariantswith
hoodsinbrushedstainlesssteel.
2.Mounting
Togetherwiththeunitisdeliveredthefollowingequipment:
1.Suspensionbracketandstoppers
2.WallBracketwithvibrationdampeninggasket
3.Selfadhesivevibrationdamping
4.Accessoriesbagcontainingthenecessaryscrews
5.4pcs.plugsforconnectingadditionalequipment.
6.Partsformountingkitchenfurniturefrontdoor.
7.Controlpanel
3938292Rev1:19.04.2017.KJK
Wereservetherighttochangetechnicaldatawithoutnotice.http://www.ensy.no Side18
First,selecthowtheunitshouldbemountedsothatthepipingsystemshouldbeaseasyaspossible.
(SketchovershowsAHU200KVSLIM)
(SketchovershowsAHU200KHSLIM)
Freshair.
Supplyair.
Extractair.
Exhaustair.
Freshair.
Supplyair
Extractair.
Exhaustair.
3938292Rev1:19.04.2017.KJK
Wereservetherighttochangetechnicaldatawithoutnotice.http://www.ensy.no Side19
2.1Bracketsandvibrationgasket
Suspensionbracketscrewedontopofthe
unitasshown.
Use8pcsM5x16mm,suppliedwiththeunit.
(SketchovershowAHU200KVSLIM)
Mountthewallbracketwithvibrationgasket.
Makesurethattheedgeprotectiongasketisplaced
onthe
wallbracket.
Besurethatthevibrationgasketisintact.
Gluevibrationgaskettothebackofthe
unit,seeillustration.Approx.50mm
fromthebottomoftheunit.
Lifttheunitinplaceandensurethat
thereisnodirectcontactbetweenunit
andbuildingconstruction.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32